Honeywell S8600 Скачать руководство пользователя страница 20

 

 

44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170. 
Website: 

https://www.add-furnace.com/

 โทร: 02-888-3472 

Line ID: @add11 e-mail: [email protected] 

 

EXHIBIT B 

 

PROCEDURE FOR INSTALLING AUTOMATIC INTERMITTENT PILOT SYSTEMS 

 

Prior to beginning this procedure, a preliminary ex- 

amination of the appliance and the automatic intermit- 
tent pilot system should be made to determine that the 
automatic  intermittent  pilot  system  can  be  properly 
applied to the appliance. 

This procedure is intended as a guide to aid in safely 

installing a listed automatic intermittent pilot system on 
an  existing  listed  appliance  equipped  with  an  atmos- 
pheric gas burner(s) and not of the direct vent type. 

This procedure is based on the assumption that the 

history of the specific installation has been one of safe 
and satisfactory operation. 

This procedure is predicated on central furnace and 

boiler  installations,  and  it  should  be  recognized  that 
generalized procedures cannot anticipate all situations. 
Accordingly, in some cases, deviation from this proce- 
dure may be necessary to determine safe operation of 
the equipment. 

The following steps should be followed in making the 

modifications: 

 

1. Perform a safety inspection of the existing appli- 

ance  installation.  See  Exhibit  A  for  a  recommended 
procedure for such a safety inspection. 

 

2. Shut off all gas and electricity to the appliance. To 

shut off gas, use the shutoff valve in the supply line to the 
appliance. Do not use the shutoff valve which is  pro- 
vided as part of a combination control. 

 

3.  Install  the automatic intermittent pilot system  in 

strict  accordance  with  the  manufacturer’s  installation 
instructions. 

 

4. Turn on all gas and electricity to the appliance. 

 

5.  Determine  that  the  appliance  transformer  has 

adequate capacity by following the steps outlined be- 
low: 

a.  Compute the approximate current draw by adding 
the current draw of the automatic intermittent  pilot 
system  to  (1)  the  current  draw  of  the  associated 
valving,  and  (2)  the  current  draw  of  any  relays  or 
other devices operated by the transformer. 
b.  Multiply the total current draw as computed above 
by  24  V  to  determine  the  total  VA  (volt-ampere) 
required. 
c.  The  total  VA  (volt-ampere)  required  should  be 
equal to or less than the VA rating of the transformer. 
d.  If the total VA (volt-ampere) required is  greater 
than the VA rating of the transformer, the transformer 
must  be  replaced  with  a  Class  2  transformer  of 
adequate rating. 

 

6. Check the heat anticipator in the comfort thermo- 

stat to determine if it is properly adjusted to the current 
draw  of  the  control  system.  Follow  the  thermostat 
manufacturer’s instructions. 

 

7.  Make  certain  wiring  connections  are  tight  and 

wires are positioned and secured so they will not be able 
to contact high temperature locations. 

 

8.  Conduct  a  Gas  Leakage  Test  of  the  appliance 

piping  and  control  system  downstream  of  the  shutoff 
valve in the supply line to the appliance. 

 

9.  a. Adjust the thermostat to its highest tempera- 

ture setting, and test manifold pressure and adjust 
the pressure regulator to match original input as 
required (refer to Exhibit A, step 9b). 
b. Visually determine that main burner is burning 
properly; i.e., no floating, lifting or flashback. Ad- 
just the primary air shutter(s) as required. 

 

10.  If  the  appliance  is  equipped  with  high  and  low 

flame control or flame modulation, check for proper main 
burner operation at both high and low flame. 

 

11.  Determine  that  the  pilot  is  igniting  and  burning 

properly and that main burner ignition is satisfactory by 
interrupting and re-establishing the electrical supply to 
the  appliance  in  any  convenient  manner.  Make  this 
determination with the appliance burner both cold and 
hot. Perform this step as many times as is necessary to 
satisfy yourself that the automatic intermittent pilot sys- 
tem is operating properly. 

 

12.  Test the pilot safety device (1) to determine if it is 

operating properly, and (2) for turndown characteristics 
according to the 

manufacturer’s installation instructions. 

No adjustments should be made other than those rec- 
ommended by the system manufacturer. 

 

13.  Sequence  the  appliance  through  at  least  three 

operating cycles. 

 

14.  Applicable only to furnaces. Check both the limit 

controller  and  the  fan  controller  for  proper  operation. 
Limit control operation can be checked by blocking the 
circulating  air  inlet  or  temporarily  disconnecting  the 
electrical supply to the blower motor and determining 
that the limit controller acts to shut off the main burner 
gas. 

 

15.  Applicable only to boilers. 

a.  Determine that the circulating water pumps are 
in operating condition. 
b.  Test low water cutoffs, automatic feed water 
controls, pressure and temperature limit control- 
lers  and  relief  valves  in  accordance  with  the 
manufacturer’s  recommendation  to  determine 
they are in operating condition. 

 

16.  Add the labels (see 1.6.1-n and -o) on the appli- 

ance. 

 

EXHIBIT B OF ANSI STANDARD Z21.71 FOR AUTOMATIC INTERMITTENT PILOT IGNITION SYSTEMS FOR FIELD 
INSTALLATION. 

Содержание S8600

Страница 1: ...ANING Once a module or gas control has been wet it may operate unreliably and must be replaced If the appliance is likely to be cleaned with water or steam the controls and associated wiring should be covered so water orsteam flow cannot reach them The controls should be high enough above the bottom of the cabinet so they will not be subject tofloodingorsplashingduringnormalcleaningprocedures If n...

Страница 2: ...on Some considerations are Cyclingfrequency Appliances that may cycle more than 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again be fore the next use PERFORM PREINSTALLATION SAFETY INSPECTION The preinstallation checks described in ANSI Standard Z21 71 on page 19 must be done before the replacement modu...

Страница 3: ... end to vent damper To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 7 for typical connec tions Connect Ignition Module 1 Connectremainingsystemcomponentstotheignition module terminals as shown in the appropriate wiring dia gram Figs 1 to 10 Fig 1 is a basic circuit for a heating only atmos pheric burner with S8600F H M S8610F H S8660D or S8670D Fig 2 shows ...

Страница 4: ... Strip the other end of the wire and fasten it under the igniter bracket mounting screw If necessary use a shield to protect the ground wire from radiant heat 3 The burner serves as the common grounding area If thereisnotgoodmetal to metalcontactbetweentheburner and ground run a lead from the burner to ground NOTE Earth ground is not required REPLACING MODULE WITH TH R TH W TERMINALS On modules th...

Страница 5: ... CONTROL 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THERMO STAT 1ST 2ND OPERATOR OPERATOR MAIN VALVE PILOT COM 3 197516A WIRING HARNESS SPARK DAMPER PLUG 5 VENT 24V GND 24V TH W S8600F H M S8610F H GND MV MV PV PV BURNER PILOT GAS SUPPLY LIMIT CONTROLLER GROUND IGNITER 1 L2 L1 HOT 4 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND L...

Страница 6: ...SE SPARK 5 VENT DAMPER PLUG 24V GND 24V TH W S8600A B S8610A B GND MV MV PV PV BURNER M1177C L2 L1 HOT 1 PILOT GAS SUPPLY COMBUSTION 1 AIR BLOWER MOTOR GROUND 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT THERMOSTAT TO TH W LEAVE 24V OPEN DO NOT REMOVE VENT DAMPER PLUG PILOT BURNER Q345 Q346 Q348 Q362 Q381 PILOT BURNER IGNITER SENSOR LIMIT CONTROLLER L2 L1 HOT 2 ALTERNATE LIMIT CONT...

Страница 7: ...L COMBUSTION AIR BLOWER RELAY 4 Q381PILOT BURNER IGNITER SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CONTROLLER 1 L1 L2 L1 L2 HOT 1 COMBUSTION AIR BLOWER MOTOR HOT M1178C 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MOD...

Страница 8: ...UND PILOT GAS SUPPLY 4 1K3 1 2 3 4 5 6 L2 L1 HOT 1 TRANSFORMER LIMIT 2 CONTROLLER THERMOSTAT OR CONTROLLER LIMIT CONTROLLER 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT T...

Страница 9: ...R SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CON TROLLER FAN CENTER 4 R C W G Y MOTOR COMBUSTION AIR BLOWER RELAY COIL FAN MOTOR FAN CONTROL C H 2 AIR PROVING SWITCH 1 POWER SUPPLY PROVIDE DISCONNECTMEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER 5 FOR MODULE ...

Страница 10: ...OR PILOT BURNER GROUND PILOT GAS SUPPLY CABLE 2 L1 HOT 1 BLUE YELLOW G L1 5 BLACK TP 1K ORANGE B R L8148J 1K1 1K3 Z W T TV 1K2 AUTO MANUAL SWITCH C1 FAN MOTOR L2 L2 B3 B2 B1 C2 M1181C THERMOSTAT 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 CUT PLUG OFF MODULE END OF D80D WIRE HARNESS CONNECT LEADWIRE COLORS AS SHOWN 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 FOR MODULE WI...

Страница 11: ...y Turn gas supply off Set thermostat or controller above room temperature to call for heat Watch for spark at pilot burner either immediately or following prepurge See device label Time spark from start to shutoff See device label On S8600M wait 6 min nom Ignition sequence should start again followed by shutoff after 90 sec max Open manual gas cock and make sure no gas is flowing to pilot or main ...

Страница 12: ...ustion air blower starts on a call for heat On proof of airflow the air proving switch closes and energizes the S8660 S8670 When the module is used in an atmospheric system the call for heat energizes the module In either case the module first initiates a 45 sec delay to allow system prepurge After prepurge the module starts the pilot ignition sequence START STAGE 1 TRIAL FOR IGNIITION 3 Pilot bur...

Страница 13: ...yretry for ignition Operation on ignition failure is the same as lockout modules except that a timer starts timing imme diately following shutoff Six minutes nom five minutes min after shutoff the module restarts the ignition se quence The ignition trial shutoff wait sequence continues until either the pilot lights or the thermostat is set below room temperature to end the call for heat The module...

Страница 14: ...exposure to extreme heat which can permit leakage to ground Replace pilot burner igniter sensor and provide shield ifnecessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire made from ignition cable or other heavily insulated wire Close the manual gas valve Disconnect the ignition cable at the SPARK...

Страница 15: ...stem SPARK STOPS WHEN PILOT IS LIT Check continuity of ignition cable and ground wire Clean flame rod Check electrical connections between flame rod and module Check for cracked ceramic flame rod insulator Check that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace module Spark okay Pull ignition lead and check spark at module TURN GAS SUPPLY OFF T...

Страница 16: ...16 44 ซ บรมราชชนนี 70 ถ บรมราชชนนี ศาลาธรรมสพน ทวีวัฒนา กทม 10170 Website https www add furnace com โทร 02 888 3472 Line ID add11 e mail add028883472 gmail com Fig 15 S8660 S8670 troubleshooting guide ...

Страница 17: ...CIRCUITS SPARK IGNITER SENSOR GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND MV WIRED AS FOLLOWS TO 24V TO 24V GND MAIN INTERNAL WIRING 1K1 2K2 1K2 VALVE MV PILOT VALVE PV MV PV EX...

Страница 18: ...E DETECTOR CIRCUIT RELAY DRIVERS HYBRID CIRCUIT TIMING CIRCUITS SPARK IGNITER GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND 3 MV WIRED AS FOLLOWS TO 24V MAIN TO 24V GND INTERNAL W...

Страница 19: ...all building doors and windows and all doors between the space in which the appliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers If after complet ing steps 7 through 12 it is believed sufficient combus tion air ...

Страница 20: ...laced with a Class 2 transformer of adequate rating 6 Check the heat anticipator in the comfort thermo stat to determine if it is properly adjusted to the current draw of the control system Follow the thermostat manufacturer s instructions 7 Make certain wiring connections are tight and wires are positioned and secured so they will not be able to contact high temperature locations 8 Conduct a Gas ...

Отзывы: