T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT

Thermostat Information

1. Press the Heat/Cool Settings key to access the

thermostat information.

M4934

2. Press the increase

 ▲

 

key to display the production

date code. The first two large digits are the month
and the third digit is the last digit of the year.
(Example: 036 = March 1996)

M4931

3. Press the increase

 ▲

 

key again to display the

software identification code. (Example: 02 =
software ID code 2)

M4932A

4. Press the increase

 ▲

 

key again to display the

software revision number. (Example: 001 = revision
number 1)

M10229

Table 4. Installer Self-Test Options (Continued).

Key to  

Press

Test

Number

Description

Cooling Equipment System Test

Heat/Cool Settings

30

Change from heating to cooling equipment system test.

  

31

Stage-one cooling and system fan come on.

  

32

Stage-two cool comes on. Stage-one cool and system fan remain on.

  

33

Stage-three cool comes on (Q7300G only). Stage-one and stage-two cool with
system fan remain on.

 

 

32

Stage-three cool turns off.

  

31

Stage-two cool turns off.

  

30

Stage-one cool and system fan turn off.

Fan Equipment System Test

Heat/Cool Settings

40

Change from cooling to fan equipment system test.

  

41

Fan comes on.

  

40

Fan turns off.

Key Operation System Test

Heat/Cool Settings

60   2

Change from fan to key operation system test.

Unoccupied Temp

60   0

Unoccupied Temp test number is displayed.

Occupied Temp

60   1

Occupied Temp test number is displayed.

▲   

60   3

Increase test number is displayed.

▼   

60   5

Decrease test number is displayed.

Clear Start Time

60   7

Clear Start Time test number is displayed.

Day

60   8

Day test number is displayed.

Copy

60   9

Copy test number is displayed.

Unoccupied Start

TIme

60   10

Unoccupied Start Time test number is displayed.

System

60   11

System test number is displayed.

Fan

60   12

Fan test number is displayed.

Set Current

Day/Time

60   14

Set Current Day/Time test number is displayed.

Run Program

60   15

Run Program test number is displayed.

Temporary

Occupied

60   16

Temporary Occupied test number is displayed.

Occupied Start Time

60   17

Occupied Start Time test number is displayed.

Continuous

Unoccupied

60   19

Continuous Unoccupied test number is displayed.

Содержание SERIES 2000 T7300D

Страница 1: ...duct 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operat...

Страница 2: ...l the configuration options available A combination of key presses are required to use the Installer Setup feature To enter the Installer Setup press and hold the Heat Cool Settings key with both the increase and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 3 and 4 Fig 2 Thermostat key locations...

Страница 3: ...ot have a system key Installer Setup Number 12 will not be displayed Review Table 2 factory settings and mark any desired changes in the Actual Setting column When Installer Setup is complete review the settings to confirm that they match the system Fig 4 Display of Installer Setup number and setting M10238B INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF TABLE 2 FACTORY SETTING OR OTHER CHOICE DISPLAY...

Страница 4: ...upied mode Fan operates with calls for heating or cooling in Unoccupied mode Auxiliary Contact Operation 18 0 0 Time of day contacts 1 1 Economizer contacts Extended fan operation in heating 19 0 No extended fan operation after the call for heat ends 1 Fan operation is extended 90 seconds after the call for heat ends Fan key adjustment models with Fan key only 21 0 Fan setting key is operational 1...

Страница 5: ...s Run Program to exit the Installer Setup Be sure to set the current day and time immediately Setting Current Day and Time 1 Press Set Current Day Time NOTE On initial power up or after an extended power loss 1 00 pm flashes on the LCD until a key is pressed 2 Press Day until the current day is displayed NOTE Sun Sunday Mon Monday Tue Tuesday Wed Wednesday Thu Thursday Fri Friday Sat Saturday M495...

Страница 6: ...art Time Unoccupied Temp Heat Cool Settings Auto System Fan Mon Room AM Occupied 1 Heat Run Program To start the system test CAUTION The minimum off time for compressors is bypassed during the Installer System Test Equipment damage can occur if the compressor is cycled too quickly Press and hold the increase and decrease keys at the same time until 10 appears All segments of the LCD are displayed ...

Страница 7: ... 32 Stage three cool turns off 31 Stage two cool turns off 30 Stage one cool and system fan turn off Fan Equipment System Test Heat Cool Settings 40 Change from cooling to fan equipment system test 41 Fan comes on 40 Fan turns off Key Operation System Test Heat Cool Settings 60 2 Change from fan to key operation system test Unoccupied Temp 60 0 Unoccupied Temp test number is displayed Occupied Tem...

Страница 8: ...nal is connected to the system transformer Check for 24 Vac between X and R or RH terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and...

Страница 9: ...nstaller Setup number 38 Reconfigure minimum off time if required System selection is not set to Heat Set system selection to Heat Cooling will not come on No power to the thermostat Check that X terminal is connected to the system transformer Check for 24 Vac between X and R or RC and Y terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the syst...

Страница 10: ...62 0123 3 10 T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT ...

Страница 11: ...62 0123 3 11 T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT ...

Страница 12: ...T Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 62 0123 3 L C Rev 12 98 Printed in Taiwan R O C Home and Building Control Honeywell 1985 Douglas Drive North Minneapolis MN 55422 4386 www honeywell com yourhome ...

Отзывы: