5895XL Manual - P/N 151142-L8:L 08/09/2017
27
Conventional Relay Installation
Hardware Installation
Installing 4-Wire Class A Smoke Detectors
Figure 3.19 illustrates how to install 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1.
Up to two Class A 4-wire loops can be connected to the control panel at once.
2.
Smoke power is supplied to each Class A loop as shown in Figure 3.19.
Figure 3.19 Class A 4-Wire Smoke Detector Connections
3.5.6 Auxiliary Power Configuration
Circuits 1-6 on the control panel can be used as auxiliary power circuits. The four types of auxiliary power available are:
•
Door Holder
•
Constant
•
Resettable Power
•
Sounder Sync Power
Auxiliary power circuits are power limited. Each circuit can source up to 3A (total current for all circuits must not exceed 6A).
To install an auxiliary power circuit:
1.
Wire the circuit(s) that will be used for auxiliary power.
2.
Configure the auxiliary power output through programming.
Door Holder Power
Door holder power is intended for fire door applications. When there are no fire system alarms in the system and the panel has AC
power, door holder circuits have 24 volt power present at their terminals. Any fire system alarm will cause power to disconnect. Power
will be re-applied when the fire system is reset. If AC power is not present, the auxiliary door holder power will be disconnected to con-
serve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits.
Constant Power
Use constant power for applications that require a constant auxiliary power source. Power is always present at Constant circuits.
Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits
selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is
disconnected from the terminals for 30 seconds, then re-applied.
Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases.
3.6 Conventional Relay Installation
5895XL relay circuits are installed in exactly the same way as the FACP relay circuits. Refer to the FACP Installation Manual for infor-
mation on installing conventional relays.
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
NOTE:
In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.19 uses I/O circuits 1, 2, 3 together and 4, 5, 6 together. In programming (1, 2, 3) would be referred to as point 1, and (4, 5, 6) would be
referred to as point 4.