2

control.

3. Install sediment trap in gas supply line. Refer to Fig. 1.

INSTALL CONTROL

1. This control can be mounted 0-90 degrees, in any

direction, from the upright position of the gas control knob,
including vertically.

2. Mount the control so gas flow is in direction of arrow

on bottom of control.

3. Thread pipe the amount shown in Table 3 for insertion

into control. DO NOT THREAD PIPE TOO FAR. Valve
distortion or malfunction may result if pipe is inserted too
deeply.

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE IN-
JURY, OR DEATH

Follow these warnings exactly:
1. Disconnect power supply before wiring to prevent

electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas, turn

off gas supply at appliance service valve before
starting installation and perform Gas Leak Test
following installation.

3. Do not bend pilot gas tubing at control or at pilot

burner after compression fitting is tightened. Gas
leakage at the connection may result.

4. Always install sediment trap in gas supply line to

prevent contamination of gas control.

5. Do not force gas control knob. Use only your hand

to turn gas control knob. If the knob will not operate
by hand, the control should be replaced by a
qualified service technician. Force or attempted
repair may result in fire or explosion.

CAUTION

Never apply a jumper across (or short) gas control
coil terminals. This may burn out thermostat heat
anticipator.

IMPORTANT

These gas controls are shipped with protective seals
over inlet and outlet tappings. Do not remove seals
until ready to connect piping.

Follow the appliance manufacturer’s instructions if avail-

able; otherwise, use the instructions provided below as a
guide.

CHOOSE LOCATION

Do not locate the combination gas control where it may

be affected by steam cleaning, high humidity, dripping
water, corrosive chemicals, dust or grease accumulation,
or excessive heat. To ensure proper operation, follow these
guidelines.

Locate in a well ventilated area.

Mount high enough above the cabinet bottom to
avoid exposure to flooding or splashing water.

Ensure the ambient temperature does not exceed the
ambient temperature ratings for each component.

Cover gas control if appliance is cleaned with water,
steam, or chemicals or to avoid dust and grease
accumulation.

Avoid locating where exposure to corrosive chemical
fumes or dripping water are likely.

Mount combination gas control in the appliance vesti-

bule on the gas manifold. In replacement applications,
mount gas control in the same location as the old control.

INSTALL PIPING TO CONTROL

All piping must comply with local codes and ordinances

or with National Fuel Gas Code (ANSI Z223.1 NFPA No.
54), whichever applies. Tubing installation must comply
with approved standards and practices.

1. Use new, properly reamed pipe free from chips. If

tubing is used, make sure ends are square, deburred, and
clean. All tubing bends must be smooth and without defor-
mation.

2. Run pipe or tubing to the control. If tubing is used,

obtain a tube-to-pipe coupling to connect tubing to the

TABLE 3—NPT PIPE THREAD LENGTH (IN.).

OVERALL

MAXIMUM DEPTH PIPE

PIPE

THREAD

CAN BE INSERTED

SIZE

LENGTH

INTO CONTROL

3/8

9/16

3/8

1/2

3/4

1/2

3/4

13/16

3/4

1

9/16

1

4. Apply moderate amount of good quality pipe com-

pound to adapter, leaving two end threads bare. Refer to
Fig. 2. (On LP gas installations, use compound resistant to
LP gas.) Do not use Teflon tape.

5. Remove seals over control inlet and outlet, if neces-

sary.

6. Connect pipe to control inlet and outlet. To tighten inlet

and outlet connections, use wrench on projecting wrench
boss. Refer to Figs. 3 and 4.

Fig. 1—Install sediment trap.

GAS
CONTROL

GAS
CONTROL

HORIZONTAL

DROP

PIPED
GAS
SUPPLY

PIPED
GAS
SUPPLY

3 IN.

(76 MM)

MINIMUM

3 IN.

(76 MM)

MINIMUM

RISER

GAS
CONTROL

TUBING
GAS
SUPPLY

HORIZONTAL

DROP

3 IN.

(76 MM)

MINIMUM

RISER

M3077

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

Содержание V400

Страница 1: ...s Line Voltage Operator V404B Low Voltage Operator V804B TABLE 1 MODEL SPECIFICATIONS MODEL NUMBER AMBIENT PRESSURE PRESSURE SUFFIX LETTER TEMPERATURE RANGE REGULATOR TYPE REGULATOR MODEL A 32 F to 175 F Standard Opening V5306A 0 C to 79 C C 32 F to 175 F Step Opening V5307A 0 C to 79 C M 40 F to 175 F Standard Opening V5306B 40 C to 79 C P 40 F to 175 F Step Opening V5307B 40 C to 79 C TABLE 2 GA...

Страница 2: ...tion follow these guidelines Locate in a well ventilated area Mount high enough above the cabinet bottom to avoid exposure to flooding or splashing water Ensuretheambienttemperaturedoesnotexceedthe ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust and grease accumulation Avoid locating where exposure to corrosive...

Страница 3: ...or routing to pilot burner Do not make sharp bends or deform tubing Do not bend tubing at control after compres sion nut has been tightened as this may result in gas leakage at connection 2 Square off and remove burrs from end of tubing Fig 2 Use moderate amount of pipe compound Fig 3 Top view of standard capacity gas control Fig 4 Always use new compression fitting CONNECT THERMOCOUPLE The thermo...

Страница 4: ...r main burner gas flow under control of thermostat and ignition module PERFORM GAS LEAK TEST WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE IN JURY OR DEATH Check for gas leaks with soap and water solution any time work is done on a gas control GAS LEAK TEST 1 Paint pipe connections upstream of gas control with rich soap and water solution Bubbles indicate gas leak 2 If leak is ...

Страница 5: ...ap or upstream of the gas control If inlet pressure is in the normal range refer to Tables 6 and 7 replace the existing control Otherwise take the necessary steps to provide proper gas pressure to the control 5 Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at leas...

Страница 6: ...e main gas supply valve is open and the pilot gas supply line is purged of air 2 Attempt to light pilot following procedure in Light Pilot page 4 If pilot still will not light a Check pilot gas adjustment screw If closed read just pilot flame Refer to page 4 b Performgasleaktestatcompressionfitting Ifleak is detected replace old compression fitting or tighten new one Refer to page 3 c Ensure that ...

Страница 7: ...control counterclock wise to PILOT 9 Push in gas control knob all the way and hold in Immediately light the pilot flame with a match and continue holding the gas control knob in for one minute after the pilot flame is lit 10 Releasegascontrolknobanditwillpopbackup Pilot flame should remain lit If pilot flame goes out repeat steps 1 through 10 If gas control knob does not pop up when released stopa...

Страница 8: ...f the world Manufacturing in U S A 1885 Douglas Drive N Australia Canada Finland France Germany Japan Mexico Netherlands Golden Valley MN 55422 4386 Spain Taiwan United Kingdom U S A CANADA 740 Ellesmere Road Scarborough Ontario M1P 2V9 PRINTED IN U S A QUALITY IS KEY ...

Отзывы: