SOLENOID SAFETY SHUT-OFF VALVE

7

65-0246—1

OPERATION AND CHECKOUT

Operation

The V4297A Safety Shutoff Valve is a normally closed valve. 
The valve opens when it is energized and closes when the 
power is removed.

WARNING

Explosion Hazard and Electrical Shock Hazard.
Can cause explosion, serious injury or death.

1. Do not put the system into service until you have 

satisfactorily completed the following Valve Leak 
Test, all applicable tests described in the Checkout 
section of the instructions for the flame safeguard 
control and any other tests required by the burner 
manufacturer.

2. All tests must be performed by a trained, 

experienced flame safeguard technician.

3. Close all manual fuel shutoff valves immediately if 

trouble occurs.

After the installation is complete, cycle the valve several times 
with the manual fuel shutoff cock closed. Make sure the valve 
functions properly. Also, perform the Valve Leak Test before 
putting the valve into service.

Valve Leak Test (Fig. 14)

This is a test for checking the closure tightness of the gas 
safety shutoff valve. It should be performed only by trained, 
experienced flame safeguard control technicians during the 
initial startup of the burner system or whenever the valve is 
replaced (see Service Information section). It is recommended 
that this test also be included in the scheduled inspection and 
maintenance procedures. For a periodic inspection test, follow 
steps 1, 3, 4, 5, 8, 9, 10, 12, 13, 16 and 17.

1.

De-energize the control system to make sure no power 
goes to the valve (C, Fig. 14).

2.

Close the upstream manual gas cock (A).

3.

Make sure the manual test petcock (F) is closed in the 
leak test tap assembly (D).

4.

Remove the leak test tap plug and connect the test 
apparatus to the leak test tap (D).

5.

Close the downstream manual gas cock (E).

6.

Open the upstream manual gas cock (A).

7.

Run the V4297A Valve to is open position (through the 
safety system); then immediately de-energize the 
system to close the V4297A Valve.

8.

Immerse a 1/4 in. (6 mm) tube vertically 1/2 in. (13 mm) 
into a jar of water.

9.

Slowly open the manual test petcock (F).

10.

When the rate of bubbles coming through the water 
stabilizes, count the number of bubbles appearing 
during a ten-second period. Each bubble appearing 
represents a flow rate of 0.001 cfh.

IMPORTANT

To meet U.S. requirements, make sure leakage does 
not exceed the rates in Table 2.

Table 2. Valve allowable leakage rate.

a

 Based on air at standard conditions, test pressure provided 

by ANSI Z21.21, Section 2.42 and a maximum of 235
 cc/h/in of seal-off diameter (not pipe size).

Fig. 14. Valve leak test.

NOTE:

NOTE: For international leak test requirements, 
contact the appropriate approval agency.

After the Test

1.

Close the upstream manual gas cock (A).

2.

Close the manual test petcock (F), remove the test 
apparatus, and close the leak test tap (D).

3.

Make sure the downstream manual gas cock (E) is 
closed.

4.

Open the upstream manual gas cock (A) and energize 
the V4297A Valve through the safety system.

5.

Test with rich soap and water solution to make sure 
there is no leak at the leak test tap (D) or any pipe 
adapter/valve mating surfaces.

6.

De-energize the V4297A Valve (C).

7.

Open the downstream manual gas cock (E).

8.

Restore the system to normal operation. If two safety 
shutoff valves are used, check each valve separately for 
closure tightness.

V4297A 

Allowable leakage 

(cc/hr)

a

Number of bubbles 

(per 10 sec.)

Low Capacity

235

8

High Capacity

470

16

M9547D

GAS
SUPPLY

UPSTREAM
MANUAL
GAS COCK

DOWNSTREAM
MANUAL
GAS COCK

BURNER

   D
LEAK 
TEST 
TAP

A

B

C

E

F

PRV

MANUAL
TEST
PETCOCK

SSOV

1/4 IN. (6 MM) 
FLEXIBLE
TUBING

1/4 IN. (6 MM)
ALUMINUM OR 
COPPER PILOT 
TUBING

JAR OR GLASS
WITH WATER

CUT AT
45 DEGREE
ANGLE

CAN ALSO BE A PERMANENT PETCOCK.

PRV = PRESSURE REGULATING VALVE.

SSOV = SAFETY SHUTOFF VALVE.

ONLY USE ONE OF THE DOWNSTREAM TAPS ON THE 550V.

1

2

3

4

4

2

3

1

1
2

(13 MM)

Содержание V4297A Series

Страница 1: ...alve body small applicable to five pipe sizes 3 4 in 19 mm 1 in 25 mm 1 1 4 in 32 mm 1 1 2 in 38 mm and 2 in 51 mm pipes Two valves with different capacities V4297A1005 1 in 25 mm internal opening small capacity V4297A1013 2 in 51 mm internal opening high capacity Two 1 4 in NPT upstream and one 1 4 in NPT downstream pressure taps and plugs Accepts C6097 Pressure Switch mounted directly to flange ...

Страница 2: ...s listed Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models V4297A1005 small body 1 in 25 mm internal opening small capacity V4297A1013 small body 2 in 51 mm internal opening high capacity Types of Gas Natural manufactured mixed or LP only Gas Train Pipe Size 3 4 in 19 mm 1 ...

Страница 3: ...00 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16534 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16535 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16536 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 ...

Страница 4: ...al connections Current Draw V4297A1005 small capacity 120V 0 2A V4297A1013 high capacity 120V 0 5A Valve Opening Time 1 sec Valve Closing Time 1 sec Dimensions See Fig 10 and 11 Weight V4297A1005 8 lb 3 6 kg V4297A1013 14 lb 6 3 kg Replacement Parts BBA51315 Coil for V4297A1005 BBA51318 Coil for V4297A1013 Accessories Pipe Adapters 32000109 001 3 4 in NPT 32000109 002 1 in NPT 32000109 003 1 1 4 i...

Страница 5: ...esign Certified Factory Mutual FM Approved KTCPI001 Visual Position Indicator required if used with pipe size larger than 3 4 in NOTE NOTE Some application codes such as NFPA require visual indication of the valve position as provided by the KTCPI001 Visual Position Indicator 2 51 5 127 5 1 2 140 5 5 8 143 2 1 2 64 1 1 2 38 2 51 2 3 4 70 1 2 13 5 3 4 147 5 5 8 143 9 229 M16541 TOP VIEW 2 51 5 127 ...

Страница 6: ...uctions on mounting a V4297A in a Honeywell Integrated Valve Train System Refer to the installation instructions packed with the Honeywell KTCPI001 Visual Position Indicator for mounting instructions of the indicator WIRING 1 Make sure all wiring agrees with all applicable local codes ordinances and regulations An opening is provided to accommodate rigid conduit or armored cable for line voltage o...

Страница 7: ...gas cock A 7 Run the V4297A Valve to is open position through the safety system then immediately de energize the system to close the V4297A Valve 8 Immerse a 1 4 in 6 mm tube vertically 1 2 in 13 mm into a jar of water 9 Slowly open the manual test petcock F 10 When the rate of bubbles coming through the water stabilizes count the number of bubbles appearing during a ten second period Each bubble ...

Страница 8: ... terminal block make sure all appropriate contacts in the thermostat or controller limits and flame safeguard controls are closed If one or more are open determine the cause s correct the trouble and proceed 4 If there is proper voltage at the valve but the valve still does not open check for normal gas pressure 5 If the valve still does not open replace the valve If the valve does not close when ...

Отзывы: