background image

SYLK™ I/O DEVICES

31-00028—02

4

IMPORTANT

• If a controller is used on Heating and Cooling 

Equipment (UL 1995, U.S. only) and transformer 
primary power is more than 150 volts, connect the 
transformer secondary common to earth ground 
(see Fig. 5 on page 6).

• When multiple controllers operate from a single 

transformer, connect the same side of the trans-
former secondary to the same power input termi-
nal in each device. The earth ground terminal 
(terminal 3) must be connected to a verified earth 
ground for each controller in the group (see Fig. 6 
on page 7
).

POWER BUDGET CALCULATION EXAMPLE

Table 3 is an example of a power budget calculation for 
typical Spyder LON controller and Sylk IO devices. While 
the example is shown for only these models, the process is 
applicable for all controller and device configurations.

Table 3. Power budget calculation example.

a

Excludes the use of digital Triac outputs.

The system example above requires 31.7 VA of peak power. 
Therefore, a 100 VA AT92A transformer could be used to 
power one controller and device of this type. Because the 
total peak power is less than 33 VA, this same transformer 
could be used to power this configuration and meet NEC 
Class 2 restrictions (no greater than 100 VA). 

See Fig. 4–Fig. 6 beginning on page 6 for illustrations of 
controller power wiring. See Table 4 for VA ratings of 
various devices.

Table 4. VA ratings for transformer sizing.

a

When used, each digital Triac output can add an addi-
tional 22 VA (peak) and 12 VA long-term.

For contactors and similar devices, the in-rush power ratings 
should be used as the worst case values when performing 
power budget calculations. Also, the application engineer 
must consider the possible combinations of simultaneously 
energized outputs and calculate the VA ratings accordingly. 
The worst case, which uses the largest possible VA load, 
should be determined when sizing the transformer. 

Each device requires 24 Vac power from an energy-limited 
Class II power source. To conform to Class II restrictions 
(U.S. only), transformers must not be larger than 100 VA. A 
single transformer can power more than one device.

GUIDELINES FOR POWER WIRING ARE AS FOLLOWS:

For multiple devices operating from a single trans-
former, the same side of the transformer secondary 
must be connected to the same power input termi-
nal in each device. The earth ground terminal must 
be connected to a verified earth ground for each 
device in the group (see Fig. 6 on page 7). Device 
configurations are not necessarily limited to three 
devices, but the total power draw, including acces-
sories, cannot exceed 100 VA when powered by the 
same transformer (U.S. only).

See Fig. 5 on page 6 for device power wiring used in 
UL 1995 equipment (U.S. only).

Many devices require all loads to be powered by the 
same transformer that powers the device.

Keep the earth ground connection wire run as short 
as possible (refer to Fig. 4–Fig. 6 beginning on 
page 6).

Do not connect earth ground to the device’s digital 
or analog ground terminals (refer to Fig. 4 and 
Fig. 6).

Unswitched 24 Vac power wiring can be run in the 
same conduit as the L

ON

W

ORKS

® Bus cable.

Device

VA

Informatio

n

Obtained  From

PUL6438SR

5.0

Spyder LON Product Data 
Sheet

SIO6042

5.0

a

See “Specifications” on 
page 2.

R8242A 
Contactor fan 
rating

21.0

TRADELINE

®

 Catalog 

inrush rating

D/X Stages

0.0

For example, assume 
cooling stage outputs are 
wired into a compressor 
control circuit and have 
no impact on the budget.

M6410A Steam 
Heating Coil 
Valve

0.7

TRADELINE

®

 Catalog, 

0.32A 24 Vac

TOTAL

31.7

Device

Description

VA

PVL0000AS, 
PVL4022AS, and 
PVL6436AS 
controllers and 
Series 60 Floating 
Damper Actuator

Controller and Actuator

a

9.0

PUL1012S, 
PUL4024S, 
PUL6438S,  
PVL4024NS, or   
PVL6438NS

Controller

a

5.0

SIO12000

IO Device

a

3.0

SIO4022

4.0

SIO642

5.0

ML684

Versadrive Valve Actuator

12.0

ML6161

Damper Actuator, 35 lb-in.

2.2

ML6185

Damper Actuator SR 50 lb-in 12.0

ML6464

Damper Actuator, 66 lb-in.

