TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
13
62-3070—07
Minimum-Off Timer Compressor
Protection
The thermostat has an adjustable Minimum-Off Timer that
can be set from zero to five minutes (Factory Setting—five
minutes). The Minimum-Off Timer can be bypassed
through the Installer System Test or it can be bypassed
permanently by setting the Minimum-Off Timer to 0
minutes in the Installer Setup. The Minimum-Off Timer is
activated after the compressor turns off:
— If the thermostat is system powered (common wire),
the Minimum-Off Timer is also activated upon initial
startup and after power interruptions.
— If there is a call for cooling or heating during the
Minimum-Off Time, the thermostat displays “Wait.”
— When the Minimum Off Timer expires, “Cool On” or
“Heat On” (heat pumps only)” appears solidly in the
display and the compressor and fan turn on.
Outdoor or Indoor Temperature
Sensor
Allow outdoor or indoor temperature sensor to absorb the
air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.
Economizer/TOD Logic (Table 6)
Table 6. Operation of Terminal A.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor
Sensor
In this operation, there is no external fossil fuel kit (dual
fuel kit) installed; the thermostat controls this function:
1.
Choose correct heat pump application in Installer
Setup Number 0170.
2.
Choose
Outdoor Temperature Sensor for Heat
Pump Temperature Lockouts
Option
in Installer
Setup Number 0340.
3.
Choose appropriate
Balance Point Temperature
in Installer Setup Number 0350.
OPERATION IN HEAT MODE ABOVE BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected
Balance Point Temperature (ISU 0350), only the
compressor operates and the fan (G terminal) energizes
when the thermostat calls for heat.
OPERATION IN HEAT MODE BELOW BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected
Balance Point Temperature (ISU 0350), only the Fossil
Fuel (auxiliary heat) operates and the fan (G terminal)
does not energize when the thermostat calls for heat.
Heat Pump with Auxiliary (Backup) Heat
and Outdoor Temperature Sensor
1.
Choose correct heat pump application in Installer
Setup Number 0170.
2.
Choose
Outdoor Temperature Sensor for
Control Option
in Installer Setup Number 0340.
3.
Choose
Compressor Lockout Temperature
in
Installer Setup Number 0350.
4.
Choose
Auxiliary Lockout Temperature
in
Installer Setup Number 0360.
NOTE: There is a 5°F deadband between Compressor
and Auxiliary Heat lockout temperatures.
Operation in Heat Mode
When the outdoor temperature is:
— Below the Compressor Lockout Temperature, only the
Auxiliary Heat operates.
— Above the Auxiliary Lockout Temperature, only the
Compressor operates. See Fig. 31.
— Between the two temperatures, both the Compressor
and Auxiliary Heat operate.
Fig. 27. Heat Pump Operation with Lockout
Temperatures Set.
Effective
Occupancy
Call for
Cool
Terminal A
Economizer
TOD
Occupied
—
Energized
Energized
Unoccupied Yes
Energized
De-energized
No
De-energized
De-energized
Override
—
Energized
Energized
35
M19950
COMPRESSOR
LOCKOUT
TEMPERATURE
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR ONLY
BOTH COMPRESSOR AND
AUXILIARY HEAT
AUXILIARY ONLY
50
OUTDOOR TEMPERATURE