Function Blocks
3/99
Function Block Reference Guide
229
2.74 TPSC (3POS) Function Block,
continued
Configuration Parameters,
continued
MOTOR
TAB, continued
Table 2-64 Motor Tab Configuration Parameters
Properties
Group
Parameter
Index#
Parameter Description
Value or Selection
Forward Relay
Output
Module
41
Module Number for
Forward Motor Direction
1 to 16
Channel
Channel Number for
Forward Motor Direction
1 to 4
Reverse Relay
Output
Module
42
Module Number for
Reverse Motor Direction
1 to 16
Channel
Channel Number for
Reverse Motor Direction
1 to 4
Motor Data
Deadband
(%)
43
Deadband is an
adjustable gap in which
neither output operates
0.5 to 5%
Traverse
Time (sec)
N/A
Motor Travel Time - the
time it takes the motor
to travel from 0 to100%
0 to 1800 Seconds
Example
Figure 2-78 shows a Function Block Diagram using a TPSC function block
3 position step control(without slidewire feedback) is accomplished by
assigning the motor control relays physical address under the Motor tab
section of the block configuration. See example below:
Note Motor-Relay Output Module &
Channel # assignment:
0601- Forward motor direction
0602 - Reverse motor direction
INC
DEC
Figure 2-78 TPSC Function Block Example