6 DIAGNOSTIC LED INDICATORS
LED Indicators
Status
Power
OK (
)
MS
NS
V+ Power Applied
ON
ANY
ANY
ANY
Self-Test FAIL
ON
ANY
OFF
ANY
Self-Test PASS
ON
ON
ANY
ANY
Network Normal
ON
ON
ON
ON
Duplicate Net ID
ON
ON
ON
OFF
Configuration Mismatch
ON
Flash (1Hz)
ON
Flash (1Hz)
OCS Stop Mode/Communication Timeout
ON
ON
ON
Flash (1Hz)
OCS Run Mode
ON
ANY
ANY
ANY
Onboard I/O Fault
ON
OFF
ON
ON
Invalid Dynamic Configuration
ON
Flash (1Hz)
ON
ON
Power Up/ Waiting to be Configured
ON
ON
Flash (1Hz)
Flash (1Hz)
LED Indicators for Individual I/O Channels
I1
Digital Input-1 active
I2
Digital Input-2 active
Q1
Digital Output-1 active
Q2
Digital Output-2 active
AI1
Analog Input Active *
AQ1
Analog output Active
NOTE
: Channel LED will be in OFF state if it is disabled
from Cscape configuration
*NOTE
:
•
LED will be ON during Normal operations.
•
Analog Input channel configured as mA, Volts or
mV LED will be OFF till the input signal is 0+0.2%
•
Analog Input channel configured as PT100,
PT1000 LED will be OFF if open circuit is detected,
LED will be ON during Normal operation
•
Analog Input channel configured as Thermocouple
Input LED will be ON if the channel is Enabled.