VR9105V, F AND VR9205V, F DIRECT IGNITION GAS CONTROL WITH INTEGRATED 1:1 REGULATOR

69-2471EF—01

4

Converting Gas Control from 
Natural Gas to LP Gas (or LP Gas 
to Natural Gas)

WARNING

Fire Or Explosion Hazard.
Can cause property damage, severe injury 
or death.

VR9105V, F and VR9205V, F cannot be converted 
between LP or Natural gas. To convert, see 
appliance manufacturer for recommendations.

Install Bushings To Control

If bushings are being installed on the control, mount them 
as follows:

Bushings

1.

Remove the seal over the control inlet.

2.

Apply a moderate amount of good quality pipe 
compound to the bushing, leaving two end threads 
bare. On an LP installation, use compound that is 
resistant to LP gas. Do not use Teflon tape.

3.

Insert the bushing in the control and carefully thread 
the pipe into the bushing until tight. 

Complete the instructions below for installing the piping, 
installing the control, connecting the wiring. Make sure the 
leak test you perform on the control after completing the 
installation includes leak testing the bushings.

Location

The gas controls are mounted in the appliance vestibule 
on the gas manifold. If this is a replacement application, 
mount the gas control in the same location as the old 
control.

Locate the combination gas control where it cannot be 
affected by steam cleaning, high humidity, or dripping 
water, corrosive chemicals, dust or grease accumulation 
or excessive heat. 

To assure proper operation, follow these guidelines:

• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom 

to avoid exposure to flooding or splashing water.

• Assure the ambient temperature does not exceed the 

ambient temperature ratings for each component.

• Cover gas control if appliance is cleaned with water, 

steam, or chemicals or to avoid dust and grease 
accumulation.

• Avoid locating gas control where exposure to corrosive 

chemical fumes or dripping water are likely.

Install Piping to Control

All piping must comply with local codes and ordinances or 
with the National Fuel Gas Code (ANSI Z223.1, 
NFPA No. 54), whichever applies. Tubing installation must 
comply with approved standards and practices.

1.

Use new, properly reamed pipe that is free from 
chips. If tubing is used, make sure the ends are 
square, deburred and clean. All tubing bends must 
be smooth and without deformation.

2.

Run pipe or tubing to the control. If tubing is used, 
obtain a tube-to-pipe coupling to connect the tubing 
to the control.

3.

Install a sediment trap in the supply line to the 
control. See Fig. 4.

Install Control

1.

Mount with the coils 90 degrees from the vertical 
upright position. See Fig. 3.

2.

Mount so the gas flow is in the direction of the arrow 
on the bottom of the control.

3.

Thread the pipe the amount shown in Table 3 for 
insertion into control or adapters. Do not thread 
pipe too far. Valve distortion or malfunction can 
result if the pipe is inserted too deeply.

4.

Apply a moderate amount of good quality pipe 
compound (do not use Teflon tape) only to the pipe, 
leaving two end threads bare. On LP installations, 
use a compound resistant to LP gas. See Fig. 5.

5.

Remove the seals over the control inlet and outlet 
before installing pipe.

6.

Connect the pipe to the control inlet. Use a socket 
on the hex end of the control. See Fig. 6.
Do not use the wrench on a Venturi Manifold.

a

All dimensions are in inches.

b

OK when bushings are used.

Air pressure connections

The air pressure difference must be connected to the air 
pressure connection. See Fig. 1 and Fig. 2.

Fig. 4.  Sediment trap installation.

Table 3. NPT Pipe Thread Length.

a

Pipe Size

Thread Pipe 

This Amount

Maximum Depth Pipe can 

be Inserted into Control

3/8

b

9/16

3/8

1/2

3/4

1/2

GAS

CONTROL

GAS

CONTROL

HORIZONTAL

DROP

PIPED

GAS

SUPPLY

PIPED

GAS

SUPPLY

3 IN.

(76 MM)

MINIMUM

3 IN.

(76 MM)

MINIMUM

RISER

GAS

CONTROL

TUBING

GAS

SUPPLY

HORIZONTAL

DROP

3 IN.

(76 MM)

MINIMUM

RISER

M3077A

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING

END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 

FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

Содержание VR9105F

Страница 1: ...uctions 69 2484EF Valve capacities are shown in Table 1 For suffix letter designation see Table 2 a Capacity based on 1000 Btu ft3 0 64 sp gr natural gas at 1 in wc pressure drop 37 3 MJ m3 0 64 sp gr natural gas at 0 25 kPa pressure drop b Minimum and Maximum regulation is at the max fire Minimum regulation at low fire is 18 KBtu h at 0 7 in WC outlet pressure a For detailed information about Ven...

