[9.2] REINSTALLATION

1 . Reinstall the detector in its housing .
2 . Restore system power . 
3 . Perform Detector Check .
4 .  Notify the proper authorities testing has been completed and the smoke 

detector system is back in operation .

[10] SENSOR REPLACEMENT

1 . Remove the sensor head by rotating counterclockwise .
2 . Pull gently to remove it . 
3 .  To replace the sensor head, align the mounting features and rotate clock-

wise into place .

[11] OPTIONAL ACCESSORIES

Optional accessories include RA400Z/RA100Z, RTS451/RTS151 and 

 

RTS451KEY/RTS151KEY .

NOTE: Ensure blue wire always remains connected to RA+ on the field 
connector side of the terminal block.

Note: If using a RA400Z, the tab should be broken for use with the intelli-
gent duct smoke detector. If using RA100Z, ensure that jumper is removed.

The RTS451/RTS151/RTS451KEY/RTS151KEY Remote Test Station facilitates 
test of the alarm capability of the duct smoke detector . These accessories pro-
vide the stimulus to initiate an alarm condition at the detector . The SK-Duct 
duct smoke detector must be reset by the system control panel .

[11.1] OPTION 1: 

REMOTE TEST USING SENSOR WITH REMOTE TEST CAPABILITY

(WITHOUT A TEST COIL):

A sensor with suffix "R" is available for use inside the SK-Duct . Suffix "R"  
represents a head with Remote Test Capability . Using this head inside the 
SK-Duct eliminates the need for a test coil when wired to a RTS451/RTS151/ 
RTS451KEY/RTS151KEY Remote Test Station .

To install the RTS451/RTS151/RTS451KEY/RTS151KEY, using the sensor with  
remote test capability connect the device as shown in 

Figure 9

; wire runs must 

be limited to 25 

Ω

 or less per interconnecting wire . 

NOTE: Resistor assembly must be in place between RA+ and OUT+  
inside the SK-Duct for Remote Test function to operate.

[11.2] OPTION 2: 

REMOTE TEST USING A TEST COIL:

 

The use of a remote test station requires the installation of an accessory 
coil, part number DCOIL, sold separately.

 

1)   Install DCOIL in housing pocket insuring that arrow is pointing toward detector .
2)  Install DCOIL mounting screw .
3)  Connect each DCOIL lead to a Test Coil Terminal .

See 

Figure 10

 below for reference .

FIGURE 10. SK-DUCT USING A TEST COIL

TEST COIL TERMINALS

DCOIL

TEST COIL SCREW

H0561-01

FIGURE 8. WIRING DIAGRAM FOR TO RA400Z/RA100Z:

RTS451/RTS451KEY

RTS151/RTS151KEY

JUMPER

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

H0633-00

FIGURE 9. RTS451/RTS451KEY/RTS151/RTS151KEY USING  

SENSOR WITH REMOTE TEST CAPABILITY

(+)

(-)

RA400Z/RA100Z

– RA

+ RA

REMOTE ALARM LED 

OPTION 1 PER UNIT 

H0570-03

FIGURE 11. WIRING DIAGRAM FROM SK-DUCT TO RTS451/RTS151/ 

RTS451KEY/RTS151KEY USING A TEST COIL:

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS451/151,

RTS451/151KEY

REMOTE TEST STATION

LED OPTION

1 PER UNIT

10mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

NOTE: The RTS451/151, RTS451/151KEY test coil circuit requires an 

 

external 24 VDC power supply which must be UL listed.

[11.3] ADDITIONAL MODULE OPTION

The SK-Duct can also accommodate a relay or control module (sold sepa-
rately) within the power board side of the housing . The relay or control mod-
ule must be listed as compatible to the fire alarm control panel .

Physical Module Mounting 

1)  Remove the breakaway tabs at the four corners of the module
2)   Locate the module at right most corner of the power board . The upper 

left corner mounting hole of the module will align with a screw boss in 
the housing .

3)   Install a #8×

3

8

˝ Plastite screw at the screw boss location

Note: See the corresponding module Installation Instructions for general  
description, control panel compatibility, wiring and ratings .

H0571-07

  

I56-3432-006 

 

 04-12

Содержание Silent Knight SK-Duct

Страница 1: ...iated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans blowers change over air handling systems etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system The SK Duct incorporates a sensor cover tamper feature that provides a trou ble signal at the panel immediately if the cover ...

Страница 2: ...R SQUARE TOP OVER BOTTOM MOUNTING CONFIGURATION Center punch at 4 target centers 2 A for sampling tubes and 2 C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 1 375 inch diameter holes using a 13 8 inch hole saw or punch Drill 156 inch diameter holes using a 5 32 inch drill at target C centers If desired drill an additiona...

Страница 3: ... greater than 0 15 volts there is enough air flow through the duct smoke detector for proper operation FIGURE 3 AIR DUCT DETECTOR SAMPLING TUBE SAMPLING TUBE ENDCAP ARROW MUST FACE INTO AIR FLOW AIR FLOW DIRECTION CAUTION The sampling tube end cap included with the detector is criti cal to proper operation of the duct smoke detector The end cap is needed to create the proper air flow to the sensor...

Страница 4: ...m control panel alarm status and control panel execution of all intended auxiliary functions i e fan shutdown damper control etc Two LEDs on the sensor are controlled by the panel to indicate sensor status Coded signals transmitted from the panel can cause the LEDs to blink latch on or latch off Refer to the control panel technical docu mentation for sensor LED operation and expected delay to alar...

Страница 5: ...on to operate 11 2 OPTION 2 REMOTE TEST USING A TEST COIL The use of a remote test station requires the installation of an accessory coil part number DCOIL sold separately 1 Install DCOIL in housing pocket insuring that arrow is pointing toward detector 2 Install DCOIL mounting screw 3 Connect each DCOIL lead to a Test Coil Terminal See Figure 10 below for reference FIGURE 10 SK DUCT USING A TEST ...

Страница 6: ...d to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequen tial or inc...

Отзывы: