Function Blocks
Function Block Reference Guide
3/99
90
2.31 LPSW Function Block
Description
The
LPSW
label stands for
Loop Switch
.
This block is part of the
Loops
category. It looks like this
graphically on the Control Builder.
Function
Digital interface to control loops to initiate autotuning, change control action, force bumpless transfer,
select tuning set. Connects to a PID, TPSC, or CARB function blocks.
Inputs
ATC
= Autotune Command (OFF to ON initiates Autotuning)**
CACT
= Change Control Action (OFF to ON changes Control Action)
FBT
= Force Bumpless Transfer (OFF to ON Forces Bumpless Transfer)**
TUN1
= Tune Set 1 (OFF to ON switches to Tune Set 1*)**
TUN2
= Tune Set 2 ( (OFF to ON switches to Tune Set 2)**
*
Switch to Tune Set 1 overrides concurrent command to switch to Tune Set2
** Not available for ON/OFF function Block
Output
SWO
= The output of this block must connect to the SW1 input of a PID, CARB, and TPSC function
block.
Block Properties
Double click on the function block to access the function block properties dialog box.
Block Order (Read Only)
You can change the assigned execution order number by selecting “Execution Order” in the “Configure”
menu and arrange the order to suit your control strategy.