Honeywell V400 Скачать руководство пользователя страница 6

6

TABLE 7—PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa.

OUTLET PRESSURE

NOMINAL

SETTING

TYPE

NOMINAL INLET

FACTORY SETTING

RANGE

MODEL

OF GAS

PRESSURE RANGE

Step

Full Rate

Step

Full Rate

A,M

NATURAL

1.2-1.7

0.9

0.7-1.2

LP

2.9-3.9

2.7

2-3

C,P

NATURAL

1.2-1.7

0.2

0.9

None

0.7-1.2

LP

2.9-3.9

0.5

2.7

None

2-3

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE IN-
JURY OR DEATH
Perform the safety shutdown test any time work is
done on a gas module.

1. Place gas control knob in PILOT position. Main burner

should go off and pilot should remain lit.

2. Extinguish pilot flame. Pilot gas flow should stop

within 2-1/2 minutes. Safety shutoff of pilot gas provides
complete shutdown since safety shutoff valve blocks flow of
gas to main burner and pilot.

3. Relight pilot burner and operate system through one

complete cycle to make sure all controls operate properly.

6. Check power unit resistance. If above 11 ohms,

replace gas control.

IF MAIN BURNER WILL NOT COME ON WITH CALL
FOR HEAT

1. Make sure gas control knob is in the ON position.
2. Adjust thermostat several degrees above room tem-

perature.

3. Disconnect leadwires to lower left TH terminal and

lower right PP terminal to isolate valve operator coil from
balance of circuit. Measure resistance of coil. If coil is not 2
ohms 

±

10 percent, replace valve operator.

4. Measure the open and closed thermocouple output

voltages and compare to acceptable range charts in the
thermocouple specifications or in the Gas Controls Hand-
book. Replace the thermocouple if voltages are outside the
acceptable range.

IF BURNER IS OVERFIRING

Adjust pressure regulator to correct pressure. If regula-

tor cannot be adjusted and supply pressure is in normal
range, replace complete gas control.

SERVICE

CAUTION

Do not apply jumper across (or short) valve coil
terminals, even temporarily. Doing so may burn out
heat anticipator in thermostat.

IMPORTANT

Allow 60 seconds after shutdown before reener-
gizing step-opening model to ensure lightoff at step
pressure.

IF PILOT WILL NOT LIGHT

1. Ensure the main gas supply valve is open and the pilot

gas supply line is purged of air.

2. Attempt to light pilot following procedure in “Light

Pilot”, page 4. If pilot still will not light:

a. Check pilot gas adjustment screw. If closed, read-

just pilot flame. Refer to page 4.

b. Perform gas leak test at compression fitting. If leak

is detected, replace old compression fitting or tighten new
one. Refer to page 3.

c. Ensure that pilot burner tubing or orifice is not

clogged. If clogged, replace combination gas control.

IF PILOT GOES OUT WHEN GAS CONTROL KNOB IS
RELEASED

1. Make sure the gas control knob is held in at least one

minute to allow the thermocouple time to heat.

2. Check pilot flame adjustment, refer to page 4.
3. Check the wiring between the thermocouple and the

valve operator in the gas control.

4. Ensure jumper between valve operator and power

unit is secure and connections are clean.

5. If pilot still goes out, measure the open and closed

thermocouple circuit output voltages. Compare to accept-
able range charts in the thermocouple specifications or in
the Gas Controls Handbook. Replace the thermocouple if
voltages are outside the acceptable range.

INSTRUCTIONS TO THE HOMEOWNER

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE IN-
JURY, OR DEATH
Follow these warnings exactly:
1. Pilot must be lit manually. Follow these instruc-

tions exactly.

2. Before lighting, smell around the appliance for

gas. Be sure to smell next to floor because LP gas
is heavier than air.

3. IF YOU SMELL GAS:

Turn off gas supply at appliance service valve.
On LP gas systems, turn off gas supply at the
tank.

Do not light any appliances in the house.

Do not touch electrical switches or use the
phone.

Leave the building and use a neighbor’s phone
to call your gas supplier.

If you can not reach your gas supplier, call the
fire department.

4. Do not force the gas control knob. Use only your

hand to push down or turn the gas control knob.
Never use any tools. If the gas control knob will not
operate by hand, the gas control should be re-
placed by a qualified service technician. Force or
attempted repair may result in fire or explosion.

5. The gas control must be replaced in case of any

physical damage, tampering, bent terminals, miss-
ing or broken parts, stripped threads, or evidence
of exposure to heat.

Содержание V400

Страница 1: ...s Line Voltage Operator V404B Low Voltage Operator V804B TABLE 1 MODEL SPECIFICATIONS MODEL NUMBER AMBIENT PRESSURE PRESSURE SUFFIX LETTER TEMPERATURE RANGE REGULATOR TYPE REGULATOR MODEL A 32 F to 175 F Standard Opening V5306A 0 C to 79 C C 32 F to 175 F Step Opening V5307A 0 C to 79 C M 40 F to 175 F Standard Opening V5306B 40 C to 79 C P 40 F to 175 F Step Opening V5307B 40 C to 79 C TABLE 2 GA...

Страница 2: ...tion follow these guidelines Locate in a well ventilated area Mount high enough above the cabinet bottom to avoid exposure to flooding or splashing water Ensuretheambienttemperaturedoesnotexceedthe ambient temperature ratings for each component Cover gas control if appliance is cleaned with water steam or chemicals or to avoid dust and grease accumulation Avoid locating where exposure to corrosive...

Страница 3: ...or routing to pilot burner Do not make sharp bends or deform tubing Do not bend tubing at control after compres sion nut has been tightened as this may result in gas leakage at connection 2 Square off and remove burrs from end of tubing Fig 2 Use moderate amount of pipe compound Fig 3 Top view of standard capacity gas control Fig 4 Always use new compression fitting CONNECT THERMOCOUPLE The thermo...

Страница 4: ...r main burner gas flow under control of thermostat and ignition module PERFORM GAS LEAK TEST WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE IN JURY OR DEATH Check for gas leaks with soap and water solution any time work is done on a gas control GAS LEAK TEST 1 Paint pipe connections upstream of gas control with rich soap and water solution Bubbles indicate gas leak 2 If leak is ...

Страница 5: ...ap or upstream of the gas control If inlet pressure is in the normal range refer to Tables 6 and 7 replace the existing control Otherwise take the necessary steps to provide proper gas pressure to the control 5 Carefully check burner lightoff at step pressure Make sure burner lights smoothly and without flashback to orifice Make sure all ports remain lit Cycle burner several times allowing at leas...

Страница 6: ...e main gas supply valve is open and the pilot gas supply line is purged of air 2 Attempt to light pilot following procedure in Light Pilot page 4 If pilot still will not light a Check pilot gas adjustment screw If closed read just pilot flame Refer to page 4 b Performgasleaktestatcompressionfitting Ifleak is detected replace old compression fitting or tighten new one Refer to page 3 c Ensure that ...

Страница 7: ...control counterclock wise to PILOT 9 Push in gas control knob all the way and hold in Immediately light the pilot flame with a match and continue holding the gas control knob in for one minute after the pilot flame is lit 10 Releasegascontrolknobanditwillpopbackup Pilot flame should remain lit If pilot flame goes out repeat steps 1 through 10 If gas control knob does not pop up when released stopa...

Страница 8: ...f the world Manufacturing in U S A 1885 Douglas Drive N Australia Canada Finland France Germany Japan Mexico Netherlands Golden Valley MN 55422 4386 Spain Taiwan United Kingdom U S A CANADA 740 Ellesmere Road Scarborough Ontario M1P 2V9 PRINTED IN U S A QUALITY IS KEY ...

Отзывы: