background image

[7] FIELD WIRING; INSTALLATION GUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction . Proper wire gauges should be used . 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes . Improper con-
nections can prevent a system from responding properly in the event of a fire .

For signal wiring (the wiring between detectors or from detector to auxiliary 
devices), it is usually recommended that single conductor wire be no smaller 
than 18 gauge . The duct smoke detector terminals accommodate wire sizes up 
to 12 gauge . Flexible conduit is recommended for the last foot of conduit; solid 
conduit connections may be used if desired .

Duct smoke detectors and alarm system control panels have specifications for 
Signaling Line Circuit (SLC) wiring . Consult the control panel manufacturer’s 
specifications for wiring requirements before wiring the detector loop . 

[7.1] WIRING INSTRUCTIONS

Disconnect power from the communication line before installing the SK-Duct 
duct smoke detector . 

The SK-Duct detectors are designed for easy wiring . The housing provides a 
terminal strip with clamping plates . Wiring connections are made by sliding 
the bare end under the plate, and tightening the clamping plate screw . See 

Figure 6

 below for system wiring .

[7.2] SET THE ADDRESS

Set the desired address on the sensor head code wheel switches on the back 
of the sensor head .

[8] VERIFICATION OF OPERATION

[8.1] INSTALL THE COVER

Install the covers making sure that the cover fits into the base groove . Tighten 
the seven screws that are captured in the covers . Note that the cover must be 
properly installed for proper operation of the sensor .

[8.2] POWER THE UNIT

Activate the communication line on terminals COM + and COM – .

[8.3] DETECTOR CHECK

Standby – If programmed by the system control panel, look for the presence of 
the flashing LEDs through the transparent housing cover . The LED will flash 
with each communication .

Trouble – If programmed by the system control panel and the detector LEDs 
do not flash, then the detector lacks power (check wiring, missing or improp-
erly placed cover, panel programming, or power supply), the sensor head is 
missing (replace), or the unit is defective (return for repair) .

[8.4] DUCT SMOKE DETECTOR TEST & MAINTENANCE PROCEDURES

Test and maintain duct smoke detectors as recommended in NFPA 72 . The 
tests contained in this manual were devised to assist maintenance personnel 
in verification of proper detector operation . 

Before conducting these tests, notify the proper authorities that the smoke 
detection system will be temporarily out of service . Disable the zone or system 
under test to prevent unwanted alarms .

[8.4.1] TEST THE UNIT

1 .   M02-04-00 Magnet Test (not included) – This sensor can be functionally 

tested with a test magnet . The test magnet electronically simulates smoke 
in the sensing chamber, testing the sensor electronics and connections to 
the control panel .

2 .   Remote Test Accessory – The use of a remote accessory for visible indica-

tion of power and alarm is recommended . 

 

 Verify system control panel alarm status and control panel execution of all 
intended auxiliary functions (i .e . fan shutdown, damper control, etc .) .

 

 Two LEDs on the sensor are controlled by the panel to indicate sensor 
status . Coded signals, transmitted from the panel, can cause the LEDs 
to blink, latch on, or latch off . Refer to the control panel technical docu-
mentation for sensor LED operation and expected delay to alarm .

[8.4.2] THE DETECTOR MUST BE RESET BY THE SYSTEM CONTROL PANEL

[8.4.3] SMOKE ENTRY TEST USING AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM) . If the air speed is 
greater than 500 FPM, use a conventional manometer to measure differential 
pressure between the sampling tubes, as described under Measurement Tests 
on Page 3 .

Drill a 

1

4

-inch hole 3 feet upstream from the duct smoke detector . With the air 

handler on, measure the air velocity with an anemometer . Air speed must be 
at least 100 FPM . Spray aerosol smoke* into the duct through the 

1

4

-inch hole 

for five seconds . Wait two minutes for the duct smoke detector to alarm . If the 
duct smoke detector alarms, air is flowing through the detector . Remove the 
duct smoke detector cover and blow out the residual aerosol smoke from the 
chamber and reset the duct smoke detector at the panel . Use duct tape to seal 
the aerosol smoke entry hole . Remember to replace the cover after the test or 
the detector will not function properly .

*Aerosol smoke can be purchased from Home Safeguard Industries at 
homesafeguard .com, model 25S Smoke Detector Tester, and Chekkit Smoke 
Detector Tester model CHEK02 and CHEK06 available from SDi . When used 
properly, the canned smoke agent will cause the smoke detector to go into 
alarm . Refer to the manufacturer’s published instructions for proper use of the 
canned smoke agent .

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary by 
manufacturer . Misuse or overuse to these products may have long term adverse 
effects on the smoke detector . Consult the canned smoke agent manufacturer’s 
published instructions for any further warnings or caution statements .

[9] DETECTOR CLEANING PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 
maintenance, and that the system will temporarily be out of service . Disable 
the zone or system undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department .

[9.1] DETECTOR SENSOR

1 . Remove the sensor to be cleaned from the system .
2 .  Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place .

3 .  Vacuum the screen carefully without removing it . If further cleaning is re-

quired continue with Step 4, otherwise skip to Step 7 .

4 .  Remove the chamber cover/screen assembly by pulling it straight out .
5 .  Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber .

6 .  Reinstall the chamber cover/screen assembly by sliding the edge over the 

sensing chamber . Turn until it is firmly in place .

7 .  Replace the cover using the LEDs to align the cover and then gently pushing 

it until it locks into place .

8 . Reinstall the detector .

FIGURE 6. SYSTEM WIRING DIAGRAM FOR SK-DUCT:

HO572-00

COMM. 

LINE (+)

UL/FM LISTED 

CONTROL 

PANEL

1ST 

DETECTOR

IN LOOP

2ND 

DETECTOR

IN LOOP

COMM. 

LINE (–)

COMM. 

LINE

HO112-01

FIGURE 7. ROTARY ADDRESS SWITCHES

  

I56-3432-006 

 

 04-12

Содержание Silent Knight SK-Duct

Страница 1: ...iated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans blowers change over air handling systems etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system The SK Duct incorporates a sensor cover tamper feature that provides a trou ble signal at the panel immediately if the cover ...

Страница 2: ...R SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at 4 target centers 2 A for sampling tubes and 2 C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target C centers If desired drill an additiona...

Страница 3: ... greater than 0 15 volts there is enough air flow through the duct smoke detector for proper operation FIGURE 3 AIR DUCT DETECTOR SAMPLING TUBE SAMPLING TUBE ENDCAP ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION CAUTION The sampling tube end cap included with the detector is criti cal to proper operation of the duct smoke detector The end cap is needed to create the proper air flow to the sensor...

Страница 4: ...m control panel alarm status and control panel execution of all intended auxiliary functions i e fan shutdown damper control etc Two LEDs on the sensor are controlled by the panel to indicate sensor status Coded signals transmitted from the panel can cause the LEDs to blink latch on or latch off Refer to the control panel technical docu mentation for sensor LED operation and expected delay to alar...

Страница 5: ...on to operate 11 2 OPTION 2 REMOTE TEST USING A TEST COIL The use of a remote test station requires the installation of an accessory coil part number DCOIL sold separately 1 Install DCOIL in housing pocket insuring that arrow is pointing toward detector 2 Install DCOIL mounting screw 3 Connect each DCOIL lead to a Test Coil Terminal See Figure 10 below for reference FIGURE 10 SK DUCT USING A TEST ...

Страница 6: ...d to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequen tial or inc...

Отзывы: