MAN0964-14-EN_XL4_XL4P_UM
N o v e m b e r 1 0 , 2 0 2 1
P a g e 51 | 194
NOTE: Note every OCS supports every %SR.
Table 6.2
–
%SR Registers
–
Master %SR Table
Register
Default I/O
Name
Description
Min-Max
Values
Program
(Read/Write)
Display
(Read/Write)
%SR1
USER_SCR
User Screen Number
*Excludes RCC Units
0 to 1023
Read/Write
Read/Write
%SR2
ALRM_SCR
Alarm Screen Number (0=none)
*Excludes RCC Units
0 to 1023
Read Only
Read Only
%SR3
SYS_SCR
System Screen Number
1 = Main System Menu
2= Set Network ID, Network Status,
(%SR29)
3= Set Network Baud (%SR30)
4= Set Contrast (%SR32)
5= View OCS Status
6= View OCS Diagnostics
7= View I/O Slots
8= Set Function Key Mode (%SR33)
9= Set Serial Ports (%SR34)
10= Set Time/Date (%SR44-%SR50)
11= Set Beeper (%SR183)
12= Set Screen (%SR185)
13= Removable Media
14= View Protocols
15= IP Address (ETN I/O Board)
16= Fail Safe System
17= Backup / Restore Data
18= Enable AutoRun
19= Enable AutoLoad
20= Clone Unit -
21= Touch Calibration
24= License Details
*Excludes RCC Units
0 to 24
Read/Write
Read/Write
%SR4
SELF_TST
Self-Test Results
Read Only
Read Only
%SR4.1
Self-Test Results
–
BIOS Error
Read Only
Read Only
%SR4.2
Self-Test Results
–
Engine Error
Read Only
Read Only
%SR4.3
Self-Test Results
–
Ladder Error
Read Only
Read Only
%SR4.4
Self-Test Results
–
RAM Error
Read Only
Read Only
%SR4.5
Self-Test Results
–
Duplicate ID Error
Read Only
Read Only
%SR4.6
Self-Test Results
–
Bad ID Error
Read Only
Read Only
%SR4.7
Self-Test Results
–
I/O Configuration
Error
Read Only
Read Only
%SR4.8
Self-Test Results
–
Bad Network Error
Read Only
Read Only
%SR4.9
Self-Test Results
–
Bad Logic Error
Read Only
Read Only
%SR4.10
Self-Test Results
–
Bad Clock Error
Read Only
Read Only
%SR4.11
Self-Test Results
–
DeviceNet Error
Read Only
Read Only
%SR4.12-.16
Reserved
%SR5
CS_MODE
Control Station Mode
0= Idle
1= Do I/O
2= Run
3= Online Change
*Supported in Linux and XL+ units only
0 to 3
Read Only
Read/Write