Страница 1: ...s Line Voltage Operator V404B Low Voltage Operator V804B TABLE 1 MODEL SPECIFICATIONS MODEL NUMBER AMBIENT PRESSURE PRESSURE SUFFIX LETTER TEMPERATURE RANGE REGULATOR TYPE REGULATOR MODEL A 32 F to 175 F Standard Opening V5306A 0 C to 79 C C 32 F to 175 F Step Opening V5307A 0 C to 79 C M 40 F to 175 F Standard Opening V5306B 40 C to 79 C P 40 F to 175 F Step Opening V5307B 40 C to 79 C TABLE 2 GA...

Страница 2: ...tion follow these guidelines Locate in a well ventilated area Mount high enough above the cabinet bottom to avoid exposure to flooding or splashing water Ensuretheambienttemperaturedoesnotexceedthe ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust and grease accumulation Avoid locating where exposure to corrosive...

Страница 3: ...or routing to pilot burner Do not make sharp bends or deform tubing Do not bend tubing at control after compres sion nut has been tightened as this may result in gas leakage at connection 2 Square off and remove burrs from end of tubing Fig 2 Use moderate amount of pipe compound Fig 3 Top view of standard capacity gas control Fig 4 Always use new compression fitting CONNECT THERMOCOUPLE The thermo...

Страница 4: ...r main burner gas flow under control of thermostat and ignition module PERFORM GAS LEAK TEST WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE IN JURY OR DEATH Check for gas leaks with soap and water solution any time work is done on a gas control GAS LEAK TEST 1 Paint pipe connections upstream of gas control with rich soap and water solution Bubbles indicate gas leak 2 If leak is ...

Страница 5: ...ap or upstream of the gas control If inlet pressure is in the normal range refer to Tables 6 and 7 replace the existing control Otherwise take the necessary steps to provide proper gas pressure to the control 5 Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at leas...

Страница 6: ...e main gas supply valve is open and the pilot gas supply line is purged of air 2 Attempt to light pilot following procedure in Light Pilot page 4 If pilot still will not light a Check pilot gas adjustment screw If closed read just pilot flame Refer to page 4 b Performgasleaktestatcompressionfitting Ifleak is detected replace old compression fitting or tighten new one Refer to page 3 c Ensure that ...

Страница 7: ...control counterclock wise to PILOT 9 Push in gas control knob all the way and hold in Immediately light the pilot flame with a match and continue holding the gas control knob in for one minute after the pilot flame is lit 10 Releasegascontrolknobanditwillpopbackup Pilot flame should remain lit If pilot flame goes out repeat steps 1 through 10 If gas control knob does not pop up when released stopa...

Страница 8: ...f the world Manufacturing in U S A 1885 Douglas Drive N Australia Canada Finland France Germany Japan Mexico Netherlands Golden Valley MN 55422 4386 Spain Taiwan United Kingdom U S A CANADA 740 Ellesmere Road Scarborough Ontario M1P 2V9 PRINTED IN U S A QUALITY IS KEY ...