T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 4. Installer System Test Options.
Heat
Auto
System
Fan
Off
Auto
Un
Mon
Wait
Lo
In
Room
Remote
%Humid
Auto
Sav
AM
PM
Comm
Cool
Duct
Only
On
Recovery
Hi
Med
Cool
TueWedThuFriSatSun
Occupied 12 Override
M4916
Aux Ht
Aux Ht
Em Ht
Em Ht
Set Program
Set Program
Set Day/Time
Set Day/Time
Start Time
Temporary Setting Enrg
Em Heat
M10257A
TEST NUMBER
4.. Press Run Program.
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
Table 3. Tests Available in Installer System Test.
Fig. 6. Display of test number.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
NOTE:
Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.
M4954A
Set Program
Set Temperature
Change
Time/Temp
Occupied
Temp
Unoccupied
Start Time
Day
System
Fan
Copy
Occupied
Start Time
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Day/Time
Clear
Start Time
Unoccupied
Temp
Heat/Cool
Settings
Auto
System
Fan
Mon
Room
AM
Occupied 1
Heat
Run
Program
To start the system test:
CAUTION
The minimum off time for compressors is bypassed
during the Installer System Test. Equipment
damage can occur if the compressor is cycled too
quickly.
Press and hold the increase
▲
and
▼
decrease keys, at
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Fig. 5 and 6.
Fig. 5. Display of all the segments of the LCD.
(continued)
Key to
Press
Test
Number
Description
Heating Equipment System Test
Heat/Cool Settings
10
Enter heating equipment system test.
▲
11
Stage-one heat comes on. When Installer Setup number 02 is 01, the system fan
is also energized.
▲
12
Stage-two heat comes on. Stage-one heat and system fan remain on.
▲
13
Stage-three heat comes on. Stage-one and stage-two heat with the system fan
are on.
▼
12
Stage-three heat turns off.
▼
11
Stage-two heat turns off.
▼
10
Stage-one heat and system fan turn off.
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and off
30 to 39
Cooling equipment can be turned on and off
40 to 49
Fan equipment can be turned on and off
60 0 to
60 19
Keyboard keys test
70 to 79
Thermostat information including date code,
software versions and subbase identification
are displayed