Function Blocks
3/99
Function Block Reference Guide
27
AMB Function Block,
continued
Configuration Parameters,
continued
ALARMS
TAB, continued
Table 2-7 Alarm Tab Configuration Parameters
Properties
Function
Parameter
Index#
Parameter Description
Value or Selection
Alarm 1
Setpoint 1
8
Alarm 1 Setpoint 1 Value
- this
is the value at which you want
the alarm type chose below to
activate
-5 to +105%
(default 0)
Type
N/A
Alarm 1 Setpoint 1 Type
- select
what you want Alarm 1 Setpoint
1 to represent.
Selections:
NO ALARM
AL_PV_HI
AL_PV_LO
AL_OUT_HI
AL_OUT_LO
Setpoint 2
9
Alarm 1 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 1 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm 2
Setpoint 1
10
Alarm 2 Setpoint 1 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 1 Type
Same as
Alarm 1 Setpoint 1
Setpoint 2
11
Alarm 2 Setpoint 2 Value
Same as
Alarm 1 Setpoint 1
Type
N/A
Alarm 2 Setpoint 2 Type
Same as
Alarm 1 Setpoint 1
Alarm
Hysteresis
%
16
Alarm Hysteresis in %
0 to 5 %
Continued next page