Honeywell VISIONPRO TB8220U Скачать руководство пользователя страница 11

TB8220U COMMERCIAL VISIONPRO™ PROGRAMMABLE THERMOSTAT

11

62-3070—07

0340

Remote 
Temperature 
Sensor

0

0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor

Averaging would not include on-board sensor. It is 
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing 
compressor lockout while displaying temperature).

0350

Heat Pump 
Compressor 
Lockout

0

0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)

Only shown for heat pump systems with more heat 
stages than cool selected and remote sensor 
selection is outdoor for control.
Must enforce a dead band between this and 
Auxiliary Lockout

0360

Heat Pump 
Auxiliary Lockout

0

0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)

Only shown for heat pump systems with more heat 
stages than cool selected and remote sensor 
selection is outdoor for control.
Must enforce a dead band between this and Heat 
Pump Compressor Lockout.

0535

Temporary 
Occupied Duration 
Limit

3

0—no duration
1—one hour
2—two hours
3—three hours
4—four hours

0 means no limit

0540

Number of Periods 4

2—2 Periods
4—4 Periods

Does not appear if Non-programmable is chosen.
Applies to all days of the week. With 2 selected the 
“Cancel Period” option does not appear on the 
display.

0580

Minimum 
Compressor Off 
Time

5

0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes

Only shown if system has cool stages.

0600

Heat Temperature 
Range Stops

90

40 to 90°F (4 to 32°C)

Only shown if system has heat stages.

0610

Cool Temperature 
Range Stops

50

50 to 99°F (10 to 37°C)

Only shown if system has cool stages.

0640

Clock Format

12

12—12 Hour
24—24 Hour

0650

Extended Fan-on 
time Heat

0

0—Off
90—90 seconds

Not displayed with fan set to fossil or with cool-only 
systems

0660

Extended Fan-on 
time Cool

0

0—Off
40—40 seconds

Only shown if system has cool stages.

0670

Keypad Lockout

0

0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked

Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.

0680

Temperature 
Control Heat

2

1—Less Aggressive
2—Standard
3—More Aggressive

Only shown if system has heat stages.
Only integral gains affected. Affects control 
operation in all control regimes (not just recovery 
or setpoint change).
More Aggressive stops signal prior to reaching the 
setpoint. (For use with oversized equipment.)

0685

Recovery Heat 
Ramp Rate

5

0-20°F/hour

Only shown if system has heat stages.
0 disables ramped recovery (step setpoint change 
at period start time).

Table 4. Installer Setup Menu. (Continued)

Installer

 Setup 

Number

Installer Setup 

Name

Default 
Setting

All Settings

Notes

Содержание VISIONPRO TB8220U

Страница 1: ...ngs given in instructions and on the product to ensure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installati...

Страница 2: ...in holes Tap the wall anchors provided into the drilled holes until flush with the wall 5 Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors 6 Insert the mounting screws into the wall anchors and tighten Fig 3 Install wallplate WIRING IMPORTANT All wiring must agree with applicable codes ordinances and regulations Use 18 gauge thermostat wire Shi...

Страница 3: ...r the W7459 TR terminal When using dual transformers at the thermostat the heating transformer must power the economizer The A signal is powered from the R terminal and energizes the economizer to signal occupied status and drive the damper to the set minimum position Table 3 Wiring Diagrams M19917 WALLPLATE M22266 WALL OPENING WIRE SHADED AREA Terminal Designation Description Rc see Note 1 Power ...

Страница 4: ...4V COMMON CONNECTION IS OPTIONAL WHEN USED THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY 1 3 2 3 2 Y2 L A W2 S1 S2 2 RC R W Y G C ECONOMIZER L1 HOT L2 1 24 VAC L1 HOT L2 1 24 VAC M22783A OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTI...

Страница 5: ...NG BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL 1 3 2 3 COOL RELAY 1 HEAT RELAY 1 COOL RELAY 2 Y2 L A W2 S1 S2 2 RC R W Y G C L1 HOT L2 1 24 VAC ECONOMIZER M22787A HEAT RELAY 2 OUTDOOR INDOOR TEMPERATURE SENSOR FAN RELAY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER WHEN USING BATTERIES THE 24V COMMON CONNECTION IS OPTIONAL WHEN USED T...

Страница 6: ...ROL AS EITHER O OR B IN THE INSTALLER SETUP OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE OUTDOOR INDOOR TEMPERATURE SENSOR 3 Y2 L A W1 S1 S2 2 RC R O B Y G C 4 L1 HOT L2 1 24 VAC 5 ECONOMIZER COMPRESSOR CONTACTOR ECONOMIZER M22790A CHANGEOVER VALVE FAN RELAY 1 2 3 4 5 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOA...

