S4E Polaris V3 Superchiller
™
240V / 50Hz
www.lancerbeverage.com
Page 15 of 19
Hoshizaki Lancer reserve the right to change specifications without notice.
Part No: 68000206
Images are for illustration purposes only as product may vary.
No 046-3
–
7 August 2019
9.
Omni Icebank Control Test
This is a test to simulate the building and erosion of the icebank; to determine if the icebank
control is operating correctly. The test assumes that all other components in the refrigeration
system (e.g. high pressure cut-out reset) are in an operational condition.
Warning
230VAC is present on PC Board.
Work should only be performed by fully trained & certified
Electrical, Plumbing & Refrigeration Technicians.
1.
Remove the ice bank probe at the PC Board.
2.
Jumper the three terminals as shown. Use a
spare male connector with wiring if available.
The compressor relay should close and
refrigeration system start.
(Simulates water covering all probes)
3.
With refrigeration system operating
(compressor relay energised) remove the
jumper from the centre terminal. Refrigeration
system should continue to operate.
(Simulates ice growth over green probe. Water
still
contacting red and black probes)
4.
Remove the remaining jumper. The
compressor relay should open and the
refrigeration system should stop.
(Simulates ice growth over the probes)