Страница 2: ...cial steps may be required to prevent nuisance shutdowns and control failure due to frequent cycling severe environmental conditions related to moisture corrosive chemicals dust or excessive heat These applications require Honeywell Combustion Engineering review contact your Honeywell Sales Representative for assistance Review the following conditions that can apply to your specific installation a...

Страница 3: ... shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for y...

Страница 4: ...to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe...

Страница 5: ...former and other controls as required 3 Connect the control circuit to the gas control terminals 4 Ensure combustion chamber is free of gas before startup 5 Adjust thermostat heat anticipator to the rating stamped on valve operator Electrical Connection VR9105V F and VR9205V F can be connected to any standard direct ignition control with 110 Vac output by using rectifier plug 45900441 039 or 24 Va...

Страница 6: ...er than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOME TER Make sure the plug is not connected to the coil connector before removing o...

Страница 7: ...one complete cycle to make sure all controls operate properly MAINTENANCE Under normal circumstances no maintenance or service is required WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassemble the gas control it contains no replaceable components Attempted disassembly repair or cleaning can damage the control resulting in gas leakage SERVICE WARNING F...

Страница 8: ...formation below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the appliance does not...

Страница 9: ...sont illustrées dans le Tableau 1 Pour le suffixe de référence consulter le Tableau 2 a Capacité basée sur 1000 Btu pied3 gravité spécifique de 0 64 gaz naturel chute de pression de 1 po c e 37 3 MJ m3 gravité spécifique 0 64 gaz naturel et chute de pression de 0 25 kPa b Régulation minimum et maximum à combustion maximum La régulation minimum à basse combustion est de 18 KBtu h à une pression de ...

Страница 10: ...pes spéciales sont requises pour éviter les coupures intempestives et les pannes de régulateur dues à des mises en marche et arrêts fréquents des conditions environnementales rigoureuses liées à l humidité des produits chimiques corrosifs de la poussière et une chaleur excessive Ces applications nécessitent d être révisées par le département d ingénierie de la combustion de Honeywell contacter le ...

Страница 11: ...ante maximum autour du régulateur ne dépasse pas les conditions de température de fonctionnement du régulateur Si l appareil fonctionne à de très hautes températures utiliser un isolant une protection et assurer une circulation d air adéquate pour protéger le régulateur Une isolation ou une protection adéquate doit être fournie par le fabricant de l appareil vérifier qu une circulation d air adéqu...

Страница 12: ...n ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l eau à la vapeur ou avec des produits chimiques et pour éviter l accumu...

Страница 13: ...structions générales ci dessous Si ces instructions diffèrent de celles du fabricant de l appareil suivre celles du fabricant RÉGULATEUR À GAZ RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU 76 MM 3 PO MINIMUM 76 MM 3 PO MINIMUM COLONNE MONTANTE RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE 76 MM 3 PO MINIMUM COLONNE M...

Страница 14: ...pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé appliquer une solution savonneuse épaisse sur les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas être réparée ...

Страница 15: ... allumeur à incandescence immédiatement ou suite au prébalayage Voir les spécifications du module d allumage direct 4 Minuter la durée de l étincelle Voir les spécifications du module d allumage direct 5 Après le verrouillage du module connecter l obturateur au connecteur de serpentin et s assurer qu il n y a pas de débit de gaz vers le brûleur principal 6 Régler le thermostat à une température in...

Страница 16: ... chauffage Les informations ci dessous décrivent une application typique mais les régulateurs spécifiques utilisés et les procédures décrites dans les instructions du fabricant de l appareil peuvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche STOP Lire les avertissements ci dessus avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pa...

Отзывы: