Honeywell VR8405 Скачать руководство пользователя страница 4

68-0150

4

VR8405

INSTALLATION

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. The installer must be a trained, experienced service

technician.

4. After installation is complete, use these instructions

to check out product operation.

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Follow these warnings exactly:
1. Disconnect power supply before wiring to pre-

vent electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas,

turn off gas supply at the appliance service valve
before starting installation, and perform the Gas
Leak Test after completion of installation.

3. Always install sediment trap in gas supply line

to prevent contamination of gas control.

4. Do not force the gas control knobs. Use only

your hand to turn the gas control knobs. Never
use any tools. If the gas control knobs will not
operate by hand, call a qualified service techni-
cian to replace the entire gas control. Force or
attempted repair can result in fire or explosion.

5. Replace entire VR8405 when doing a product

replacement. Do not replace individual valve
components.

6. For complete device shutoff, both gas control

knobs must be in the OFF position. For complete
appliance shutoff, turn off the upstream appli-
ance valve and disconnect the power supply.

7. Use the wiring harness for connecting the en-

tire gas control to the ignition control module.
Do not remove the harness or modify the wires
in the harness.

CAUTION

Never apply a jumper across or short the valve
leadwires. This can burn out the heat anticipator
in the thermostat or damage the electronic direct
ignition (DI) module.

IMPORTANT:  This entire gas control is shipped with

protective seals over inlet and outlet tappings. Do
not remove seals until ready to connect piping.

Follow the appliance manufacturer instructions if avail-

able; otherwise, use the instructions provided below.

INSTALL BUSHINGS ON ENTIRE GAS CONTROL

1. Remove seals over gas control inlet or outlet.
2. Apply moderate amount of good quality pipe com-

pound to bushing, leaving two end threads bare. On an LP
gas installation, use compound resistant to LP gas. See
Fig. 3. Do not use Teflon tape.

3. Insert bushing in entire gas control and thread pipe

carefully into bushing until tight.

CHOOSE GAS CONTROL LOCATION

Locate the gas control in the appliance vestibule on the

gas manifold. In replacement applications, locate the entire
gas control in the same location as the old gas control.

Do not locate the entire gas control where it can be

affected by steam cleaning, high humidity, dripping water,
corrosive chemicals, dust or grease accumulation, or exces-
sive heat. To safeguard proper operation, follow these
guidelines:

• Locate entire gas control in a well-ventilated area.
• Mount entire gas control high enough above the cabi-

net bottom to avoid exposure to flooding or splashing
water.

• Make sure the ambient temperature does not exceed

the ambient temperature ratings for the entire gas
control.

• Cover entire gas control when appliance is cleaned

with water, steam, or chemicals or to avoid dust and
grease accumulation.

• Avoid locating gas control where exposure to corro-

sive chemical fumes or dripping water is possible.

Install Appliance Shutoff Valve

It is recommended that an appliance shutoff valve be

installed upstream of the VR8405. Refer to the instructions
provided by the valve manufacturer.

Install Piping to Gas Control

All piping must comply with local codes and ordinances

or with the National Fuel Gas Code (ANSI Z223.1 NFPA
No. 54), whichever applies. Tubing installation must com-
ply with approved standards and practices.

1. Use new, properly reamed pipe free from chips. If

tubing is used, make sure the ends are square, deburred and
clean. Make sure all tubing bends are smooth and without
deformation.

2. Run pipe or tubing to the gas control. If tubing is

used, obtain a tube-to-pipe coupling to connect the tubing
to the gas control.

3. Install sediment trap in the supply line to the entire

gas control. See Fig. 2.

Содержание VR8405

Страница 1: ...t3 hour 20 3 meters3 hour Minimum capacity rated 200 feet3 hour 5 7 meters3 hour Solenoid operated dual first automatic valves open on thermostat call for heat and close when call for heat ends Diaphragm operatedsecondautomaticvalvesopen under control of the regulator and close if gas or power supply is interrupted Two position gas control knobs have ON and OFF positions All adjustments and wiring...

Страница 2: ...e ordering number or specify 1 Order Number 2 Natural or LP gas 3 Step pressure on VR8405P 4 Accessories is desired 5 Order separately transformer igniter sensor module limit controller and thermostat or controller as required If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Home and Building...

Страница 3: ...ravity natural gas at 0 25 kPa pressure drop PRESSURE REGULATION Not adjustable DIMENSIONS See Fig 1 TEMPERATURE RATING VR8405H 0 F to 175 F 18 C to 79 C VR8405M P 40 F to 175 F 40 C to 79 C PRESSURE TAPPING Inlet and outlet taps standard Taps accessible from top of control Tap is 1 8 in NPT with plug containing recess for 3 16 in Allen wrench PRESSURE RATING AGA rating 1 2 psi 3 5 kPa inlet press...

Страница 4: ...e appliance manufacturer instructions if avail able otherwise use the instructions provided below INSTALL BUSHINGS ON ENTIRE GAS CONTROL 1 Remove seals over gas control inlet or outlet 2 Apply moderate amount of good quality pipe com pound to bushing leaving two end threads bare On an LP gas installation use compound resistant to LP gas See Fig 3 Do not use Teflon tape 3 Insert bushing in entire g...

Страница 5: ...ENGTH IN IN Pipe Size Thread Pipe This Amount Maximum Depth Pipe Can Be Inserted Into Control 3 4 13 16 3 4 1 1 1 16 1 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use a wrench on the manifold rather than on the gas control Refer to Figs 4 and 5 WIRING Follow the wiring instructions furnished by the appli ance manufacturer if availabl...

Страница 6: ... VALVE GND TEMPERATURE CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM IGNITER SENSOR CABLE LENGTH 3 ft 9 m OR LESS 3 A REPLACEABLE FUSE ALARM TERMINAL PROVIDED ON SOME MODELS M8051 MVPV MVPV L1 HOT L2 1 2 1 2 3 VR8405 COMBINATION GAS CONTROL Q347 IGNITER SENSOR BURNER 4 4 5 IGNITER SENSOR AND BURNER GROUND 3 5 ALARM ...

Страница 7: ... leak is detected tighten the pipe connection 3 Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flash back in the appliance vestibule Turn on the entire gas control and light the main burner as described below 4 With the main burner in operation paint all pipe joints and gas control inlet and outlet with a rich soap and water solution 5 Ifanot...

Страница 8: ...ustable Step Opening Pressure Regulator 1 The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate 2 With the main burner operating check the gas con trol flow rate using the meter clocking method 3 If desired flow rate is not as stamped on the control check the inlet pressure using a manometer at inlet pres sure tap or upstream of the gas control Regula...

Страница 9: ...nce these environments can cause the gas control to deteriorate more rapidly the system should be checked more often If the gas controls will be exposed to high ammonia conditions e g those used in greenhouses or animal barns contact your Honeywell sales representative to request a gas control with corrosion resistant construction The entire gas control should be replaced if It does not perform pr...

Страница 10: ... repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly higher allowing less gas flow to the gas control outlet This increases gas pressure under the automatic valve diaphragm and repositions the valve disc closer to the seat Thus flow of gas through the second automatic ...

Страница 11: ...operators close bypassing the regulator s and shutting off the main burner As pres sure inside the gas controls and underneath the automatic valvediaphragmsequalize springpressureclosesthesecond automatic valves to provide a second barrier to gas flow Fig 9 Position of gas control components during burner on cycle Both valves are positioned the same one valve shown for simplicity two main valves a...

Страница 12: ...appliance The information below will be of assistance in a typical control application but the specific controls used and the procedures outlined by the manufac turer of your appliance may differ and require special instructions TO TURN ON THE APPLIANCE STOP READ THE WARNING ABOVE The lighting sequence of this appliance is automatic Do not attempt to manually light the main burner If the appli anc...

Отзывы: