5895XL Manual - P/N 151142-L8:L 08/09/2017
11
Calculating Current Draw and Standby Battery
Before You Begin Installing
6815 SLC Expander
(63 max.)
Standby/Alarm: 78 mA
mA
mA
6860 Remote LCD Annunciator
(16 max.)
Standby: 25 mA
mA
Alarm: 50 mA
mA
5860 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
6855 Remote LCD Annunciator
Standby: 20 mA
mA
Alarm: 25 mA
mA
5824 Serial/Parallel I/O Module
(4 max.)
Standby/Alarm: 45 mA
mA
mA
5895XL Power Supply
(16 max.)
Standby/Alarm: 10 mA
mA
mA
5496 NAC Expander
Standby/Alarm: 10 mA
mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby: 35 mA
mA
Alarm: 145 mA
mA
5865-3 LED Annunciator
Standby: 35 mA
mA
Alarm: 145 mA
mA
5880 I/O Module
Standby: 35 mA
mA
Alarm: 200 mA
mA
5883 Relay Interface
(32 max.)
Standby: 0 mA
mA
Alarm: 220 mA
(22 mA per relay)
mA
EVS-50W or EVS-125W Audio
Amplifier with/without EVS-CE4
(4 max.)
Standby: 10 mA
mA
Alarm: 10 mA
mA
EVS-INT50W Internal Amplifier
(4 max.)
Standby: 52 mA
mA
Alarm @ 25V: 275 mA
mA
Alarm @ 70V: 310 mA
mA
EVS-VCM Voice Control Module
(1 max.)
Standby: 70 mA
mA
Alarm: 100 mA
mA
EVS-SW24 Switch Expander
(5 max.)
Standby: 10 mA
mA
Alarm: 25 mA
mA
EVS-RPU Remote Paging Unit
(4 max.)
Standby: 70 mA
mA
Alarm: 100 mA
mA
EVS-LOC Local Operating Console
(includes 6860, RVM & SW-24)
(4 max.)
Standby: 100 mA
mA
Alarm: 150 mA
mA
EVS-100W 100W amplifier
(4 max.)
Standby/Alarm: 10 mA
mA
mA
EVS-100WBU backup daughter card
(4 max.)
Standby/Alarm: 10 mA
mA
mA
Total System Current
Network Cards
SK-NIC Network Interface Card
(1 Max.)
Standby/Alarm: 21 mA
mA
mA
SK-FML Fiber Optic Multi Mode
(1 Max.)
Standby/Alarm: 53 mA
mA
mA
SK-FSL Fiber Optic Single Mode
(1 Max.)
Standby/Alarm: 79 mA
mA
mA
Wireless Modules
WSK-WGI Wireless Gateway
Max current using ext supply 40 mA
mA
mA
Max current SLC Power 24 mA
mA
mA
Auxiliary Devices
4
Refer to devices manual for current rating.
IPDACT-2 IP Communicator
(1 max.)
Standby: 93 mA
mA
Alarm: 136 mA
mA
IPDACT-2UD IP Communicator
(1 max.)
Standby: 98 mA
mA
Alarm: 155 mA
mA
CELL-MOD/CELL-CAB-SK
Standby: 55 mA
mA
Alarm: 100 mA
mA
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current