T775P SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0256—11
28
Fig. 69. Program - Sensor B - Max. Setpoint.
2.2.4. RESET B2 or OUTSD MAX
Sensor B value when Sensor A is at minimum.
1.
From the menu, use the
and
buttons to high-
light RESET B2 or OUTSD MAX.
2.
Press the
button to display the setpoint value.
3.
Use the
and
buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
4.
Press the
button to accept the value and display
the next option.
Fig. 70. Program - Throttling Range.
2.2.5. THROTTLING RANGE
The throttling range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.
1.
From the menu, use the
and
buttons to high-
light THROT RNG.
2.
Press the
button to display the throttling range
value.
3.
Use the
and
buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
4.
Press the
button to accept the value and display
the next option.
Fig. 71. Program - Sensor Selection.
2.2.6. SENSOR
Select Sensor A to use the Supply sensor as the
controlled temperature.
Select Sensor C to use the Return sensor as the
controlled temperature.
1.
From the menu, use the
and
buttons to high-
light SENSOR.
2.
Press the
button to display the sensor selections.
3.
Use the
and
buttons to select Sensor A or C.
Default: Sensor A
4.
Press the
button to accept the highlighted sensor
and display the next option.
Fig. 72. Program - Heat/Cool Selection.
2.2.7. HEAT/COOL
1.
From the menu, use the
and
buttons to high-
light HEAT/COOL.
Default: HEAT
2.
Press the
button to display the heat and cool
selections.
3.
Use the
and
buttons to select Heat or Cool.
4.
Press the
button to accept the value and display
the next option.
PROGRAM
RESET B2
MENU
PROGRAM
RESET B2
60
F
o
ENTER
MAXIMUM
VALUE FOR
OUTSIDE B
M24637
PROGRAM
THROT RNG
MENU
PROGRAM
THROT RNG
20
F
o
ENTER
THROTTLING
RANGE
M24638
PROGRAM
SENSOR
MENU
PROGRAM
SENSOR
SELECT
SENSOR FOR
STAGES
SENSOR A
SENSOR C
M24639
PROGRAM
HEAT/COOL
MENU
PROGRAM
HEAT/COOL
SELECT
HEAT/COOL
FOR
STAGES
HEAT
COOL
M24640