background image

U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR

32-00015—05

6

Fig. 5. Sighting opposed fired burners.

Mounting Accessories

1.

Cable assemblies for quick disconnect models are 
listed below. All are ITC/CIC approved, and meet 
IP67 at connector when properly installed.
• ASYU2S molded connector with 50 foot cable.
• ASYU2S-100 molded connector with 100 foot 

cable.

• ASYU2-200 molded connector with 200 foot 

cable.

• ASYU2-300 molded connector with 300 foot 

cable.

2.

Fiber Optic System - The U2 models are compatible 
with the Honeywell FASA Glass or Quartz fiber optic 
extension. Refer to Honeywell manual 69-2683

3.

U2-S supports Modbus protocol. The system can be 
monitored using user's hardware and software 
and/or Honeywell FlameTool for PC or Honeywell 
FlameTool for Panel (S7999). For detail refer to man-
ual 32-00001 and 32-00003. 

4.

There are several mounting accessories available 
from Honeywell. Please check with your sales person 
for detail.
a. R-518-PT12 (Ultem Iso PT Adapter)
b. R-518-PT12L (Ultem Iso PT Adapter with lens)
c. R-518-CL12-PG (Purge Air Coupler 1" NPTM & 

1/2" NPTF)

d. M-701-2 (Swivel Mount)
e. R-518-CL12-HTG (Locking Coupler). 

OPERATION

Available sensors continuously convert flame radiation to 
a magnitude displayed on the U2 display. The displayed 
value described further as "flamecount" is the sum of all 
active sensor readings. 

If flame count is greater than the flame on setpoint for 
longer than the time delay, a flame on condition is realized 
and the flame relay contacts are closed. The flame relay 
contacts remain closed until the flame count falls below 
the flame off setpoint for longer than the flame failure 

response time, at which a flame off condition is realized 
and the flame relay contacts are opened. Periodic self 
check performs fault detection, and if a fault is detected, 
both the flame relay and self check relay contacts are 
opened.

While File Input Select is low, file parameters defined at 
Modbus register 40093 are used to determine flame relay 
state. While file input select is high (+24V), file 1 parameter 
settings are used to determine flame relay state. 

File Select Output provides feedback to indicate the state 
of the file input select. See chart below:

There are several parameter adjustments that permit 
configuration of each sensor. . 

A touch wheel located at the back of the viewing head 
provides access to parameters for adjustment and 
configuration. The configuration menu is simple and easy 
to follow. Full character, 4-digit, scrolling LED displays are 
visible in the dark or sunlight. Individual sensor LEDs 
(model dependent 1, 2, or 3 total located below the 
display) flash to indicate the output of each sensor (green 
= UVTron, Blue = SSUV, Red = IR). The upper right green 
self-check LED provides indication, and status of the self 
check. The upper left red "Flame On" LED provides status 
of the flame relay.

NOTE:

The number of LEDs are model dependent.

The touch wheel is designed like an iPod™ to allow for slow 
or fast changes by moving a finger slower or faster around 
the back glass. Alternatively, the user may tap 

 (-) or 

 

(+) to make changes. Swirl finger at touchwheel > 360 
degrees and release to enter the menu. Tap 
ENTER/STORE to store selected data. Tap BACK to return 
to the previous menu. Exiting all of the menus will display 
the current flame count.

VIEWING HEAD

BURNER NOZZLE

NO. 1

NO. 1 FLAME

ENVELOPE

NO. 2 FLAME

ENVELOPE

VIEWING HEAD

BURNER 

NOZZLE NO. 2

HIGH FREQUENCY

IR ZONE

LOW FREQUENCY

ZONE (LESS THAN 

36HZ)

HIGH FREQUENCY

IR ZONE

M33287B

File Input Select Value

File Select Output Value

0V

0V

24V

24V

Содержание U2-1010S

Страница 1: ...and Recycling Waste electrical products should not be disposed of with general waste Please recycle where these facilities exist Check with your local authority for recycling advice GENERAL INFORMATION The Honeywell U2 101xS series model is a viewing head and signal processor in a single enclosure intended for use with a burner control system in Industrial Flame Monitoring applications There are s...

Страница 2: ... resettable for power source and Flame Relay Maximum furnace back pressure 35 Kg Cm2 500 PSI Selectable Flame Failure Response Time FFRT 1 2 3 seconds Error 0 0sec 0 5sec Internal Temperature Indication Degrees C or F in dis play menu of U2 or available at Modbus register 40019 Self Checking Internal electronic self checking is performed once per second to verify that system is operating properly ...

Страница 3: ...rried out by a qualified engineer and should meet all local standards and safety requirements Hazardous location installations require the use of ITC CIC approved cable installed in cable tray for non PF models and in metal conduit for PF models The cable installation must conform to the latest revision of the National Electrical Code or Canadian Electrical Code for Class I Division 2 non PF model...

Страница 4: ...entative for your application 1 Ensure location provides clear view of the flame under all operating conditions 2 If the burner is provided with a pipe mount use a bell type reducer to 1 NPT M 3 When using purge cooling air make sure hoses are electrically isolated from the Earth to prevent multi ple ground loops 4 Depending upon the application purge cooling air pressure and flow will be differen...

Страница 5: ...ation Fig 4 UV viewing head location DETECTOR IN GOOD SIGHTING POSITION PARALLEL SIGHTING BURNER NOZZLE CENTERLINE DETECTOR IN POOR SIGHTING POSITION LOW FREQUENCY FLICKER ZONE HIGH FREQUENCY FLICKER ZONE M33285B UV VIEWING HEAD SIGHTED ON UV ZONE BURNER NOZZLE CENTERLINE UV RADIATION ZONE M33286B ...

Страница 6: ...ition is realized and the flame relay contacts are opened Periodic self check performs fault detection and if a fault is detected both the flame relay and self check relay contacts are opened While File Input Select is low file parameters defined at Modbus register 40093 are used to determine flame relay state While file input select is high 24V file 1 parameter settings are used to determine flam...

Страница 7: ...g the MA gain does not alter gain settings of UVTron SSUV or IR After completing flame setpoint configuration adjustment to the MA gain may be used to set MA output at full system load Flame On Threshold Setting Displays the current Flame On threshold settings It is important to note that flame count must reach this threshold in order for the flame relay to energize After the flame relay is energi...

Страница 8: ... A factory default 4 digit access code is required to enable panel lock This code is only available from the factory Once enabled the same code will be required to modify parameters from the touch wheel interface Any attempt to make changes will generate the message Panel Locked Enter Code The display will show Bad upon entry of an incorrect access code Additionally a user may select a unique lock...

Страница 9: ...rently selected file parameters to default values See File Selection Factory Default Selecting factory default will reset all file parameters to default values along with additional settings of panel lock code baud rate communications address file selection register and number of active files allowed Temperature This menu displays the U2 internal temperature software version and device hours Tappi...

Страница 10: ...ube sensor supply failure Device must be replaced 8 IR SENSOR IR Sensor failure Adjust gain or apply orifice to lower flamecount If failure persists replace device 14 RELAYDRIVE FAILURE Relay drive failure device must be replaced 16 POWER FAILURE Clear Lockout Verify power source is correctly set before continuing 24V 120ma If error persists device must be replaced Symptoms Remedies No Display 1 C...

Страница 11: ...f threshold calculate FLAME ON Flame OFF ratio The ratio of 1 5 or higher is desirable Adjust flame ON and flame OFF thresholds to calculated values in step 3 5 Extinguish target flame while maximum background radiation is present Observe flamecount and increase filter setting s of sensor s to decrease total flamecount present from background radia tion The resulting background radiation flamecoun...

Страница 12: ...LOW FLAME SIGNAL INPUT 30VDC 1A MAX PURPLE FILE SELECT INPUT 30VDC MAX TAN FILE SELECT OUTPUT 24VDC 10ma MAX ORANGE mA OUPUT 500Ω MAX BLUE mA OUPUT 500Ω MAX WHITE RS485 BROWN RS485 RED 24V INPUT 120mA MAX BLACK POWER SUPPLY MCR35492 SCREW TO EARTH GROUND CABLE DRAIN TO EARTH GROUND FLAME RELAY SELF CHECK RELAY U2 101xS FLAMESCANNER BURNER CONTROL SYSTEM 500Ω MAX 24VDC SELV POWER SUPPLY ...

Страница 13: ...ion which is performed by a safety related system with the aim of achieving or maintaining a safe state for the plant in respect of a specified hazardous event Proof Test Periodic test performed to detect failures in a safety related system so that if necessary the system can be restored to an as new condition or as close as practical to this condition MTTR Mean Time To Restoration The average dur...

Страница 14: ... incandescent bulb for IR sensor deep UV light for solid state UV and UV tube sensors If none of these are available a flame may be used Note that IR and SSUV sensors require flickering light source Setup 1 Set power supply to OFF Connect U2 S model to power supply as described in manual 2 While performing the proof test disconnect or disre gard the signal processor so that any outputs due to test...

Страница 15: ... gain and store the setting Confirm the flamecount increased b Decrease the gain and store the setting Confirm the flamecount decreased 8 Restore all original settings as recorded in setup and reconnect the signal processor to the safety system Product Decommissioning When required decommissioning of the U2 S flamescanner should be performed in accordance with requirements of the overall safety sy...

Страница 16: ...A 30308 customer honeywell com Honeywell MAXON branded products 201 E 18th Street Muncie IN 47302 USA www maxoncorp com Belgium Maxon International BVBA Luchthavenlaan 16 18 1800 Vilvoorde Belgium Tel 32 2 255 09 09 Fax 32 2 251 82 41 U S Registered Trademark 2017 Honeywell International Inc 32 00015 05 M S Rev 10 17 Printed in United States ...

Отзывы: