MAN0974-14-EN_XL7_XL7P_UM
July 6, 2022
Page 69 | 199
If communications are successful, the message line should show “USB (COM8)” for this example, and an
(R) should follow the Target number. For more information on the status bar, see the
section.
Local ID and Target ID Match
If the controller is not communicating, ensure the target ID is set correctly. If not, set the target ID of the
controller in Cscape or on the unit. The
Target ID
allows directing communications to a particular unit
when multiple units are connected via a CsCAN network. Units without CsCAN network ports respond to
any network ID and do not require the ID to be configured.
To check or change the ID on the XL7/XL7 PRIME OCS, press the System Menu key.
The first item in the menu is
Set Networks
. Pressing
Enter
allows the ID of the unit to be viewed or
modified.
To change the Target ID of Cscape use the
Controller
→
Set Target Network ID
dialog.
When connected directly to the controller to which Cscape
communications are required, the
Local ID and the Target
ID should match.