FIG. 2-INSTALL FLANGE TO GAS CONTROL. 

DRDP 

I  I 

Ii 

I

HORIZONTAL: 

PIPED 

GAS 

SUPPLY 

RISER 

PIPED 

GAS 

SUPPLY 

I

I  I 

I  I 

I  : 
I  I 

RISER 

I  I 

I  I 

I  I 

DROP 

TUBING 

GAS 

SUPPLY 

3 INCHES  [76 mm) 

MINIMUM 

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH. 

fil 

CAUTION,  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP 

TO PREVENT GAS FROM FILLING THE WORK AREA. TEST FOR GAS LEAK· 

AGE WHEN INSTALLATION IS COMPLETE. 

6933E 

FIG. 3-INSTALL SEDIMENT TRAP. 

that are used for installing the gas control. After the adapter 

is installed,  the gas control is attached to the adapter as 

outlined above. Note that using an adapter increases the 

overall length of the gas control. 

CHOOSE GAS CONTROL LOCATION 

Do not locate the gas control where it may be affected 

by steam cleaning, high humidity, dripping water, corrosive 

chemicals,  dust  or  grease  accumulation,  or  excessive 

heat. To ensure proper operation, follow these guidelines. 

• Locate gas control in a well ventilated area.

• Mount gas control high enough above the cabinet

bottom to avoid  exposure to flooding or splashing

water. 

• Ensure the ambient temperature does not exceed

the ambient temperature ratings for each compo­

nent.

• Cover gas control if appliance is cleaned with water,

steam,  or chemicals  or  to  avoid dust  and  grease

accumulation.

• Avoid locating gas control where exposure to cor­

rosive chemical fumes or dripping water are likely.

Locate the gas control in the appliance vestibule on the 

gas manifold. In replacement applications, locate the gas 

control in the same location as the old gas control. 

Install Piping to Gas Control 

All piping must comply with local codes and ordinances 

or with the National Fuel Gas Code (ANSI Z223.1 NFPA 

No. 54), whichever applies. Tubing installation must comply 

with approved standards and practices. 

1. Use new,  properly  reamed pipe free from chips.  If

tubing is used, ensure the ends are square, deburred and 

clean.  All  tubing  bends  must  be  smooth  and  without 

deformation. 

2. Run pipe or tubing to the gas control. If tubing is used,

obtain a tube-to-pipe coupling to connect the tubing to the 

gas control. 

3. Install  sediment  trap  in  the  supply  line  to  the  gas

control. See Fig. 3. 

Install Gas Control 

1. 

Mount the gas control 

0-90 

degrees, in any direction,

from the upright position of the gas control knob, including 

vertically. 

2. Mount the gas control so gas flow is in the direction

of the arrow on the bottom of the gas control. 

3. Thread pipe the amount shown in Table 4 for inser­

tion into the gas control  or adapter.  DO NOT  THREAD 

PIPE TOO FAR. Valve distortion or malfunction may result 

if the pipe is inserted too deeply into the gas control. 

TABLE 4-NPT PIPE THREAD LENGTH IN INCHES. 

MAXIMUM DEPTH 

PIPE CAN BE 

PIPE 

THREAD PIPE 

INSERTED INTO 

SIZE 

THIS AMOUNT 

CONTROL 

3/8 

9/16 

3/8 

1/2 

3/4 

1/2 

3/4 

13/16 

3/4 

4. Apply a moderate amount of good quality pipe com­

pound (DO NOT use Teflon tape) to pipe only, leaving two 

end  threads  bare.  On  LP  installations,  use  compound 

resistant to LP gas. 

TWO  IMPERFECT  �t�TROL 

THREADS 

THREAD PIPE THE AMOUNT 

SHOWN IN TABLE FOR 

INSERTION  INTO 

GAS CONTROL. 

APPLY A MODERATE AMOUNT 

OF PIPE COMPOUND TO PIPE 

ONLY (LEAVE TWO END 

THREADS BARE). 

313F 

FIG.  4-USE  MODERATE  AMOUNT 

OF 

PIPE  COM­

POUND. 

68-0108-1

Содержание VR8304

Страница 1: ...ing connections are accessible from top of the control Compact size Straight through body pattern right angle adapters avail able for inlet and outlet Available in 1 2 and 3 4 inch inlet and outlet 1 2 and 3 4 inch straight and angle flanges available Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure Inlet screen inc...

Страница 2: ... instructions sheet STANDARD MODELS MODELS VR8304 Dual Automatic Valve Combination Gas Controls for use in Intermittent Pilot Systems with S86F H S860D S8600F H andS90A B modules See Table 1 for model specifications SUPPLY VOLTAGE 24 Va c 50 60 Hz CURRENT DRAW 0 7 A ELECTRICAL CONNECTIONS 1 4 inch male quick con nects Terminal block color coded orange TYPE OF GAS Separate models available for natu...

Страница 3: ...o 3 MAXIMUM REGULATED CAPACITY 340 feet3 hour 9 6 meter3 hour 370 feet3 hour 10 5 meter3 hour 415 feet3 hour 11 8 meter3 hour acapacity basedon 1000 btu 1eet3 0 64specific gravity naturalgas at 1 inch wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 25 kPa pressure drop Use conversion factors in Table 2 to convert capacities for other gasses TABLE 2 GAS CAPACITY CONVERSION FA...

Страница 4: ...turer s instructions if available otherwise use the instructions provided below 4 APPROVALS AMERICANGASASSOCIATIONDESIGNCERTIFICATE UP 70 69A CANADIAN GAS ASSOCIATION DESIGN CERTIFI CATE UP 70 69A AUSTRALIAN GAS ASSOCIATION Not available DELTA C Not available ACCESSORIES Flanges see Table 3 394349 9 64 inch hex tool for flange assembly screws 393691 Natural to LP gas conversion kit 394588 LP to Na...

Страница 5: ...l in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whicheverapplies Tubinginstallationmustcomply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used ensure the ends are square deburred and clean All tubing bends...

Страница 6: ...ITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED 911B FIG 7 ALWAYS USE NEW COMPRESSION FlmNG 4 Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms While holding tubing all the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 7 5 Connect other en...

Страница 7: ...VR8304 WIRING CONNECTIONS IN INTERMITTENT IGNITION SYSTEM WITH S86 PV GND VR8304 S8610F H _ VENT 24V DAMPER COMBINATION PV MV GAS CONTROL MV MV PV PV BURNER GND 24V TH W PLUG MV PILOT BURNER GROUND s POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION bi CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER DB0D VENT DAMPER _ REM...

Страница 8: ...t cover screw Refer to Fig 5 8 2 Turn the inner adjustment screw clockwise to decrease or counterclockwise n to increase the pilot flame 3 Alwaysreplace thecover screw after adjustment and tighten firmly to ensure proper operation 3 8 TO 1 2 INCH 10 TO 13 MILLIMETRES IGNITER SENSOR FIG 10 PROPER FLAME ADJUSTMENT CHECK AND ADJUST GAS INPUT TO MAIN BURNER CAUTION 1 Do not exceed the input rating sta...

Страница 9: ...counter clockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to ensure proper operation 4 If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control check the inlet pressure using a manometer at inlet pressure tap or upstream of thegascontrol If the inlet pressure is in the normal range refer to Table5 or6 replace the exi...

Страница 10: ...er immediately or following prepurge See IP module specifications 4 H module has timed ignition time length of spark operation See IP module specifications 5 After themodulelocksout open gascontrol knoband ensure there is no pilot or main burner gas flow With modules that continue spark until pilot lights or system is shut down manually pilot should light when gas control knob is opened 6 Settherm...

Страница 11: ... and the pilot is burning The servo pressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power thermostat satisfied de energizes the S8600 module and closes both automatic valves The system is ready to return to normal service when power is restored through the thermostat Loss of pilot flame or flame too small to reliably light main burner closes the second a...

Страница 12: ...f inlet pressure and flow rate vary widely Any outlet pressure change is immediately reflected back to the pressure regulator diaphragm which repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly higher allowing less gas flow to the gascontroloutlet This increases gaspre...

Страница 13: ...ure regulator maintains the desired full rate outlet FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control It contains no replaceable components Attempted disas sembly or repair may damage the gas control 13 pressure as described for the standard regulator The step model requires approximately 60 seconds to reset once the main burner goes off ...

Страница 14: ... any physical damage tampering bent termi nals missingorbrokenparts strippedthreads or evidence of exposure to heat 14 IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The infor mation below will be of assistance in a typical gas control application but the specific controls used and the procedures outlined by the manufacturer or your appliance may...

Отзывы: