background image

68-0049—2

8

VR8205; VR4205

STARTUP AND CHECKOUT

Startup and Checkout

!

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH
1. Do not force the gas control knob on the appli-

ance. Use only your hand to turn the gas con-
trol knob. Never use any tools.

2. If the knob will not operate by hand, the con-

trol should be replaced by a qualified service
technician.

GAS CONTROL KNOB SETTINGS

Gas control knob settings are as follows:
OFF: Prevents main gas flow through the control.
ON: Permits gas to flow into the control body. Under

control of the thermostat and direct ignition module,
gas can flow to the main burner.

NOTE: Controls are shipped with the gas control knob in

the ON position.

PERFORM GAS LEAK TEST

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH
Check for gas leaks with soap and water solution
any time work is done on a gas system.

GAS LEAK TEST

1. Paint pipe connections upstream of gas control with

rich soap and water solution. Bubbles indicate gas leak.

2. If leak is detected, tighten pipe connections.
3. Stand clear of main burner while lighting to prevent

injury caused from hidden leaks that could cause flashback
in the appliance vestibule. Light main burner.

4. With main burner in operation, paint pipe joints

(including adapters) and control inlet and outlet with rich
soap and water solution.

5. If another leak is detected, tighten adapter screws,

joints, and pipe connections.

6. Replace part if leak cannot be stopped.

TURN ON SYSTEM

Rotate the gas control knob counterclockwise

to

ON.

TURN ON MAIN BURNER

Follow instructions provided by appliance manufac-

turer or turn up thermostat to call for heat.

!

CHECK AND ADJUST GAS INPUT AND
BURNER IGNITION

CAUTION

1. Do not exceed input rating stamped on appli-

ance nameplate, or manufacturer recommended
burner orifice pressure for size orifice(s) used.
Make certain primary air supply to main burner
is properly adjusted for complete combustion.
Follow appliance manufacturer instructions.

2. IF CHECKING GAS INPUT BY CLOCK-

ING GAS METER. Make certain there is no
gas flow through the meter other than to the
appliance being checked. Other appliances must
remain off with their pilots extinguished (or
their consumption must be deducted from the
meter reading). Convert flow rate to Btuh as
described in form 70-2602, Gas Controls Hand-
book, and compare to Btuh input rating on
appliance nameplate.

3. IF CHECKING GAS INPUT WITH MANO-

METER: Be sure gas control is in OFF posi-
tion before removing outlet pressure tap plug
to connect manometer (pressure gauge). Also
turn gas control knob back to OFF when re-
moving gauge and replacing plug. Before re-
moving inlet pressure tap plug, shut off gas
supply at the manual valve in the gas piping to
the appliance or, for LP, at the tank. Also shut
off gas supply before disconnecting manom-
eter and replacing plug. Repeat Gas Leak Test
at plug with main burner operating.

Standard Pressure Regulator

1. Check the manifold pressure listed on the appliance

nameplate. Gas control outlet pressure should match the
nameplate.

2. With main burner operating, check gas control flow

rate using the meter clocking method or check pressure by
using a manometer connected to the outlet pressure tap on
the gas control. See Fig. 5.

3. If necessary, adjust pressure regulator to match ap-

pliance rating. See Table 5A or 5B for factory set nominal
outlet pressure and adjustment setting range.

a. Remove pressure regulator adjustment cap screw.
b. Using screwdriver, turn inner adjustment screw

clockwise

to increase or counterclock-

wise

to decrease gas pressure to burner.

c. Always replace cap screw and tighten firmly to

prevent gas leakage.

4. If desired outlet pressure or flow rate cannot be

achieved by adjusting the gas control, check gas control
inlet pressure using a manometer at the gas control inlet
pressure tap. If inlet pressure is in the nominal range (see
Table 5A or 5B), replace gas control. Otherwise, take the
necessary steps to provide proper gas pressure on the
control.

!

Содержание VR8205

Страница 1: ...tomatic valve opens on thermostat call for heat and closes when call for heat ends Diaphragm operatedsecondautomaticvalveopensunder control of the regulator and closes if gas or power supply is interrupted Two positiongascontrolknobhasONandOFFpositions All adjustments and wiring connections accessible from top of the control Compact size Straight through body pattern right angle adapters available...

Страница 2: ...o provide ease of stocking ease of handling and maximum replacement value TRADELINE model specifications are the same as those of standard models except as noted below TRADELINE MODEL AVAILABLE VR8205A Dual Automatic Combination Gas Control for Direct Ignition Systems Models for natural or LP gas ADDITIONAL FEATURES 3 8 in bushing 3 4in straightflangeassembly withO ringandscrews Tool for flange he...

Страница 3: ...m the upright position of the gas control knob including vertically TEMPERATURE RATING VR8205A C H VR4205H 0 F to 175 F 18 C to 79 C VR8205M P K VR4205M P 40 F to 175 F 40 C to 79 C DIMENSIONS See Fig 1 APPROVALS AmericanGasAssociationdesigncertificate L2025006 CanadianGasAssociationdesigncertificate L2025006 Australian Gas Association design certificate 4214 Approved for Delta C applications ACCE...

Страница 4: ...r natural gas on an LP gas system or a gas control set for LP gas on a natural gas system 2 When making conversion main pilot burner orifices must be changed to meet appliance manufacturer specifications Refer to appliance manufacturer instructions for orifice specifications and changeover procedure Gas controls are factory set for natural and manufactured or LP gas Do not attempt to use a control...

Страница 5: ...essive heat To assure proper operation follow these guidelines Locate gas control in a well ventilated area Mount gas control high enough above the cabinet bottom to avoid exposure to flooding or splashing water Assure the ambient temperature does not exceed the ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust a...

Страница 6: ...ntrol inlet and outlet if neces sary 6 Connect pipe to control inlet and outlet Use wrench on the square ends of the control If an adapter is used place wrench on adapter rather than on control Refer to Figs 5 and 6 TWO IMPERFECT THREADS GAS CONTROL THREAD PIPE THE AMOUNT SHOWN IN TABLE 4 FOR INSERTION INTO GAS CONTROL APPLY A MODERATE AMOUNT OF PIPE COMPOUND TO PIPE ONLY LEAVE TWO END THREADS BAR...

Страница 7: ...ition system Fig 8 Wiring connections for 24 volt control in S87 Direct Ignition System IGNITION MODULE L1 HOT L2 LIMIT CONTROLLER Q347 IGNITER SENSOR 120V GND VALVE VALVE GND POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION M3090A BURNER 120V VR4205 DUAL VALVE COMBINATION GAS CONTROL L2 L1 2 1 1 2 WHITE BLUE BLACK BLUE HOT SURFACE IGNIT...

Страница 8: ...inburner is properly adjusted for complete combustion Follow appliance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCK ING GAS METER Make certain there is no gas flow through the meter other than to the appliancebeingchecked Otherappliancesmust remain off with their pilots extinguished or their consumption must be deducted from the meter reading Convert flow rate to Btuh as describedinf...

Страница 9: ...aracteristics TABLE 5A PRESSURE REGULATOR SPECIFICATION PRESSURES in wc Model Type Nominal Inlet Factory Set Nominal Outlet Pressure Setting Range Type of Gas Pressure Range Step Full Rate Step Full Rate Standard Natural 5 0 7 0 3 5 3 0 5 0 slow opening LP 12 0 14 0 10 0 8 0 12 0 Step opening Natural 5 0 7 0 0 9 3 5 3 0 5 0 LP 12 0 14 0 2 2 10 0 8 0 12 0 TABLE 5B PRESSURE REGULATOR SPECIFICATION P...

Страница 10: ...tor is de energized closing the channel to the pressure regulator and opening a channel to the under side of the second automatic valve operator valve dia phragm The combination of spring pressure under the second automatic valve diaphragm and lack of outlet pres sure holds the diaphragm firmly closed Gas flow to the main burner is blocked by both valves Regular preventive maintenance is important...

Страница 11: ...gmoregasflowto the gas control outlet This decreases gas pressure under the second automatic valve diaphragm and repositions the valve disc further from the seat Thus flow of gas through the second automatic valve is increased and outlet pressure rises to the desired level Fig 10 Position of gas control components during thermostat off cycle Slow Opening Regulation Slow opening gas controls functi...

Страница 12: ...ressurecloses the second automatic valve to provide a second barrier to gas flow Fig 11 Position of gas control components during burner on cycle Service WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control it contains no replaceable components Attempted disassembly or repair may damage the control CAUTION Do not apply a jumper across...

Страница 13: ...e It must be replaced in case of any physical damage such as bent terminals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions pro vided by the manufacturer of your heating appliance The information below will be of assistance in a typical control application but the specific controls used and the procedures outlined by the manufac ...

Отзывы: