background image

VR9105V, F AND VR9205V, F DIRECT IGNITION GAS CONTROL WITH INTEGRATED 1:1 REGULATOR

69-2471EF—01

6

STARTUP AND CHECKOUT

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury 
or death.

Perform Gas Leak Test every time work is done on 
a gas system.

IMPORTANT

Do not spray soap and water solution on the gas 
control. Do not use an excessive amount of soap 
and water solution to perform the gas leak test. 
These can damage the control.

Gas Leak Test

1.

Apply rich soap and water solution onto pipe con-
nections. Bubbles indicate a gas leak.

2.

If a leak is detected, tighten the pipe connections.

3.

Light the main burner. Stand clear of the main 
burner while lighting to prevent injury caused from 
hidden leaks that could cause flashback in the 
appliance vestibule.

4.

With the main burner in operation, apply rich soap 
and water solution onto the pipe joints (including 
bushings) and the control inlet and outlet.

5.

If another leak is detected, turn the gas control to 
off, tighten the joints and pipe connections.

6.

Replace the part if a leak cannot be stopped.

Turn On System and Main Burner

Follow appliance manufacturer instructions or turn 
thermostat up to call for heat.

Adjustment

Do not adjust regulator if cap is sealed.

Refer to the instructions below for making adjustments to 
the offset or 1:1 gas/air regulator setting if the cap is not 
sealed.

IMPORTANT

1. Do not exceed input rating stamped on appli-

ance nameplate or manufacturer's recom-
mended burner orifice size(s). Make certain 
primary air supply to main burner is properly 
adjusted for complete combustion. Follow appli-
ance manufacturer instructions.

2. IF CHECKING GAS INPUT BY CLOCKING GAS 

METER: Make certain there is no gas flow 
through the meter other than to the appliance 
being checked. Other appliances must remain 
off with the pilots extinguished (or deduct their 
consumption from the meter reading). Convert 
flow rate to Btuh as described in form 70-2602, 
Gas Controls Handbook, and compare to Btuh 
input rating on appliance nameplate.

3. IF CHECKING GAS INPUT WITH MANOME-

TER: Make sure the plug is not connected to the 
coil connector before removing outlet pressure 
tap plug to connect manometer (pressure 
gauge). Also pull out the plug from coil connector 
when removing the gauge and replacing pres-
sure tab plug. Before removing inlet pressure tap 
plug, shut off gas supply at the manual valve in 
the gas piping to the appliance or, for LP, at the 
tank. Also shut off gas supply before disconnect-
ing manometer and replacing plug. Repeat Gas 
Leak Test at plug with main burner operating.

Pressure Tap and Pressure Port

The combination gas control is provided with 1/8-in. NPT 
pressure tap plugs. The 1:1 regulator is provided with M5 
threaded hole or 6 mm O.D. fitting connection (optional) to 
sense appliance air pressure. Fitting connection accepts 
3/16 in. I.D. rubber hose.

CAUTION

To ensure a safe closing of the valves, it is 
essential that power supplied to the gas valve 
be disconnected.

1:1 Gas/Air Regulator/Offset adjustment 
on outlet pressure

• If cap screw is not sealed, remove cap screw to 

expose adjustment screw.

• Check gas supply pressure to the appliance with the 

valve flowing gas at max using a pressure gauge 
connected to the inlet pressure tap.

• Control the fan to produce the air pressure difference 

stated by the appliance manufacturer.

• Energize the gas valve in order to have gas supplied to 

the burner. The main burner should ignite within 3 
seconds.

• Turn the outlet pressure adjustment screw slowly until 

the desired pressure is obtained. Turn adjustment 
screw counter clockwise to increase or clockwise to 
decrease outlet pressure.

• Replace and tighten cap screw and pressure tap plugs.

Содержание VR9105F

Страница 1: ...uctions 69 2484EF Valve capacities are shown in Table 1 For suffix letter designation see Table 2 a Capacity based on 1000 Btu ft3 0 64 sp gr natural gas at 1 in wc pressure drop 37 3 MJ m3 0 64 sp gr natural gas at 0 25 kPa pressure drop b Minimum and Maximum regulation is at the max fire Minimum regulation at low fire is 18 KBtu h at 0 7 in WC outlet pressure a For detailed information about Ven...

Страница 2: ...cial steps may be required to prevent nuisance shutdowns and control failure due to frequent cycling severe environmental conditions related to moisture corrosive chemicals dust or excessive heat These applications require Honeywell Combustion Engineering review contact your Honeywell Sales Representative for assistance Review the following conditions that can apply to your specific installation a...

Страница 3: ... shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for y...

Страница 4: ...to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe...

Страница 5: ...former and other controls as required 3 Connect the control circuit to the gas control terminals 4 Ensure combustion chamber is free of gas before startup 5 Adjust thermostat heat anticipator to the rating stamped on valve operator Electrical Connection VR9105V F and VR9205V F can be connected to any standard direct ignition control with 110 Vac output by using rectifier plug 45900441 039 or 24 Va...

Страница 6: ...er than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOME TER Make sure the plug is not connected to the coil connector before removing o...

Страница 7: ...one complete cycle to make sure all controls operate properly MAINTENANCE Under normal circumstances no maintenance or service is required WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassemble the gas control it contains no replaceable components Attempted disassembly repair or cleaning can damage the control resulting in gas leakage SERVICE WARNING F...

Страница 8: ...formation below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the appliance does not...

Страница 9: ...sont illustrées dans le Tableau 1 Pour le suffixe de référence consulter le Tableau 2 a Capacité basée sur 1000 Btu pied3 gravité spécifique de 0 64 gaz naturel chute de pression de 1 po c e 37 3 MJ m3 gravité spécifique 0 64 gaz naturel et chute de pression de 0 25 kPa b Régulation minimum et maximum à combustion maximum La régulation minimum à basse combustion est de 18 KBtu h à une pression de ...

Страница 10: ...pes spéciales sont requises pour éviter les coupures intempestives et les pannes de régulateur dues à des mises en marche et arrêts fréquents des conditions environnementales rigoureuses liées à l humidité des produits chimiques corrosifs de la poussière et une chaleur excessive Ces applications nécessitent d être révisées par le département d ingénierie de la combustion de Honeywell contacter le ...

Страница 11: ...ante maximum autour du régulateur ne dépasse pas les conditions de température de fonctionnement du régulateur Si l appareil fonctionne à de très hautes températures utiliser un isolant une protection et assurer une circulation d air adéquate pour protéger le régulateur Une isolation ou une protection adéquate doit être fournie par le fabricant de l appareil vérifier qu une circulation d air adéqu...

Страница 12: ...n ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l eau à la vapeur ou avec des produits chimiques et pour éviter l accumu...

Страница 13: ...structions générales ci dessous Si ces instructions diffèrent de celles du fabricant de l appareil suivre celles du fabricant RÉGULATEUR À GAZ RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU 76 MM 3 PO MINIMUM 76 MM 3 PO MINIMUM COLONNE MONTANTE RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE 76 MM 3 PO MINIMUM COLONNE M...

Страница 14: ...pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé appliquer une solution savonneuse épaisse sur les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas être réparée ...

Страница 15: ... allumeur à incandescence immédiatement ou suite au prébalayage Voir les spécifications du module d allumage direct 4 Minuter la durée de l étincelle Voir les spécifications du module d allumage direct 5 Après le verrouillage du module connecter l obturateur au connecteur de serpentin et s assurer qu il n y a pas de débit de gaz vers le brûleur principal 6 Régler le thermostat à une température in...

Страница 16: ... chauffage Les informations ci dessous décrivent une application typique mais les régulateurs spécifiques utilisés et les procédures décrites dans les instructions du fabricant de l appareil peuvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche STOP Lire les avertissements ci dessus avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pa...

Отзывы: