Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2
45
14 General specification
Sensepoint XCD Transmitter
Use
3-wire, 4-20mA, gas detector transmitter for use with directly installed flammable and toxic gas
sensors. For the protection of personnel and plant from flammable and toxic gas hazards.
Electrical
Input Voltage Range:
Max Power Consumption:
Current output
≥
0.0<1.0 mA
4.0 mA to 20.0 mA
2.0 mA or 4.0 mA (17.4 mA)
22.0 mA
Terminals
Relays
Communication
16 to 32Vdc (24Vdc nominal)
Max 5 Watts. at 24Vdc (see section 2 regarding maximum in
rush current)
4-20mA (Source or Sink)
Fault (refer to table 5 section 12.3 for further details).
Normal gas measurement
Inhibit (during configuration/user settings)
Maximum over range
15 x screw terminals suitable for wire diameter 0.5mm
2
to
2.5mm
2
(20AWG to 13AWG).
3 x 5A@250VAC. Selectable normally open or normally closed
(switch) and energized/de-energized (programmable).
RS485, Modbus RTU (Pending)
Construction
Material
Epoxy painted aluminium alloy or 316 Stainless Steel
Weight
Aluminium alloy: 1.7kg, 316 Stainless Steel: 3.7kg
Mounting
Pole or wall mounting
Entries
2 x M20 (for ATEX/IECEx/AP Approval) or 2x3/4NPT (for UL Approval)
Detectable Gases & Performance (See notes below)
Certification
China
Korea
US
European
International
GB Ex d IIC T4 GB3836.1&2 -2000, PA, (CCCF – Pending)
KTL Ex d IIC T6 (-40ºC to +65ºC)
UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II,
Division, Groups E, F & G, Class II, Division 2, Groups F & G. -40ºC to+65ºC
ATEX Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
IEC Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66
CE
EN50270:2006 EN6100-6-4:2007
Environmental
IP Rating
IP66 in accordance with EN60529:1992
Operating
Temperature
-40ºC to +65ºC/ -40ºF to +149ºF, (IR: -20ºC to +50ºC/ -4ºF to +122ºF).
Note: The detector display may become illegible at temperatures below -40°C, but the detector continues its gas monitoring
function. The display is not damaged and recovers when the temperature rises back above -20 °C.
Operating
Humidity
Continuous 20-90%RH (non condensing), Intermittent 10-99%RH (non condensing)
Operating
Pressure
90-110kPa
Storage
Conditions
-25°C to +65°C (-13°F to +149°F)
43
Min
Max
A1
A2
O xygen
25.0% V/V only
25.0% V/V
n/a
20.9% V/V (Fixed) 20.9% V/V
<30
<+/-0.5% Vol.
-20°C / -4°F
55°C / 131°F
19.5V/V
▼
23.5V/V
▲
H ydrogen Sulfide
10.0 to 100.0ppm
50.0ppm
1.0ppm
25.0ppm
<50
<+/-1ppm
-20°C / -4°F
55°C / 131°F
10.0ppm
▲
20.0ppm
▲
C arbon M onoxide
100 to 1,000ppm
300ppm
100ppm
100ppm
<30
<+/-6ppm
-20°C / -4°F
55°C / 131°F
100ppm
▲
200ppm
▲
H ydrogen
1,000ppm only
1,000ppm
n/a
500ppm
<65
<+/-25ppm
-20°C / -4°F
55°C / 131°F
200ppm
▲
400ppm
▲
Flam m able 1 to 8*
20 to 100% LEL
100% LEL 10% LEL
50% LEL
<25
<+/-1.5% LEL
-20°C / -4°F
55°C / 131°F
20% LEL
▲
40% LEL
▲
M ethane
20 to 100% LEL
100% LEL 10% LEL
50% LEL
<40
<+/-1.5% LEL
-20°C / -4°F
50°C / 122°F
20% LEL
▲
40% LEL
▲
C arbon D ioxide
2.00% Vol only
2.00% V/V
n/a
1.00% V/V
<40
<+/-0.04% Vol.
-20°C / -4°F
50°C / 122°F
0.40% V/V
▲
0.80% V/V
▲
Default Cal
Point
Response
Time (T90)
secs
Accuracy
Gas
User Selectable Full
Scale Range
Default
Range
Steps
Infrared Sensors
30 to 70% of
selected full scale
range
Catalytic Bead Sensors
Operating Temperature*
Default alarm points
Electrochemical Sensors
User Selectable
Cal Gas Range
▲ - Rising Alarm ▼ - Falling Alarm
NOTES
Performance figures are taken at 20~25
℃
;
1. measured using a sample humidity of 50%RH, applicable between 10 and 90% of full scale,
2. measured using test units calibrated at 50% of full scale,
3. measured at 1000cc/min for Methane CAT, 500cc/min for O
2
, Toxic and Methane/Carbon Dioxide IR with calibration cup (S3KCAL).
Response time (T90) may increase when operating in lower temperature conditions or when gas is introduced with the Weather
Protection accessory (SPXCDWP) fitted. Methane IR sensor is calibrated and linearised only for Methane. Should it be exposed to other
HC then non linear response is expected. For linearised operation other than Methane contact HA for alternate parts. Flammable CAT
and Methane IR is calibrated at the factory 50%LEL Methane (2.5%Vol). This calibration enables 100% functional test prior to dispatch.
This calibration does not remove need for calibration & test as part of commissioning at site. For gases other than Methane the unit has
to be calibrated at site using target gas.Data represents typical values, and system conditioning may be required to achieve stated
result. Contact HA for details.
* Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensor except for IR and H2 EC sensors, with an
accuracy of +/- 30% of applied gas from -20°C to -40°C (-4°F to -40°F) and +55°C to +65°C (+131°F to +149°F). Long term operation
at this range may cause decline in sensor performance.
Contact Honeywell Analytics for any additional data or details.
Содержание Sensepoint XCD
Страница 1: ...Technical Manual Sensepoint XCD Gas Detector P R E L A U N C H ...
Страница 54: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 54 17 6 Mounting Bracket Drawing ...
Страница 56: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 56 China GB Ex English Version ...
Страница 57: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 57 China PA Certification ...
Страница 58: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 58 18 2 Korea KTL ...
Страница 59: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 59 18 3 European ATEX ATEX For Transmitter ...
Страница 60: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 60 ATEX for Sensor ...
Страница 61: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 61 18 4 International IEC IEC Ex for Transmitter ...
Страница 62: ...Sensepoint XCD Technical Manual SPXCDHMANEN Issue 2 62 IEC Ex for Sensor ...