T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT

TROUBLESHOOTING GUIDE (Continued)

Symptom

Possible Cause

Action

Heating does not
come on.

No power to the thermostat.

Check that X terminal is connected to the system
transformer.

Check for 24 Vac between X and R or RH terminals.

If missing 24 Vac:

Check if the circuit breaker is tripped—reset the
circuit breaker.

Check if the system fuse is blown—replace the
fuse.  

Check if the system switch at the equipment is in
the Off position—set to On position.

Check wiring between the thermostat and the
HVAC equipment—replace any broken wires and
tighten any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum Off time is
activated and wait indicator is
displayed.

Wait up to five minutes for the system to respond.

Enter Installer Setup 38. Reconfigure minimum On time (if
required).

System selection is not set to
Heat.

Set system selection to Heat.

Cooling does not
come on.

No power to the thermostat.

Check that the X terminal is connected to the system
transformer.

Check for 24 Vac between X and R or RC and Y terminals.

If missing 24 Vac:

Check if the circuit breaker is tripped—reset the
circuit breaker.

Check if the system fuse is blown—replace the
fuse.  

Check if the system switch at the equipment is in
the Off position—set to the On position.

Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten
any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Cooling does not
come on
(continued)

Thermostat minimum Off time is
activated and wait indicator is
displayed.

Wait up to five minutes for the system to respond.

Enter Installer Setup 33. Reconfigure minimum Off time (if
required).

System selection is not set to
Cool.

Set system selection to Cool.

System On
indicator is lit, but
no heat is being
delivered.

Fan operation set to 00
(conventional heat) when it
should be set to 01 (electric
heat).

Enter Installer Setup mode number 02 and reconfigure the fan
operation.

Conventional heating  
equipment turns on the fan
when the furnace has  
warmed up to a setpoint.

Wait a minute after seeing the On indicator and then check the
registers.

Heating equipment is not
operating.

Verify operation of heating equipment in Self-Test.

24V is present on
all terminals.

When thermostat is powered
but is not connected to
heating/cooling equipment, arc
suppression will be present
(24V ghost voltage)

Connect heating/cooling equipment to the thermostat. Voltage
will drop to zero.

69-0964–2  D.S.  Rev. 12-98   Printed in Taiwan R.O.C.

www.honeywell.com/building/components

Содержание t7100f

Страница 1: ...taller must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Electrical Hazard Can cause electrical shock or equipment damage Disconnect power supply before installation X XX UL INSTALLATION INSTRUCTIONS T7100FMicroelectronicConventional orHeatPumpThermostat Mounting and Wiring Q7100 Subbase Refer to the s...

Страница 2: ...dels The T7100 temperature settings can be overridden in three ways Using the T7100 Override key acting as a toggle Using a remote setback timer Using an occupancy sensor The temperature settings change based on Installer Setup 27 NOTE Installer Setup 27 is factory set at zero degrees so this setting must be changed for the tempera ture to change The Override key changes the current temperature te...

Страница 3: ...up mode press the Information i key To change a setting use the increase or decrease key To exit the Installer Setup mode press and hold the Information i key until the display returns to normal approximately three seconds The display scrolls the mode numbers backward to get to the normal display The Installer Setup mode is automatically exited if no key presses are made for five minutes Fig 4 Dis...

Страница 4: ...s Fan key adjustment 21 00 Fan setting key is operational 01 Fan setting key is continuously in the Auto position Remote sensing 22 00 Remote sensing not activated 01 Remote sensing activated Temperature averaging networkc 23 00 Temperature averaging disabled 01 Temperature averaging between local sensor and remote sensor s activated Not used 24 Keypad lockout level 25 0 No lockout 01 02 01 View s...

Страница 5: ...f 20 29 Emergency heat Q7100C only equipment can be turned on and off 30 39 Cooling equipment can be turned on and off 40 49 Fan equipment can be turned on and off 60 69 Keyboard keys test 70 79 Thermostat information including date code and software versions is displayed Mode Number Press i key Factory Setting Other Choices Press or key to change Select to change Display Description Display Descr...

Страница 6: ...ing to emergency heating equipment Self Test 21 Emergency heat comes on 20 Emergency heat turns off Cooling Equipment Self Test i 30 Change from heating or emergency heating to cooling equipment self test 31 Stage one cooling and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Stage two cool turns off 30 Stage one cool and system fan turn off Fan Equipment ...

Страница 7: ...e the fuse Check if the power switch on the HVAC equipment is in the Off position set to the On position Check the wiring between the thermostat and the HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Thermostat microprocessor is locked up Remove the thermostat from the subbase for 2 minutes After 2 minutes replace the the...

Страница 8: ... breaker Check if the system fuse is blown replace the fuse Check if the system switch at the equipment is in the Off position set to the On position Check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Cooling does not come on continued Thermostat minimum Off time is activated and wait indic...

Отзывы: