TSV1-3 THERMOSTATIC SHOWER VALVE 

WITH AUTOMATIC DIVERTER VALVE (T605A & variants) 

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS 

Installation requirements and specifications 

Approvals 

The TSV1-3 Thermostatic Shower Valve within the panel has been independently tested by the WRc and 
approved to all the requirements of NHS Model Engineering Specifications D08 Thermostatic Mixing Valves 
(Healthcare Premises) to the following designations and for the following applications: 
 

HP-S 

Shower with supply pressures of 1 

– 5 bar and unrestricted flow rate 

LP-S 

Shower with supply pressures of 0.2 

– 1 bar and unrestricted flow rate 

 

Supply Water Pressure requirements 

The minimum water pressure required to achieve a satisfactory spray at each spray-head is a dynamic head of 
20m (30 psi, 2 bar) measured from the spray head.   

Note that dynamic head is measured with the water running. 

The maximum recommended supply pressure is 6 bar (90 psi, 60m head) for hot and 10 bar (150 psi, 100m 
head) for the cold. 

 

Supply Water Temperature Requirements 

Max. Hot Water Temperature*   

65°C 

Min. Hot Water Temperature#   

55°C 

Max. Cold Water Temperature#   

20°C 

A minimum temperature differential of 5°C should exist between the mixed water temperature and each inlet 
temperature. 

 
Note that requirements marked * originate from WRAS approval of non-metallic components, and those marked 
# originate from HTM 04:01, Part A, 2007. 

 

Temperature Adjustment Range 

The mixed water temperature can be adjusted from cool through to a top limit (which can be preset during 
installation 

– factory set to approx. 41°C - with full anti-scald protection throughout the range). 

 

Water and Energy Conservation 

The TSV1 range of shower panels is fitted with a flow regulator at the shower outlet to reduce the flow rate and 
conserve water and energy.  The drawing at the end of this document provides information for accessing the 
flow regulator for removal or replacement. 

Every  HORNE  TSV1-3  is  supplied  with  an  integral  WRAS  approved  single  check  valve  and  integral  large 
surface area strainer.  The Shower Panel terminates in 15mm copper pipes for hot and cold supplies.   The hot 
pipe is on the left, cold on the right, when viewed from the user’s perspective. 

 

Содержание TSV1-3

Страница 1: ...mmended supply pressure is 6 bar 90 psi 60m head for hot and 10 bar 150 psi 100m head for the cold Supply Water Temperature Requirements Max Hot Water Temperature 65 C Min Hot Water Temperature 55 C M...

Страница 2: ...e wall that is on the required centreline for the casing 15mm below the line of the top of the casing for the support screw see Fig 1 2 Install the Support Screw Drill a 7 0mm dia hole in the wall and...

Страница 3: ...el to the Wall Carefully re hang the panel on the temporary screw and then attach it firmly to the wall by the four other screws Put the four supplied screw bushes in the mounting holes in the panel a...

Страница 4: ...anel is replaced prior to connecting up the supply pipes Connect the hot water supply to the left hand inlet and cold water to the right hand inlet see Fig 5 DO NOT OPEN THE WATER SUPPLIES AT THIS STA...

Страница 5: ...th the casing through the lower end cap Using the supplied 4mm hex key isolate the cold and hot water supplies at the low level servicing valves Remove the strainer cap and strainer basket and screw i...

Страница 6: ...st the temperature control and check for any water leaks upstream of the TSV1 3 valve Make good any leaks found The valve is now ready for commissioning Note that if the controls enclosure and shower...

Страница 7: ...lies may have to be connected before the pre plumbed enclosure is attached to the wall Accordingly point 7 on the attached installation instructions Connect the Supply Pipes should be performed before...

Страница 8: ...not been altered and to ensure user safety If the maximum temperature requires adjustment remove the temperature control cap using a sharp blade or the tip of a penknife and adjust the small slotted...

Страница 9: ...h contain O rings and or the thermostatic element are available Smear all O rings with silicon grease oil prior to installing them Torque the TSV1 3 cover to 13 Nm 10 lbft This is to prevent the user...

Страница 10: ...k valves and strainer basket should be replaced It is not possible to satisfactorily remove the check valves itself from the inlet elbow and should not be attempted The shower valve body must be remov...

Страница 11: ...be undetectable in normal use and only become apparent when disruption occurs in the hot or cold water supply temperatures or pressures The frequency of in service testing depends upon the condition...

Страница 12: ...Horne Engineering Ltd Issue 4 June 2016 12 Insert DRAWING 10393 showing position of Flow Reg...

Страница 13: ...Horne Engineering Ltd Issue 4 June 2016 13...

Страница 14: ...ax Mixed Water Temp during CW Isolation test C Mixed Water Temp on restoration of CW Supply C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments In...

Страница 15: ...C Note MWT should return within 2 degrees of set temp and be no greater than 43C after this test Comments Recommended Date of Next In Service Test In Service Testing Record Establishment Location of V...

Страница 16: ...neering Ltd Issue 4 June 2016 16 Brochure Ref L 180 Horne Engineering Ltd PO Box 7 Rankine Street Johnstone SCOTLAND PA5 8BD Tel 44 0 1505 321455 Fax 44 0 1505 336287 Email Technical horne co uk www h...

Отзывы: