INSTALLATION INSTRUCTIONS

®U.S. Registered Trademark
Copyright © 1997 Honeywell Inc.  •            •   All Rights Reserved

69-0774B-1

T874D Multistage Thermostat and

Q674A,D Subbases

APPLICATION

The T874D Thermostat and Q674A,D Subbases provide
24 to 30 Vac control of standard 2 stage heating and 2
stage cooling systems.

Q674A Subbase provides HEAT-AUTO-COOL system
switching and AUTO-ON fan switching.

OPERATION

The stages of heat 

make sequentially as the temperature

drops. 

Make refers to the mercury switch initiating a call for

heat or cool.

There are about 2

°

F (1

°

C) between stages so that the

second stage makes only when the first stage cannot
handle the load. This is the 

interstage differential.

RECYCLING NOTICE

This control contains mercury in a sealed tube. Do
not place control in the trash at the end of its useful
life.

If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of this control, or of an old control
containing mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could cause a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

IMPORTANT

An incorrectly leveled subbase will cause the
temperature control to deviate from setpoint. It is
not a calibration problem.

CAUTION

1.

Disconnect power supply to prevent electrical
shock or equipment damage.

2.

To prevent interference with the thermostat
linkage, keep wire length to a minimum and
run wires as close as possible to the subbase.

3.

Do not overtighten thermostat captive
mounting screws because damage to
subbase threads can result.

4.

Do not short across coil terminals on relay.
This can burn out the thermostat heat
anticipator.

Location

Install the thermostat about 5 ft (1.5 m) above the floor in
an area with good air circulation at average temperature.

Do not install the thermostat where it may be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Mount Subbase

The thermostat subbase can be mounted on a vertical
outlet box, horizontal outlet box or directly on the wall.

1.

If you must mount the subbase on a vertical outlet
box, order Honeywell part no. 193121A Adapter
Assembly. See Fig. 1. The assembly includes an
adapter ring, two screws and a cover plate to cover
marks on the wall. Install the ring and cover plate on
the vertical outlet box.

For a wall installation, hold subbase in position and mark
holes for anchors. See Fig. 2. Wall anchors must be
obtained from local hardware store. Be careful that the
wires do not fall back into the wall opening. Set aside
subbase. Drill four 3/16 in. (4.6 mm) holes and gently tap
anchors into the holes until flush with the wall.

2.

Pull electrical wires through the cover plate (if used)
and subbase cable opening. See Fig. 3.

3.

Secure the cover plate (if used) and subbase with
the screws provided. Do not fully tighten the
subbase screws.

Содержание Tradeline Q674A

Страница 1: ...re control to deviate from setpoint It is not a calibration problem CAUTION 1 Disconnect power supply to prevent electrical shock or equipment damage 2 To prevent interference with the thermostat linkage keep wire length to a minimum and run wires as close as possible to the subbase 3 Do not overtighten thermostat captive mounting screws because damage to subbase threads can result 4 Do not short ...

Страница 2: ... 2 Firmly tighten each terminal screw 3 Fit wires as close as possible to the subbase Push excess wire back into the hole 4 Plug hole with nonflammable insulation to prevent drafts from affecting the thermostat SPIRIT LEVEL MOUNTING HOLES 2 M927 TOP MOUNTING HOLES 2 WIRING TERMINAL THERMOSTAT CABLE OPENING TO SPRING FINGER CONTACTS ON THE THERMOSTAT UP TO 12 POST 2 FOR MOUNTING THERMOSTAT FOR STRA...

Страница 3: ...UMPER RC RH FOR SINGLE TRANSFORMER M5633 L1 HOT L2 1 COMPRESSOR CONTACTOR 2 COMPRESSOR CONTACTOR 1 H2 FALL C2 ANTICIPATOR RISE RISE C1 C2 THERMOSTAT SUBBASE SYSTEM COMPONENTS H2 ANTICIPATOR B NO FAN SWITCHING NO SYSTEM SWITCHING Fig 6 Schematic and hookup for T874D Thermostat and Q674A Subbase Fig 7 Mounting thermostat on subbase THERMOSTAT MOUNTING POST 2 M5631 50 60 70 80 50 60 70 80 HEAT COOL T...

Страница 4: ...s automatically controlled by the thermostat Cooling system is off AUTO thermostat automatically changes between heat and cool modes depending on indoor tempera ture COOL cooling system is automatically controlled by the thermosat Heating system is off Fan switching positions control fan operation as follows ON fan operates continuosly AUTO fan operatres as controlled by the thermostat in heat pum...

Страница 5: ...69 0774B 1 5 T874D MULTISTAGE THERMOSTAT AND Q674A D SUBBASES CALIBRATION Thermostat T874 Thermostats are accurately calibrated at the factory They do not have provision for field calibration ...

Страница 6: ... AND Q674A D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Rev 4 97 Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Страница 7: ...s Le fait de ne pas les suivre risque d endommager le produit ou de constituer un danger 2 Vérifier les caractéristiques nominales spécifiées dans les instructions et indiquées sur le produit pour s assurer que celui ci correspond à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente 4 Une fois l installation terminée vérifier le fonctionn...

Страница 8: ...st pas de niveau entraînera un écart entre la température ambiante et le point de consigne du thermostat Il ne s agit pas d un problème d étalonnage Thermostat multi étage T874D et plaques de commutation Q674A D MF925 ANNEAU D ADAPTATION PLAQUE DE COMMUTATION CACHE VIS DE FIXATION 2 VIS DE FIXATION 2 1 PLAQUE DE COMMUTATION VIS DE FIXATION 2 BOÎTE DE SORTIE HORIZONTALE 1 2 2 PIÈCE NON COMPRISE ACC...

Страница 9: ...le long de la bordure intérieure du haut du support du thermostat Ces ergots s insèrent dans les encoches de la plaque de commutation Installer le support du thermostat sur la plaque de commutation 5 Aligner les vis du support de thermostat sur les tiges de la plaque de commutation Voir Fig 7 Serrer les deux vis de fixation imperdables NE PAS TROP SERRER les vis pour éviter d endommager les tiges ...

Страница 10: ...tème de chauffage 1 Raccorder l ampèremètre c a avec la gamme de mesure appropriée entre les bornes de chauffage de la plaque de commutation Étage 1 ______entre W1 et RH Étage 2 ______entre W2 et RH TIGES DE FIXATION DU THERMOSTAT 2 MF5631 50 60 70 80 50 60 70 80 HEAT COOL TROUS DE FIXATION DU THERMOSTAT 2 PLAQUE DE COMMUTATION THERMOSTAT VIS DE FIXATION IMPERDABLES 2 2 Attendre une minute ensuite...

Страница 11: ...AT Placer le doigt de réglage du chauffage du thermostat T874 à environ 6 C 10 F au dessus de la température ambiante Les deux étages de chauffage et le ventilateur devraient se mettre en marche Placer le doigt de réglage du chauffage à environ 6 C 10 F au dessous de la température ambiante Le chauffage et le ventilateur devraient s arrêter REMARQUE Certains fabricants ajoutent une minuterie à leu...

Страница 12: ...D SUBBASES Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 69 0774B 1 C B Revu 4 97 Imprimé aux États Unis Home and Building Control Honeywell International Inc P O Box 524 Golden Valley MN 55422 ...

Отзывы: