background image

CHECK SAFETY SHUTDOWN PERFORMANCE 

:;:;:;:;:;:;:::;:;:;'.'*;i�,'.'.:t;t:·�;!;yJi1111= . 

.i .. : •• ·::: ,,, 

�'''\At:]Ciy2f'l

FIRE OR EXPLOSION HAZARD 

CAN CAUSE PROPERTY DAMAGE, SEVERE 

INJURY, OR DEATH 

Perform the safety shutdown test any time work 

Is done on a gas system. 

NOTE: Read steps 1-7 below before starting and compare 

to the safety shutdown or safety lockout tests recom­

mended  for  the intermittent pilot (IP) module. Where 

they  differ,  use  the  procedure recommended  for  the 

module. 

:·.·:·.·:·:'··=·�···.1::·T

iii

�-·i�r:]lfl'R!NljNGnl1l:·.··:

.

,:;11111111111111111111··11"'i1i1;Iilll'.

FIRE OR EXPLOSION HAZARD 

CAN CAUSE PROPERTY DAMAGE, SEVERE 

INJURY, OR DEATH 

Improper clean Ing or reassembly may cause gas 

leakage,  When cleaning,  ensure that control Is 

reassembled properly and perform gas leak test. 

Regular preventive maintenance is important in appli­

cations that place a heavy load on system controls, such 

as in the commercial cooking and agricultural and indus­

trial industries because: 

• In many such applications, particularly commercial

cooking, the equipment operates 100,000 to 200,000

cycles per year. Such heavy cycling can wear out the

gas control in one to two years.

• Exposure  to  water,  dirt,  chemicals  and  heat  can

damage the gas control and shut down the control

system.

The  maintenance  program  should  include  regular 

10 

1. Turn gas supply off.

2. Set thermostat or controller above room temperature

to call for heat. 

3. Watch for spark at pilot burner either immediately or 

following prepurge. See IP module specifications. 

4. H  module  has  timed  ignition,  time  length  of  spark

operation. See IP module specifications. 

5. After the module locks out, open gas control knob and

ensure  there  is  no  pilot  or  main  burner  gas  flow.  With 

modules that continue spark until pilot lights or system is 

shut down  manually,  pilot should light  when  gas control 

knob is opened. 

6. Set thermostat below room temperature and wait one

minute. 

7. Operate system through one complete cycle to  en­

sure all controls operate properly. 

checkout of the gas control as outlined under STARTUP 

AND CHECKOUT on page 8, and the control  system as 

described in the appliance manufacturer's literature. 

Maintenance frequency must be determined individu­

ally for each application. Some considerations are: 

• Cycling  frequency.  Appliances  that  may  cycle

100,000 times annually should be checked monthly.

• Intermittent use. Appliances that are used season­

ally should be checked before shutdown and again

before the next use.

• Consequence of unexpected shutdown. Where the

cost of an unexpected shutdown would be high,  the 

system should be checked more often.

• Dusty,  wet,  or corrosive environment.  Since these

environments can cause the gas control to deterio­

rate more  rapidly,  the  system  should  be  checked

more often.

The gas control should be replaced if: 

• It  does  not  perform  properly  on  checkout  or

troubleshooting.

• The gas control knob is hard to turn or push down, or 

it fails to pop back up when released.

• The gas control is likely to have operated for more

than 200,000 cycles.

-

Содержание VR8304

Страница 1: ...ing connections are accessible from top of the control Compact size Straight through body pattern right angle adapters avail able for inlet and outlet Available in 1 2 and 3 4 inch inlet and outlet 1 2 and 3 4 inch straight and angle flanges available Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure Inlet screen inc...

Страница 2: ... instructions sheet STANDARD MODELS MODELS VR8304 Dual Automatic Valve Combination Gas Controls for use in Intermittent Pilot Systems with S86F H S860D S8600F H andS90A B modules See Table 1 for model specifications SUPPLY VOLTAGE 24 Va c 50 60 Hz CURRENT DRAW 0 7 A ELECTRICAL CONNECTIONS 1 4 inch male quick con nects Terminal block color coded orange TYPE OF GAS Separate models available for natu...

Страница 3: ...o 3 MAXIMUM REGULATED CAPACITY 340 feet3 hour 9 6 meter3 hour 370 feet3 hour 10 5 meter3 hour 415 feet3 hour 11 8 meter3 hour acapacity basedon 1000 btu 1eet3 0 64specific gravity naturalgas at 1 inch wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 25 kPa pressure drop Use conversion factors in Table 2 to convert capacities for other gasses TABLE 2 GAS CAPACITY CONVERSION FA...

Страница 4: ...turer s instructions if available otherwise use the instructions provided below 4 APPROVALS AMERICANGASASSOCIATIONDESIGNCERTIFICATE UP 70 69A CANADIAN GAS ASSOCIATION DESIGN CERTIFI CATE UP 70 69A AUSTRALIAN GAS ASSOCIATION Not available DELTA C Not available ACCESSORIES Flanges see Table 3 394349 9 64 inch hex tool for flange assembly screws 393691 Natural to LP gas conversion kit 394588 LP to Na...

Страница 5: ...l in the same location as the old gas control Install Piping to Gas Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whicheverapplies Tubinginstallationmustcomply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used ensure the ends are square deburred and clean All tubing bends...

Страница 6: ...ITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED 911B FIG 7 ALWAYS USE NEW COMPRESSION FlmNG 4 Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms While holding tubing all the way in slide compression fitting into place and engage threads turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 7 5 Connect other en...

Страница 7: ...VR8304 WIRING CONNECTIONS IN INTERMITTENT IGNITION SYSTEM WITH S86 PV GND VR8304 S8610F H _ VENT 24V DAMPER COMBINATION PV MV GAS CONTROL MV MV PV PV BURNER GND 24V TH W PLUG MV PILOT BURNER GROUND s POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION bi CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER DB0D VENT DAMPER _ REM...

Страница 8: ...t cover screw Refer to Fig 5 8 2 Turn the inner adjustment screw clockwise to decrease or counterclockwise n to increase the pilot flame 3 Alwaysreplace thecover screw after adjustment and tighten firmly to ensure proper operation 3 8 TO 1 2 INCH 10 TO 13 MILLIMETRES IGNITER SENSOR FIG 10 PROPER FLAME ADJUSTMENT CHECK AND ADJUST GAS INPUT TO MAIN BURNER CAUTION 1 Do not exceed the input rating sta...

Страница 9: ...counter clockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to ensure proper operation 4 If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control check the inlet pressure using a manometer at inlet pressure tap or upstream of thegascontrol If the inlet pressure is in the normal range refer to Table5 or6 replace the exi...

Страница 10: ...er immediately or following prepurge See IP module specifications 4 H module has timed ignition time length of spark operation See IP module specifications 5 After themodulelocksout open gascontrol knoband ensure there is no pilot or main burner gas flow With modules that continue spark until pilot lights or system is shut down manually pilot should light when gas control knob is opened 6 Settherm...

Страница 11: ... and the pilot is burning The servo pressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power thermostat satisfied de energizes the S8600 module and closes both automatic valves The system is ready to return to normal service when power is restored through the thermostat Loss of pilot flame or flame too small to reliably light main burner closes the second a...

Страница 12: ...f inlet pressure and flow rate vary widely Any outlet pressure change is immediately reflected back to the pressure regulator diaphragm which repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly higher allowing less gas flow to the gascontroloutlet This increases gaspre...

Страница 13: ...ure regulator maintains the desired full rate outlet FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control It contains no replaceable components Attempted disas sembly or repair may damage the gas control 13 pressure as described for the standard regulator The step model requires approximately 60 seconds to reset once the main burner goes off ...

Страница 14: ... any physical damage tampering bent termi nals missingorbrokenparts strippedthreads or evidence of exposure to heat 14 IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The infor mation below will be of assistance in a typical gas control application but the specific controls used and the procedures outlined by the manufacturer or your appliance may...

Отзывы: