VisionPRO® IAQ
3
69-1816EFS—03
0210
External fossil
fuel kit
1
External fossil fuel kit controls backup heat
0
Thermostat controls backup heat (outdoor sensor required)
0220
Stage 1 compressor
1cycle rate
E
Auto Discover
**
[Other options: 1 to CPH]
0230
Stage 2 compressor
cycle rate
E
Auto Discover
**
[Other options: 1 to 6 CPH]
0240
Stage 1 heat cycle
rate (CPH= cycles
per hour)
E
Auto Discover
**
[Other options: 1 to 12 CPH]
0250
Stage 2 stage heat
cycle rate (CPH)
E
Auto Discover
**
[Other options: 1 to 12 CPH]
0260
Stage 3 heat cycle
rate (CPH)
E
Auto Discover
**
[Other options: 1 to 12 CPH]
0280
Backlight
0
Backlight on for approx. 45 seconds after keypress
1
Backlight always on low intensity, full bright after keypress
0300
Manual/Auto
changeover
0
Manual
(User options: Heat/Cool/Off)
1
Automatic (User options: Heat/Cool/Auto/Off)
(System selects heat/cool based on indoor temp.)
0310
Auto changeover
deadband
3
Heat/cool settings 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)]
0320
Temperature display 0
Fahrenheit
1
Celsius
0330
Daylight savings
2
Auto-change to daylight savings time
(2007 and beyond, for
areas that use the new 2007 DST calendar)
1
Auto-change to daylight savings time (through 2006, and for areas
that do not use the new 2007 DST calendar)
0
Daylight savings time is turned off
0340
Indoor temp.
sensor
0
Display temp. at thermostat location only
1
Display temp. at indoor sensor location(s)
2
Average between thermostat & sensor location(s)
0342
Outdoor temp.
sensor
E
Auto Discover
**
0
None
1
Remote sensor
0345
Dual fuel heat
pump control
1
Balance point plus 2°F droop
**
0
Balance point only
**
2
Balance point/Aux Heat Lockout plus 2°F droop
**
0346
Dual fuel heat
pump upstage to
furnace timer
60
60 minutes
**
0
Off
[Other options: 30, 45 or 75 minutes]
0350
Heat pump
compressor lockout
0
No compressor lockout
**
[Other options: 5 to 60°F (-15°C to 15.5°C)]
0360
Heat pump
auxiliary lockout
0
No heat pump auxiliary lockout
**
[Other options: 5 to 65°F (-15°C to 18.5°C)]
0365
Discharge temp.
sensor
E
Auto Discover
**
0
No
1
Yes
0370
Indoor humidity
sensor
1
Internal sensor in thermostat
0
Sensors disabled
E
Auto Discover
**
Setup function
Settings & options (factory default in bold)
Installer setup
**See page 6