10
Installer Settings
There are a number of 'Installer Settings' that should be set on
installation.
These can be found under the 'SET UP MENU' on page 15 of the
user instructions.
The TPI Cycles setting and Optimum Start settings should be
carefully set on installation as this will affect system performance.
Clock Format
AM/PM or 24 Hour clock display - Default
setting
Daylight saving
On or Off - Default setting ON for UK Market
Standby temperature
Frost protection setting – Default setting 5°C
Upper and Lower
Default settings 30°C and 5°C
Temperature limits
TPI Cycles
This setting will change according to the
type of boiler being used - Default setting 6
For Gas boiler this setting should be 6
cycles per hour
For Oil boilers this setting should be 3
cycles per hour
For Electric panel heaters this should be 12
cycles per hour
Optimum Start
On or Off – Default setting Off
AM/P