WIRELESS INSTALLATION & INTEGRATION REFERENCE GUIDE FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
27
63-4522—02
TB7600 Integration – Graphical User Interface Objects
The following objects should be typically used in a GUI:
• Room Temperature (Numeric);
• Occupied and Unoccupied Heat Setpoints (Numeric);
• Occupied and Unoccupied Cool Setpoints (Numeric);
• Outdoor Temperature (Numeric);
• Supply Temperature (Numeric) (If available);
• Occupancy Command (Enum);
• Effective Occupancy (Enum);
• System Mode RTU (Enum) or System Mode HPU (Enum);
• G Fan (Boolean);
• Y1 Cool (Boolean);
• Y2 Cool (Boolean);
• W1 Heat (Boolean);
• W2 Heat (Boolean) or Reversing Valve (Boolean);
• Economizer Output (Numeric) (if available);
• Aux (Boolean);
• DI 1 Status (Boolean);
• DI 2 Status (Boolean);
• Frost Alarm (Boolean) (if available);
• Filter Alarm (Boolean) (if available);
• Service Alarm (Boolean) (if available);
• Fan Lock Alarm (Boolean) (if available);
Fig. 21. Typical GUI for a TB7605B5014W with Economizer Control.
(BI 38)
(AV22)
(BI 25)
(BI 26)
(BI 27)
(BI 28)
(BI 29)
(MV 12)
(MV 14)
(BI 24)
(BI 31)
(BI 32)
(BI 36)
(BI 39)
(AI 16)
(AV 42)
(AV 43)
(AV 44)
(AV 45)
(AV 45)
(AV 45)