T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
11
5. Press the increase
▲
key again to display the
EEPROM identification code.
(Example: 222 = EEPROM ID 222).
Table 8. Installer Self-Test Options.
M4867
6. Press and hold the increase
▲
and decrease
▼
keys
together, until the room temperature is displayed, to exit
the Self-Test. The Self-Test times out after five minutes
without any key presses.
a
Available on select models.
Key to
Press
Test
Number
Description
Heating Equipment Self-Test
i
10
Enter heating equipment Self-Test.
▲
11
Stage-one heat turns on. When Installer Setup number 01 is 01 or 02 is 01, the system fan is
also energized.
▲
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
▲
13
Stage-three heat turns on. Stage-one and stage-two heat remain on.
▼
12
Stage-three heat turns off.
▼
11
Stage-two heat turns off.
▼
10
Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select models of Q7100C subbase)
i
20
Change from heating to emergency heating equipment Self-Test.
▲
21
Emergency heat turns on. System fan also turns on.
▼
20
Emergency heat turns off.
Cooling Equipment Self-Test
i
30
Change from heating or emergency heating to cooling equipment Self-Test.
▲
31
Stage-one cool and system fan turn on.
▲
32
Stage-two cool and system fan turn on.
▼
31
Stage-two cool and system fan turn off.
▼
30
Stage-one cool and system fan turn off.
Fan Equipment Self-Test
i
40
Change from cooling to fan equipment Self-Test.
▲
41
Fan turns on.
▼
40
Fan turns off.
Key Test
a
i
60
Displays 2.
▲
60
Displays 4.
▼
60
Displays 3.
Override
60
Displays 5.
System
a
60
Displays 0.
Fan
a
60
Displays 1.