Страница 7: ...21 A 10K ohm sensor to provide a temperature averaging network Fig 21 Wiring four C7189U 10K ohm Sensors to provide a temperature averaging network M27481 S1 S2 T T SUBBASE TR21 T T TR21 T T TR21 T T TR21 M27482 S1 S2 SUBBASE TR21 A T4 T3 TR21 A T4 T3 1 1 1 THE TR21 A IS A 10K OHM SENSOR M27483 T4 T3 TR21 A 1 1 THE TR21 A IS A 10K OHM SENSOR S1 S2 T T SUBBASE TR21 T T TR21 M22935 WIRES MUST HAVE A...

Страница 8: ...rmostat is designed to under normal use automatically keep current time and day in memory for up to ten years once the calendar is set There are two ways to set the calendar for this thermostat SETTING CALENDAR WHEN THERMOSTAT IS FIRST POWERED When the thermostat is first powered the display is ready to set the calendar and time The thermostat proceeds through a sequence of setup screens See Fig 2...

Страница 9: ...TESTS TABLE 4 Fig 26 Entering Installer Setup Installer System Tests Use the Installer System Test to test the heating cooling and fan Refer to the latter portion of Table 4 CAUTION Equipment Damage Hazard Minimum compressor off time is bypassed during Installer System Test Avoid cycling compressor quickly IMPORTANT Use Installer System Test to test heating cooling and fan The setting chosen for S...

Страница 10: ...stages Selection in this stage changes default CPH of second stage cool 0230 CPH for second stage compressor 3 1 6 Only shown if two stages of cool selected 0240 CPH for first stage conventional heat 5 1 12 Only shown if system is conventional with heat stages Selection in this stage changes default CPH of second stage heat 0250 CPH for second stage conventional heat 9 1 12 Only shown with at leas...

Страница 11: ...ys of the week With 2 selected the Cancel Period option does not appear on the display 0580 Minimum Compressor Off Time 5 0 Off 2 2 minutes 3 3 minutes 4 4 minutes 5 5 minutes Only shown if system has cool stages 0600 Heat Temperature Range Stops 90 40 to 90 F 4 to 32 C Only shown if system has heat stages 0610 Cool Temperature Range Stops 50 50 to 99 F 10 to 37 C Only shown if system has cool sta...

Страница 12: ... oversized equipment 0695 Recovery Cool Ramp Rate 3 0 20 F hour Only shown if system has cool stages 0 disables ramped recovery step setpoint change at period start time 0700 Temperature Display Offset 0 3 1 5 3 F 1 5 C 2 1 0 2 F 1 0 C 1 0 5 1 F 0 5 C 0 0 0 0 F 0 0 C 1 0 5 1 F 0 5 C 2 1 0 2 F 1 0 C 3 1 5 3 F 1 5 C This offset applies to both the control temperature and to the display temperature f...

Страница 13: ...oint Temperature in Installer Setup Number 0350 OPERATION IN HEAT MODE ABOVE BALANCE POINT OUTDOOR TEMPERATURE When the outdoor temperature is above the selected Balance Point Temperature ISU 0350 only the compressor operates and the fan G terminal energizes when the thermostat calls for heat OPERATION IN HEAT MODE BELOW BALANCE POINT OUTDOOR TEMPERATURE When the outdoor temperature is below the s...

Страница 14: ...e thermostat is functional Check the heating equipment to find the cause of the problem Loose or broken wire connection between thermostat and heating equipment Check for 24 Vac between the heat terminal W and transformer common If voltage is not present check wire connection loose or broken between the thermostat and the heating equipment Heat pump puts out cool air in the heat mode and warm air ...

Страница 15: ...tem setting to Heat System Type Installer Setup Number 0170 is set to Cool Only Set System Type Installer Setup Number 0170 to match the installed heating and or cooling equipment Cannot set the system setting to Cool System Type Installer Setup Number 0170 is set to Heat Only or Heat Only with Fan Set System Type Installer Setup Number 0170 to match the installed heating and or cooling equipment ...

Страница 16: ...4 4 C to 65 6 C Operating Relative Humidity Non condensing 5 to 90 Thermostat Dimensions 3 3 4 in 95 mm high x 6 in 152 mm wide x 1 3 8in 35 mm deep Accessories C7089U Outdoor Sensor 10K ohm NTC C7189U Remote Indoor Sensor 10K ohm NTC C7772 Flush Mount Remote Indoor Sensor 20K ohm NTC TR21 Wall Mount Remote Indoor Sensor 20K ohm NTC TR21 A Wall Mount Remote Indoor Sensor 10K ohm NTC Perchlorate Ma...

Отзывы: