background image

SYLK™ I/O DEVICES

5

31-00028—02

Line-Loss

Devices must receive a minimum supply voltage of 20 Vac. 
If long power or output wire runs are required, a voltage 
drop due to Ohms Law (I x R) line-loss must be considered. 
This line-loss can result in a significant increase in total 
power required and thereby affect transformer sizing. The 
following example is an I x R line-loss calculation for a 200 
ft. (61m) run from the transformer to a device drawing 37 
VA and using two 18 AWG (1.0 sq mm) wires.

The formula is:

Loss = [length of round-trip wire run (ft.)] x [resistance 
in wire (ohms per ft.)] x [current in wire (amperes)]

From specification data:

18 AWG twisted pair wire has a resistance of 6.52 ohms 
per 1000 feet.

Loss = [(400 ft.) x (6.52/1000 ohms per ft.)] x [(37 
VA)/(24V)] = 4.02 volts

This means that four volts are going to be lost between the 
transformer and the device. To assure the device receives 
at least 20 volts, the transformer must output more than 
24 volts. Because all transformer output voltage levels 
depend on the size of the connected load, a larger 
transformer outputs a higher voltage than a smaller one 
for a given load. Fig. 3 shows this voltage load 
dependence.

In the preceding I x R loss example, even though the 
device load is only 37 VA, a standard 40 VA transformer is 
not sufficient due to the line-loss. Looking at Fig. 3, a 40 
VA transformer is just under 100 percent loaded (for the 
37 VA controller) and has a secondary voltage of 22.9 
volts. (Use the lower edge of the shaded zone in Fig. 3 that 
represents the worst case conditions.) When the I x R loss 
of four volts is subtracted, only 18.9 volts reaches the 
device. This is not enough voltage for proper operation.

In this situation, the engineer has three alternatives:

1.

Use a larger transformer. For example, if an 80 VA 
model is used, an output of 24.4 volts, minus the 
four volt line-loss, supplies 20.4V to the device (see 
Fig. 3). Although acceptable, the four-volt line-loss 
in this example is higher than recommended.

IMPORTANT

No installation should be designed where the 
line-loss is greater than two volts. This allows for 
nominal operation if the primary voltage drops to 
102 Vac (120 Vac minus 15 percent).

2.

Use heavier gauge wire for the power run. 14 AWG 
(2.0 sq mm) wire has a resistance of 2.57 ohms per 
1,000 ft. Using the preceding formula results in a 
line-loss of only 1.58 volts (compared with 4.02 
volts). This would allow a 40 VA transformer to be 
used. 14 AWG (2.0 sq mm) wire is the recommended 
wire size for 24 Vac wiring.

3.

Locate the transformer closer to the device. This 
reduces the length of the wire run, and the line-loss.

The issue of line-loss is also important in the case of the 
output wiring connected to the Triac digital outputs. The 
same formula and method are used. Keep all power and 
output wire runs as short as practical. When necessary, 
use heavier gauge wire, a bigger transformer, or install the 
transformer closer to the controller.

To meet the National Electrical Manufacturers Association 
(NEMA) standards, a transformer must stay within the 
NEMA limits. The chart in Fig. 3 shows the required limits 
at various loads.

With 100 percent load, the transformer secondary must 
supply between 23 and 25 volts to meet the NEMA 
standard. When a purchased transformer meets the 
NEMA standard DC20-1986, the transformer voltage 
regulating ability can be considered reliable. Compliance 
with the NEMA standard is voluntary.

Fig. 3. NEMA Class 2 transformer voltage output limits.

The Honeywell transformers listed in Table 5 meet the 
NEMA standard DC20-1986.

Table 5. Honeywell transformers that meet 

NEMA standard DC20-1986.

NOTE:

The AT88A and AT92A transformers do not meet 
the voluntary NEMA standard DC20-1986.

Wiring

All wiring must comply with applicable electrical codes 
and ordinances, or as specified on installation wiring 
diagrams. Device wiring is terminated to the screw 
terminal blocks located on the top and the bottom of the 
device.

Transformer Type

VA Rating

AT40A

40

AT72D

40

AT87A

50

AK3310 Assembly

100

27
26
25
24
23

22
21
20
19
18
17
16
15
14

0

50

100

150 

% OF LOAD

SECONDAR

Y

 VOL

TAGE

200 

M993

Содержание Sylk SI012000

Страница 1: ...ended for use in HVAC applications that require a programmable controller where the IO count is more than the full sized Spyder point count All devices provide flexible universal inputs for external sensors while SIO6042 and SIO4022 provide a combination of analog and digital outputs FEATURES Expands a single Spyder controller s IO count by 8 12 IO per device Up to three devices for Lon Spyders an...

Страница 2: ...able in three models see Table 1 Review the power input and output specifications on page 2 before installing the device Hardware driven by Triac outputs must have a minimum current draw when energized of 25 mA and a maximum current draw of 500 mA Hardware driven by the analog current outputs must have a maximum resistance of 550 Ohms resulting in a maximum voltage of 11 volts when driven at 20 mA...

Страница 3: ... bottom flex connectors Fig 2 Controller DIN rail mounting models SIO12000 SIO4022 and SIO6042 Power Before wiring the controller and device determine the input and output device requirements for each controller and device used in the system Select input and output devices compatible with the controller device and the application Consider the operating range wiring requirements and the environment...

Страница 4: ...ice requires 24 Vac power from an energy limited Class II power source To conform to Class II restrictions U S only transformers must not be larger than 100 VA A single transformer can power more than one device GUIDELINES FOR POWER WIRING ARE AS FOLLOWS For multiple devices operating from a single trans former the same side of the transformer secondary must be connected to the same power input te...

Страница 5: ...ple is higher than recommended IMPORTANT No installation should be designed where the line loss is greater than two volts This allows for nominal operation if the primary voltage drops to 102 Vac 120 Vac minus 15 percent 2 Use heavier gauge wire for the power run 14 AWG 2 0 sq mm wire has a resistance of 2 57 ohms per 1 000 ft Using the preceding formula results in a line loss of only 1 58 volts c...

Страница 6: ...ls IMPORTANT Use the heaviest gauge wire available up to 14 AWG 2 0 sq mm with a minimum of 18 AWG 1 0 sq mm for all power and earth ground wiring Screw type terminal blocks are designed to accept up to one 14 AWG 2 0 sq mm conductor or up to two 18 AWG 1 0 sq mm conductors More than two wires that are 18 AWG 2 0 sq mm can be con nected with a wire nut Include a pigtail with this wire group and at...

Страница 7: ...erent bus address and there may be multiple Sylk IOs wired on a single Sylk bus To change the bus address of a device adjust the address dipswitches to match that of the desired bus address 1 15 Use the bus address label shown in Fig 7 as a reference The default address for Sylk IOs is 1 The address on the device must match the address in the configuration tool Fig 7 Bus address settings Wiring Me...

Страница 8: ...NING MULTIPLE SYLK IOS HOME RUNNING MULTIPLE SYLK IOS TO CONTROLLER TO SYLK IO M35403 1 2 13 STRIP 1 2 IN 13 MM FROM WIRES TO BE ATTACHED AT ONE TERMINAL 1 2 TWIST WIRES TOGETHER WITH PLIERS A MINIMUM OF THREE TURNS 3 CUT TWISTED END OF WIRES TO 3 16 IN 5 MM BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION SIO4022 T...

Страница 9: ... mm for each controller in the group see Fig 6 on page 7 Verify that Triac wiring of the digital outputs to external devices uses the proper load power and 24 Vac common terminal digital output common terminals for High Side switching NOTE All wiring must comply with applicable electrical codes and ordinances or as specified on installa tion wiring diagrams For guidelines for wiring run lengths an...

Страница 10: ...ction WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before beginning device replacement to prevent electrical shock or equipment damage Terminal Block Removal To simplify device replacement all terminal blocks are designed to be removed with the wiring connections intact and then re installed on the new device See Fig 10 and refer to the f...

Страница 11: ...erminal block and do the same Repeat until the terminal block is evenly raised 1 4 in 6 35 mm from its alignment pins 2 Once the terminal block is raised 1 4 in 6 35 mm from its alignment pins grasp the terminal block at its center for long terminal blocks grasp it at each end and pull it straight up Device Replacement SIO12000 SIO4022 and SIO6042 Perform the following to replace the SIO12000 SIO4...

Страница 12: ... M S Rev 01 17 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the li...

Отзывы: