Honeywell V4297A Series Скачать руководство пользователя страница 1

PRODUCT DATA

65- 0246- 1

® U.S. Registered Trademark
Copyright © 2001 Honeywell •  All Rights Reserved 

V4297A

Solenoid Safety Shut-Off Valve

APPLICATION

The V4297A controls gas flow to commercial and industrial 
burners. The valve is part of the Honeywell Integrated Valve 
Train System that allows gas train components to be directly 
bolted together.

FEATURES

Used with natural or liquefied petroleum (LP) gases.

V4297A normally closed valves are rated for final 
shutoff service (safety shutoff).

One valve body (small) applicable to five pipe sizes:

3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in. (32 mm), 
1-1/2 in. (38 mm) and 2 in. (51 mm) pipes.

Two valves with different capacities:

V4297A1005: 1 in. (25 mm) internal opening 
(small capacity).

V4297A1013: 2 in. (51 mm) internal opening 
(high capacity).

Two 1/4 in. NPT upstream and one 1/4 in. NPT 
downstream pressure taps and plugs.

Accepts C6097 Pressure Switch mounted directly 
to flange (upstream pressure tap only).

NEMA 1 enclosure standard.

Optional Visual Position Indicator available.

Unpainted aluminum body.

Contents

Application ........................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information  ........................................................

2

Installation ........................................................................

6

Wiring ...............................................................................

6

Operation And Checkout  ..................................................

7

Troubleshooting ................................................................

8

Service Information  ..........................................................

8

Содержание V4297A Series

Страница 1: ...alve body small applicable to five pipe sizes 3 4 in 19 mm 1 in 25 mm 1 1 4 in 32 mm 1 1 2 in 38 mm and 2 in 51 mm pipes Two valves with different capacities V4297A1005 1 in 25 mm internal opening small capacity V4297A1013 2 in 51 mm internal opening high capacity Two 1 4 in NPT upstream and one 1 4 in NPT downstream pressure taps and plugs Accepts C6097 Pressure Switch mounted directly to flange ...

Страница 2: ...s listed Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models V4297A1005 small body 1 in 25 mm internal opening small capacity V4297A1013 small body 2 in 51 mm internal opening high capacity Types of Gas Natural manufactured mixed or LP only Gas Train Pipe Size 3 4 in 19 mm 1 ...

Страница 3: ...00 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16534 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16535 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 1 000 10 000 30 000 10 1 0 1 PRESSURE DROP IN WC FLOW CAPACITY cfh M16536 Propane sp gr 1 53 Natural Gas sp gr 0 64 LEGEND 100 100 ...

Страница 4: ...al connections Current Draw V4297A1005 small capacity 120V 0 2A V4297A1013 high capacity 120V 0 5A Valve Opening Time 1 sec Valve Closing Time 1 sec Dimensions See Fig 10 and 11 Weight V4297A1005 8 lb 3 6 kg V4297A1013 14 lb 6 3 kg Replacement Parts BBA51315 Coil for V4297A1005 BBA51318 Coil for V4297A1013 Accessories Pipe Adapters 32000109 001 3 4 in NPT 32000109 002 1 in NPT 32000109 003 1 1 4 i...

Страница 5: ...esign Certified Factory Mutual FM Approved KTCPI001 Visual Position Indicator required if used with pipe size larger than 3 4 in NOTE NOTE Some application codes such as NFPA require visual indication of the valve position as provided by the KTCPI001 Visual Position Indicator 2 51 5 127 5 1 2 140 5 5 8 143 2 1 2 64 1 1 2 38 2 51 2 3 4 70 1 2 13 5 3 4 147 5 5 8 143 9 229 M16541 TOP VIEW 2 51 5 127 ...

Страница 6: ...uctions on mounting a V4297A in a Honeywell Integrated Valve Train System Refer to the installation instructions packed with the Honeywell KTCPI001 Visual Position Indicator for mounting instructions of the indicator WIRING 1 Make sure all wiring agrees with all applicable local codes ordinances and regulations An opening is provided to accommodate rigid conduit or armored cable for line voltage o...

Страница 7: ...gas cock A 7 Run the V4297A Valve to is open position through the safety system then immediately de energize the system to close the V4297A Valve 8 Immerse a 1 4 in 6 mm tube vertically 1 2 in 13 mm into a jar of water 9 Slowly open the manual test petcock F 10 When the rate of bubbles coming through the water stabilizes count the number of bubbles appearing during a ten second period Each bubble ...

Страница 8: ... terminal block make sure all appropriate contacts in the thermostat or controller limits and flame safeguard controls are closed If one or more are open determine the cause s correct the trouble and proceed 4 If there is proper voltage at the valve but the valve still does not open check for normal gas pressure 5 If the valve still does not open replace the valve If the valve does not close when ...