![Honeywell VISIONPRO TB8220U Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/honeywell/visionpro-tb8220u/visionpro-tb8220u_installation-instructions-manual_2158877012.webp)
TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT
62-3070—07
12
NOTE: Press the Done button to exit the Installer System Test.
OPERATION
System Settings
Heat
—
Thermostat controls the heating system.
Off
—
Both heating and cooling systems are off.
Cool
—
Thermostat controls the cooling system.
Auto
—
Thermostat automatically changes between heat
and cool operation, depending on indoor temperature.
Fan Settings
Auto
—
Fan runs only when heating/cooling system is on.
On
—
Fan runs continuously.
Table 5 shows default program settings. See Owner’s
Guide for complete instructions to change the program.
Table 5. Energy-saving Default Program Settings.
a The thermostat default setting is two period only. To use
four periods, change the appropriate setup parameter.
0690
Temperature
Control Cool
2
1—Less Aggressive
2—Standard
3—More Aggressive
Only shown if system has cool stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)
0695
Recovery Cool
Ramp Rate
3
0-20°F/hour
Only shown if system has cool stages.
0 disables ramped recovery (step setpoint change
at period start time).
0700
Temperature
Display Offset
0
-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)
This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).
0710
Restore Factory
Defaults
0
0—No
1—Yes
Resets all ISU parameters to default values and
resets the schedule to default. Retains only
calendar settings and time.
INSTALLER TESTS
Test 1
Installer Test
Cool
0
0—Off
1—Cool Stage 1
2—Cool Stage 2
Test 2
Installer Test
Fan
0
0—Off
1—Fan On
Test 3
Installer Test
Heat
0
0—Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3
Test 4
Installer Test
Auxiliary Heat
0
0—Auxiliary Heat Off
1—Auxiliary Heat On
Test 8
Installer Test
TOD/Economizer
0
0—TOD/Economizer Off
1—TOD/Economizer On
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting
All Settings
Notes
Schedule
Period
Time
Setpoints
Fan
Setting
Heat
Cool
Occ1
8:00am
70°F
(21°C)
78°F
(25.5°C)
Auto
Unocc1
10:00pm
55°F
(10°C)
85°F
(29.5
°
C)
Auto
Occ2
a
—
—
—
—
Unocc2
a
—
—
—
—