technical specifications continued....
2
CAN TABLE
CAN Pin Assignments
PIN
SIGNAL
DESCRIPTION
1
CAN_H
CAN Data High
2
CAN_L
CAN Data Low
3
GND
Ground
4
Reserved
Do Not Connect
5
Reserved
Do Not Connect
6
CAN_SHLD
Shield
7
GND
Ground
8
VIN Passthrough
Do Not Connect
page 2 of 8
1.5 Flexible Inputs - Digital / Analog
Number of Channels
2 (Digital or Analog)
Configured as Analog I/O
Analog Input Ranges
4-20mA / 0-10V
Analog Input Data Ranges
0~4000 / -2000~2000 /
0~1000 / 0~32000
Alarm
Value / Register
Configured to Digital Inputs
Digital Input Ranges
24V / 12V / 5V / Custom
Input Voltage Range
0 - 24VDC
Absolute Max Voltage
+/- 30VDC
Input Impedance
10k
Ω
Custom Digital Input Ranges
Threshold ON
Threshold OFF
OFF to ON Response
1ms
ON to OFF Response
1ms
Digital Input Active Mode
Positive / Negative Logic
Connector Type
Phoenix Contact 2202234
1.6 Analog Outputs
Number of Channels
2 Analog
Analog Outputs
0-20mA / 4-20mA / 0-10V
Analog Output Data Ranges
0~4000 / -2000~2000 /
0~1000 / 0~2000/ 0~32000
Nominal Resolution
12 Bit
Minimum 10V Load
500
Ω
Maximum Current Load
500
Ω
Analog Output Halt State
Current / Minimum /
Maximum / Median