STARTUP AND CHECKOUT

TURN ON GAS CONTROL

Rotate the gas control knobs counterclockwise 

to

ON.

TURN ON MAIN BURNER

Follow instructions provided by appliance manufacturer

or turn up thermostat to call for heat.

CHECK GAS INPUT TO MAIN BURNER

CAUTION

1. Do not exceed the input rating stamped on the

appliance nameplate, or manufacturer recom-
mended burner orifice pressure for the size
orifice(s) used. Make certain the primary air
supply to the main burner is properly adjusted
for complete combustion (refer to the appli-
ance manufacturer instructions).

2. WHEN CHECKING GAS INPUT BY

CLOCKING THE GAS METER:
• Make sure that the only gas flow through

the meter is that of the appliance being
checked.

• Make certain that other appliances are turned

off with pilot burners extinguished (or de-
duct that gas consumption from the meter
reading).

• Convert flow rate to Btuh as described in

the Gas Controls Handbook, form 70-2602,
and compare to the Btuh input rating on
the appliance nameplate.

Standard-Opening and Slow-Opening Pressure
Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With the main burner operating, check the gas con-

trol flow rate using the meter clocking method.

3. If the desired gas flow rate is not as stamped on the

control, check the gas control inlet pressure using a ma-
nometer at the inlet pressure tap. Regulators are fixed. They

are not adjustable. If the inlet pressure is in the normal
range (refer to Table 4), replace the entire gas control.
Otherwise, take the necessary steps to provide proper gas
pressure to the gas control.

NOTE: Factory set outlet pressure is not field adjustable.

Step-Opening Pressure Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With the main burner operating, check the gas con-

trol flow rate using the meter clocking method.

3. If desired flow rate is not as stamped on the control,

check the inlet pressure using a manometer at inlet pres-
sure tap or upstream of the gas control. Regulators are
fixed. They are not adjustable
. If the inlet pressure is in the
normal range (refer to Table 4), replace the entire gas con-
trol. Otherwise, take the necessary steps to provide proper
gas pressure to the gas control.

4. Carefully check main burner lightoff at the step

pressure. Make sure the main burner lights smoothly and
without flashback to the orifice and that all ports remain
lit. Cycle the main burner several times, allowing at least
30 seconds between cycles for the regulator to resume the
step function. Repeat after allowing main burner to cool.

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Perform the safety shutdown test any time work is
done on a gas system.

NOTE: Read steps 1 through 7 below before starting, and

compare to the safety shutdown or safety lockout tests
recommended for the direct ignition (DI) module. Where
they differ, use the procedure recommended for the
module.

NOTE: Factory set outlet pressure is not field adjustable.

Factory Set Outlet Pressure

Model

Type of Gas

Nominal Inlet Pressure

Step

Full Rate

H (Slow-opening)

Natural

7.0 [1.7]

3.0 - 5.0 [0.7 - 1.2]

LP

14.0 [3.9]

8.0 - 12.0 [2.0 - 3.0]

M (Standard)

Natural

7.0 [1.7]

3.0 - 5.0 [0.7 - 1.2]

LP

14.0 [3.9]

8.0 - 12.0 [2.0 - 3.0]

P (Step-opening)

Natural

7.0 [1.7]

0.7, 0.9, 1.2, 1.7,

[0.17, 0.22, 0.30, 0.42]

3.0 - 5.0 [0.7 - 1.2]

LP

14.0 [3.9]

1.4, 2.5, 4.0, 5.5

[0.35, 0.62, 1.0, 1.4]

8.0 - 12.0 [2.0 - 3.0]

TABLE 4—PRESSURE REGULATOR SPECIFICATION PRESSURES IN IN. WC [kPa].

Содержание VR8405

Страница 1: ...t3 hour 20 3 meters3 hour Minimum capacity rated 200 feet3 hour 5 7 meters3 hour Solenoid operated dual first automatic valves open on thermostat call for heat and close when call for heat ends Diaphragm operatedsecondautomaticvalvesopen under control of the regulator and close if gas or power supply is interrupted Two position gas control knobs have ON and OFF positions All adjustments and wiring...

Страница 2: ...e ordering number or specify 1 Order Number 2 Natural or LP gas 3 Step pressure on VR8405P 4 Accessories is desired 5 Order separately transformer igniter sensor module limit controller and thermostat or controller as required If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Home and Building...

Страница 3: ...ravity natural gas at 0 25 kPa pressure drop PRESSURE REGULATION Not adjustable DIMENSIONS See Fig 1 TEMPERATURE RATING VR8405H 0 F to 175 F 18 C to 79 C VR8405M P 40 F to 175 F 40 C to 79 C PRESSURE TAPPING Inlet and outlet taps standard Taps accessible from top of control Tap is 1 8 in NPT with plug containing recess for 3 16 in Allen wrench PRESSURE RATING AGA rating 1 2 psi 3 5 kPa inlet press...

Страница 4: ...e appliance manufacturer instructions if avail able otherwise use the instructions provided below INSTALL BUSHINGS ON ENTIRE GAS CONTROL 1 Remove seals over gas control inlet or outlet 2 Apply moderate amount of good quality pipe com pound to bushing leaving two end threads bare On an LP gas installation use compound resistant to LP gas See Fig 3 Do not use Teflon tape 3 Insert bushing in entire g...

Страница 5: ...ENGTH IN IN Pipe Size Thread Pipe This Amount Maximum Depth Pipe Can Be Inserted Into Control 3 4 13 16 3 4 1 1 1 16 1 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use a wrench on the manifold rather than on the gas control Refer to Figs 4 and 5 WIRING Follow the wiring instructions furnished by the appli ance manufacturer if availabl...

Страница 6: ... VALVE GND TEMPERATURE CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM IGNITER SENSOR CABLE LENGTH 3 ft 9 m OR LESS 3 A REPLACEABLE FUSE ALARM TERMINAL PROVIDED ON SOME MODELS M8051 MVPV MVPV L1 HOT L2 1 2 1 2 3 VR8405 COMBINATION GAS CONTROL Q347 IGNITER SENSOR BURNER 4 4 5 IGNITER SENSOR AND BURNER GROUND 3 5 ALARM ...

Страница 7: ... leak is detected tighten the pipe connection 3 Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flash back in the appliance vestibule Turn on the entire gas control and light the main burner as described below 4 With the main burner in operation paint all pipe joints and gas control inlet and outlet with a rich soap and water solution 5 Ifanot...

Страница 8: ...ustable Step Opening Pressure Regulator 1 The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate 2 With the main burner operating check the gas con trol flow rate using the meter clocking method 3 If desired flow rate is not as stamped on the control check the inlet pressure using a manometer at inlet pres sure tap or upstream of the gas control Regula...

Страница 9: ...nce these environments can cause the gas control to deteriorate more rapidly the system should be checked more often If the gas controls will be exposed to high ammonia conditions e g those used in greenhouses or animal barns contact your Honeywell sales representative to request a gas control with corrosion resistant construction The entire gas control should be replaced if It does not perform pr...

Страница 10: ... repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly higher allowing less gas flow to the gas control outlet This increases gas pressure under the automatic valve diaphragm and repositions the valve disc closer to the seat Thus flow of gas through the second automatic ...

Страница 11: ...operators close bypassing the regulator s and shutting off the main burner As pres sure inside the gas controls and underneath the automatic valvediaphragmsequalize springpressureclosesthesecond automatic valves to provide a second barrier to gas flow Fig 9 Position of gas control components during burner on cycle Both valves are positioned the same one valve shown for simplicity two main valves a...

Страница 12: ...appliance The information below will be of assistance in a typical control application but the specific controls used and the procedures outlined by the manufac turer of your appliance may differ and require special instructions TO TURN ON THE APPLIANCE STOP READ THE WARNING ABOVE The lighting sequence of this appliance is automatic Do not attempt to manually light the main burner If the appli anc...

Отзывы: