S4E Polaris V3 Superchiller
™
240V / 50Hz
www.lancerbeverage.com
Page 7 of 19
Hoshizaki Lancer reserve the right to change specifications without notice.
Part No: 68000206
Images are for illustration purposes only as product may vary.
No 046-3
–
7 August 2019
•
SPK2-11 version superchillers are intended for use in a non temp controlled storage
area.
•
Ensure sufficient clearance around superchiller to allow good fresh air circulation
through the condenser
–
allow at least 200mm at rear, sides and top, with the front
unobstructed.
•
Installation should only be performed by a qualified and competent technician.
3.4
Mounting Superchiller
•
Install on a flat, level surface using adjustable legs or casters (Optional).
Caution
Superchiller operational weight is 157/179kg; ensure that all
supporting structures are certified for this loading by a registered
Mechanical Engineer.
Supporting structure must be securely fixed to floors or walls.
3.5
Connecting Python
Connect Python to Superchiller and Dispenser.
Caution
NOTE: The superchiller is rated to operate with a maximum of 30m
of python connected.
Exceeding manufacturer’s ratings may cause damage to the
superchiller and void warranty.
Python Details
Recirculation Lines ½” Dia Glycol tubing
Beer Lines: Max 6-
off 3/8” Dia Beer line tubing
Beer line connections are
made on top of the tank onto John Guest 3/8” Superseal
flowbend connection.
3.6
Plumbing the Drain
The 13mm elbow exiting from the RH Pump Panel of the unit should be plumbed to a
suitable drain, installation in accordance with AS/NZS 3500.1 and AS/NZS 3500.2.
3.7
Filling Unit
Glycol - Remove superchiller lid and fill the tank with glycol/water mixture of 30% (refer to
chart in Section 5 for details) until mixture flows out of the overflow.
Water - If the unit is to be used as an ice bank, simply fill with clean water until it flows out
the overflow tube.
3.8
Electrical Connection
•
This unit is connected to the supply via a flexible cord fitted with a 3 pin plug.
•
Check the name plate on the machine for electrical supply requirements. Use only the
power supply specified on the name plate.
Warning
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
Warning
To avoid possible fatal electric shock or serious injury the
superchiller must be electrically grounded.
Electrical Connection Must Be Made In Accordance With The
Appropriate Local Codes And Regulations.
Use of an RCD is recommended.