Honeywell T810D Скачать руководство пользователя страница 3

T810D; TS810B HEATING THERMOSTATS

3

69-1160B-1

SETTINGS AND CHECKOUT

Temperature Setting

Move the temperature setting lever to the desired 
setpoint on the thermostat scaleplate. See Fig. 1. 
Temperature is controlled to that point. On positive Off 
models, the control circuit is broken when the lever is 
moved to the extreme lowest end setting of the 
temperature scale.

Heat Anticipator Setting (T810D)

IMPORTANT

1. Use this thermostat only with controls that have 

current rating equal to (or within) the rating of 
the heat anticipator.

2. The T810D Thermostat is equipped with an 

adjustable heat anticipator and operates cor-
rectly only if this heater is adjusted to match the 
current draw of the primary valve or relay.

3. Do not use the T810 Thermostat on Powerpile® 

(millivolt) Systems. Use the TS810 THermostat 
that is designed for use on the Powerpile® 
(millivoltage) Systems.

The T810D features an adjustable heat anticipator rated 
from 0.18A to 0.8A at 30 Vac. This heat anticipator must 
be adjusted to match the current draw of the primary 
control for optimum thermostat performance. The rating 
of the primary control is stamped on the control 
nameplate. To adjust, move the anticipator indicator lever 
to correspond to the control rating.

If the setting and current rating are not available, wire the 
thermostat into the system, but do not attach it to the 
wall. If the thermostat is already mounted, remove it from 
the wall, leaving it connected to the system wiring.

Connect an ammeter of the appropriate range (about 
0.0A to 2.0A) between the terminals on the back of the 
thermostat. Move the temperature setting lever to a low 
setting so the contacts are broken. In cold weather, it 
may be necessary to hold the switch so the controls 
remain open. Allow the system to operate through the 
ammeter for one minute. Adjust the anticipator to match 
the meter reading.

NOTE: For best performance, the heat anticipator can 

require further adjustment. To lengthen burner-
on time, move the indicator in the direction of 
the longer arrows, but no more than one-half 
scale marking at a time. To shorten burner-on 
time, move the indicator in the opposite direc-
tion.

Checkout

CAUTION

Equipment Damage Hazard. 
Shorting across system controls can damage 
heat anticipator.

Do not short across system control terminals to 
check system operation. 

IMPORTANT

To assure accurate temperature control, do not 
touch or breathe on bimetal of thermometer.

1.

Observe the system through at least one complete 
automatic cycle.

2.

Be sure the system operates as intended.

3.

Check for correct operation of the positive Off 
switch, if used

Calibration

This thermostat is carefully calibrated at the factory and 
should not need field adjustment. If the thermostat seems 
out of adjustment, check as follows:

1.

Move the temperature setting lever to the lowest 
end setting of the temperature scale. Do not move 
the lever all the way to Off on models with positive 
Off switch. Wait at least five minutes.

2.

Remove the thermostat cover. Slowly move the 
temperature lever until the snap switch just makes 
contact.

3.

Replace the cover and wait five minutes for the 
cover and the thermostat to lose the heat gained 
from your hands. If the thermometer pointer and 
the setting lever indicator read approximately the 
same, no recalibration is needed.

If the thermostat needs recalibration, order part no. 
104994A Open-end Wrench. Follow the recalibration 
instructions included with the wrench.

Содержание T810D

Страница 1: ...ad these instructions carefully Failure to follow them could damage the product or cause a hazard ous condition 2 Check the ratings given in the Instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions CAUTION E...

Страница 2: ...mounting holes at each side of the device See Fig 1 Level the thermostat for best appearance 6 Replace the thermostat cover Fig 2 T810D in typical gas heating system Fig 3 Typical hookup for TS810B in millivolt system Fig 4 Internal schematic for all standard and positive Off heating models Table 1 Maximum Wiring Length Wire Size Maximum Length 2 Wire Cable Maximum Combined Length 2 Single Wires f...

Страница 3: ...to a low setting so the contacts are broken In cold weather it may be necessary to hold the switch so the controls remain open Allow the system to operate through the ammeter for one minute Adjust the anticipator to match the meter reading NOTE For best performance the heat anticipator can require further adjustment To lengthen burner on time move the indicator in the direction of the longer arrow...

Страница 4: ...l com yourhome T810D TS810B HEATING THERMOSTATS Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Страница 5: ...entes instructions Le fait de ne pas les suivre risque d endommager le produit ou pourrait constituer un danger 2 Vérifier les caractéristiques nominales indiquées dans les instructions et sur le produit et s assurer que l appareil convient à l application prévue 3 L installateur doit être un technicien d expérience ayant reçu une formation pertinente 4 Une fois l installation terminée vérifier le...

Страница 6: ...au le thermostat à des fins esthétiques 6 Remettre le couvercle sur le thermostat Fig 2 Le T810D dans un système type de chauffage au gaz Fig 3 Raccordement type du TS810B dans un système à tension millivolt Fig 4 Schéma interne pour tous les modèles pour chauffage standard et à coupure à OFF Tableau 1 Longuer maximale des fils Calibre de fils Longueur maximum Câble bifilaire Longueur combinee max...

Страница 7: ...pérature suffisamment basse pour couper les contacts Par temps froid il faut parfois tenir les contacts pour que les commandes restent ouvertes Faire fonctionner le système en laissant l ampèremètre branché pendant une minute Régler l anticipateur pour qu il indique la même grandeur que celle de l ampèremètre REMARQUE Pour un meilleur rendement il est parfois nécessaire d effectuer d autres réglag...

Страница 8: ...rhome THERMOSTATS DE CHAUFFAGE T810D ET TS810B Solutions de régulation et d automatisation Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Отзывы: