![Honeywell VR8304 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/honeywell/vr8304/vr8304_manual_149166006.webp)
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
OUTLET
PRESSURE TAP
INLET.
THERMOCOUPLE
CONNECTION
RED RESET BUTTON
PILOT OUTLET
PILOT ADJUSTMENT
(UNDER CAP SCREW)
M1639
FIG. 5-TOP VIEW OF GAS CONTROL.
Connect PIiot Gas Tubing
1. Cut tubing to desired length and bend as necessary
for routing to pilot burner. Do not make sharp bends or
deform the tubing. Do not bend tubing at gas control or pilot
burner after compression fitting has been tightened, as this
may result in gas leakage at the connection.
2. Square off and remove burrs from end of tubing.
3. Unscrew compression fitting from the pilot outlet (Fig.
5). Slip the compression fitting over the tubing and slide out
of the way.
NOTE: When replacing a gas control, cut off old compres
sion fitting and replace with the new compression fitting
provided on the gas control. Never use the old com
pression fitting as it may not provide a gas-tight seal.
WHEN FLANGE IS NOT USED
APPLY WRENCH
OR BOTTOM OF
TO EITHER SHA
TIGHTEN NUT ONE TURN
/ BEYOND FINGER TIGHT
tt-------,,
TO PILOT BURNER
FITTING
BREAKS
OFF
AND CLINCHES TUBING
AS NUT IS TIGHTENED
&911B
FIG. 7-ALWAYS USE NEW COMPRESSION FlmNG.
4. Push tubing into the pilot gas tapping on the outlet
end of the control until it bottoms. While holding tubing all
the way in, slide compression fitting into place and engage
threads-turn until finger tight. Then tighten one more turn
with wrench. Do not overtighten. Refer to Fig. 7.
5. Connect other end of tubing to pilot burner according
to pilot burner manufacturer's instructions.
WIRING
Follow the wiring instructions furnished by the appli
ance manufacturer, if available, or use the general in
structions provided below.
All wiring must comply with applicable electrical codes
and ordinances.
Disconnect power supply before making wiring con
nections to prevent electrical shock or equipment damage.
1. Check the power supply rating on the gas control and
ensure it matches the available supply. Install transformer,
thermostat, and other controls as required.
2. Connect control circuit to gas control terminals. See
Figs. 5 and 8 or 9.
3. Adjust thermostat heat anticipator to 0. 70 rating
stamped on valve operator.
WHEN FLANGE
IS
USED
13,05,4
FIG. 6-PROPER USE OF WRENCH ON GAS CONTROL WITH AND WITHOUT FLANGES.
6
-