5895XL Manual - P/N 151142-L8:L 08/09/2017
Before You Begin Installing
Calculating Current Draw and Standby Battery
1.
The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2.
If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24 VAC, 120 VAC or 240 VAC.
3.
If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that
time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be drawn
from the panel.
4.
Use next size battery with capacity greater than required.
5.
Total does not include isolator devices or accessory bases.
* Use a separate worksheet for each 5895XL.
EVS-RPU Remote Paging Unit
(4 max.)
Standby: 70 mA
mA
Alarm: 100 mA
mA
EVS-LOC Remote Command Unit
(includes 6860, RVM & SW-24)
(4 max.)
Standby: 100 mA
mA
Alarm: 150 mA
mA
EVS-100W 100W Amplifier
(4 max.)
Standby/Alarm: 10 mA
mA
mA
EVS-100WBU backup daughter card
(4 max.)
Standby/Alarm: 10 mA
mA
mA
A
Total System Current
Network Cards
SK-NIC Network Interface Card
(1 Max.)
Standby/Alarm: 21 mA
mA
mA
SK-FML Fiber Optic Multi Mode
(1 Max.)
Standby/Alarm: 53 mA
mA
mA
SK-FSL Fiber Optic Single Mode
(1 Max.)
Standby/Alarm: 79 mA
mA
mA
Auxiliary Devices
3
Refer to devices manual for current rating.
IPDACT-2 IP Communicator
(1 max.)
Standby: 93 mA
mA
Alarm: 136 mA
mA
IPDACT-2UD IP Communicator
(1 max.)
Standby: 98 mA
mA
Alarm: 155 mA
mA
CELL-MOD/CELL-CAB-SK
Standby: 55 mA
mA
Alarm: 100 mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
Alarm/Standby: mA
mA
mA
B
Auxiliary Devices Current
Notification Appliance Circuits
Refer to device manual for current rating.
5495/5499 Power Supply
24 VDC
One input circuit: 15 mA
mA
Both input circuits: 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA
E
Total current ratings converted to amperes (line D x .001):
A
A
F
Number of standby hours:
H
G
Multiply lines E and F.
Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
Add lines G and I.
4
Total ampere hours
required
AH
Table 2.5 Current Draw Worksheet for SD SLC Devices
Device
# of Devices
Current per Device
Standby
Current
Alarm
Current