3.0

ML6474

Damper Actuator, 132 lb-in. 3.0

R6410A

Valve Actuator

0.7

R8242A

Contactor

21.0

Содержание Sylk SI012000

Страница 1: ...ended for use in HVAC applications that require a programmable controller where the IO count is more than the full sized Spyder point count All devices provide flexible universal inputs for external sensors while SIO6042 and SIO4022 provide a combination of analog and digital outputs FEATURES Expands a single Spyder controller s IO count by 8 12 IO per device Up to three devices for Lon Spyders an...

Страница 2: ...able in three models see Table 1 Review the power input and output specifications on page 2 before installing the device Hardware driven by Triac outputs must have a minimum current draw when energized of 25 mA and a maximum current draw of 500 mA Hardware driven by the analog current outputs must have a maximum resistance of 550 Ohms resulting in a maximum voltage of 11 volts when driven at 20 mA...

Страница 3: ... bottom flex connectors Fig 2 Controller DIN rail mounting models SIO12000 SIO4022 and SIO6042 Power Before wiring the controller and device determine the input and output device requirements for each controller and device used in the system Select input and output devices compatible with the controller device and the application Consider the operating range wiring requirements and the environment...

Страница 4: ...ice requires 24 Vac power from an energy limited Class II power source To conform to Class II restrictions U S only transformers must not be larger than 100 VA A single transformer can power more than one device GUIDELINES FOR POWER WIRING ARE AS FOLLOWS For multiple devices operating from a single trans former the same side of the transformer secondary must be connected to the same power input te...

Страница 5: ...ple is higher than recommended IMPORTANT No installation should be designed where the line loss is greater than two volts This allows for nominal operation if the primary voltage drops to 102 Vac 120 Vac minus 15 percent 2 Use heavier gauge wire for the power run 14 AWG 2 0 sq mm wire has a resistance of 2 57 ohms per 1 000 ft Using the preceding formula results in a line loss of only 1 58 volts c...

Страница 6: ...ls IMPORTANT Use the heaviest gauge wire available up to 14 AWG 2 0 sq mm with a minimum of 18 AWG 1 0 sq mm for all power and earth ground wiring Screw type terminal blocks are designed to accept up to one 14 AWG 2 0 sq mm conductor or up to two 18 AWG 1 0 sq mm conductors More than two wires that are 18 AWG 2 0 sq mm can be con nected with a wire nut Include a pigtail with this wire group and at...

Страница 7: ...erent bus address and there may be multiple Sylk IOs wired on a single Sylk bus To change the bus address of a device adjust the address dipswitches to match that of the desired bus address 1 15 Use the bus address label shown in Fig 7 as a reference The default address for Sylk IOs is 1 The address on the device must match the address in the configuration tool Fig 7 Bus address settings Wiring Me...

Страница 8: ...NING MULTIPLE SYLK IOS HOME RUNNING MULTIPLE SYLK IOS TO CONTROLLER TO SYLK IO M35403 1 2 13 STRIP 1 2 IN 13 MM FROM WIRES TO BE ATTACHED AT ONE TERMINAL 1 2 TWIST WIRES TOGETHER WITH PLIERS A MINIMUM OF THREE TURNS 3 CUT TWISTED END OF WIRES TO 3 16 IN 5 MM BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION SIO4022 T...

Страница 9: ... mm for each controller in the group see Fig 6 on page 7 Verify that Triac wiring of the digital outputs to external devices uses the proper load power and 24 Vac common terminal digital output common terminals for High Side switching NOTE All wiring must comply with applicable electrical codes and ordinances or as specified on installa tion wiring diagrams For guidelines for wiring run lengths an...

Страница 10: ...ction WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before beginning device replacement to prevent electrical shock or equipment damage Terminal Block Removal To simplify device replacement all terminal blocks are designed to be removed with the wiring connections intact and then re installed on the new device See Fig 10 and refer to the f...

Страница 11: ...erminal block and do the same Repeat until the terminal block is evenly raised 1 4 in 6 35 mm from its alignment pins 2 Once the terminal block is raised 1 4 in 6 35 mm from its alignment pins grasp the terminal block at its center for long terminal blocks grasp it at each end and pull it straight up Device Replacement SIO12000 SIO4022 and SIO6042 Perform the following to replace the SIO12000 SIO4...

Страница 12: ... M S Rev 01 17 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the li...

Отзывы: