•  Make sure electrical connections are clean and tight. 

Replace damaged wire with moisture-resistant No. 
18 wire rated for continuous duty up to 105

 

C [221

 

F]. 

•  Check for cracked ceramic insulator, which can cause 

short to ground, and replace igniter-sensor if neces- 
sary. 

•  At the gas control, disconnect main valve wire from 

the TH or MV terminal. 

•  Turn on power and set thermostat to call for heat. The 

pilot should light but the main burner will remain off 
because the main valve actuator is disconnected. 

•  Check the pilot flame. Make sure it is blue, steady and 

envelops 3/8 to 1/2 in. [10 to 13 mm] of the flame rod. 
See  Fig.  13  for  possible  flame  problems  and  their 
causes. 

•  If necessary, adjust pilot flame by turning the pilot 

adjustment 

screw 

on 

the 

gas 

control 

clockwise 

to 

 

decrease 

or 

counterclockwise  

to increase pilot flame. Fol- 

lowing adjustment, always replace pilot adjustment 
cover screw and tighten firmly to assure proper gas 
control operation. 

•  Set thermostat below room temperature to end call 

for heat. 

 

Recheck ignition sequence as follows. 
•  Reconnect main valve wire. 
•  Set thermostat to call for heat. 
•  Watch ignition sequence at burner. 
•  If spark still doesn’t stop after pilot lights, replace 

ignition module. 

•  If main burner doesn’t light or if main burner lights but 

system locks out, check module, ground wire and gas 
control as described in appropriate troubleshooting 
chart, Fig. 14 or 15. 

 

START

 

 

 

NO

 

 

YES

 

 

NO

 

 

NO

 

 
 

YES

 

 

 
 

YES

 

 
 

 

NO

 

 
 

 

NO

 

 

YES

 

 
 
 

 

 

NO

 

 

YES

 

 

 

NO

 

 

YES

 

 

 

NO

 

 

 

YES

 

 

 

 

 

POWER TO MODULE? 

(24V NOMINAL)

 

NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min. 
nom. for retry or reset system.

 

CALL FOR HEAT ENDS

 

SYSTEM SHUTS OFF?

 

SYSTEM RUNS UNTIL 

CALL FOR HEAT ENDS?

 

Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at 
the time of checkout.

 

Check that pilot flame covers flame rod and is steady and blue. 
If checks are okay, replace module.

 

NOTE: If S86XXB,H,D,J goes into lockout, reset system. For S86XXC,M,U,J,K, wait 6 min. 
nom. for retry or reset system.

 

SPARK STOPS WHEN 

PILOT IS LIT?

 

Check continuity of ignition cable and ground wire. 
Clean flame rod.

 

Check electrical connections between flame rod and module. 
Check for cracked ceramic flame rod insulator.

 

Check that pilot flame covers flame rod and is steady and blue. 
Adjust pilot flame.

 

If problem persists, replace module.

 

Spark okay?

 

 

Pull ignition lead and 
check spark at module.

 

TURN GAS SUPPLY OFF. 

TURN THERMOSTAT 

(CONTROLLER) TO CALL 

FOR HEAT

 

 

Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring. Also, 
check air proving switch on combustion air blower system (if used) and that vent damper (if used) is open and 
end switch is made.

 

Before troubleshooting, familiarize yourself with the startup and checkout procedure.

 

NOTE: Models with TH-W terminal (7) must have call for heat 24 Vac supply connected to the TH-W terminal. 

Models with no TH-W terminal must have call for heat 24 Vac supply connected to 24V terminal (6).

 

TROUBLESHOOTING 

ENDS

 

Check for proper thermostat (controller) operation.

 

Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas 
control.

 

MAIN BURNER LIGHTS?

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

 

Check electrical connections between module and gas control. If okay, replace gas control or gas control 
operator.

 

Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice 
is not blocked.

 

Check electrical connections between module and pilot operator on gas control.

 

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, 

replace module.

 

NOTE: It may be necessary to recycle the call for heat to clear the pilot supply tubes of air.

 

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

 

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and 
boot from excessive temperatures.

 

 

SPARK ACROSS 
IGNITER/SENSOR GAP? 
(S8660, S8670, S8680

 

HAVE 45 SECOND [NOMINAL] 
PREPURGE BEFORE SPARK 
STARTS.)

 

On models with vent damper plug, make sure vent damper 
has not been installed, then removed. Replace vent damper 
if necessary.

 

On other models, replace module.

 

TURN GAS SUPPLY ON 
AND RECYCLE CALL 
FOR HEAT

 

PILOT BURNER LIGHTS?

 

 

YES

 

 

 

Repeat procedure until troublefree operation is obtained.

 

 

Fig. 14

—S8600, S8610 troubleshooting guide. 

 

Содержание S8600

Страница 1: ...ANING Once a module or gas control has been wet it may operate unreliably and must be replaced If the appliance is likely to be cleaned with water or steam the controls and associated wiring should be covered so water orsteam flow cannot reach them The controls should be high enough above the bottom of the cabinet so they will not be subject tofloodingorsplashingduringnormalcleaningprocedures If n...

Страница 2: ...on Some considerations are Cyclingfrequency Appliances that may cycle more than 20 000 times annually should be checked monthly Intermittent use Appliances that are used seasonally should be checked before shutdown and again be fore the next use PERFORM PREINSTALLATION SAFETY INSPECTION The preinstallation checks described in ANSI Standard Z21 71 on page 19 must be done before the replacement modu...

Страница 3: ... end to vent damper To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 7 for typical connec tions Connect Ignition Module 1 Connectremainingsystemcomponentstotheignition module terminals as shown in the appropriate wiring dia gram Figs 1 to 10 Fig 1 is a basic circuit for a heating only atmos pheric burner with S8600F H M S8610F H S8660D or S8670D Fig 2 shows ...

Страница 4: ... Strip the other end of the wire and fasten it under the igniter bracket mounting screw If necessary use a shield to protect the ground wire from radiant heat 3 The burner serves as the common grounding area If thereisnotgoodmetal to metalcontactbetweentheburner and ground run a lead from the burner to ground NOTE Earth ground is not required REPLACING MODULE WITH TH R TH W TERMINALS On modules th...

Страница 5: ... CONTROL 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED THERMO STAT 1ST 2ND OPERATOR OPERATOR MAIN VALVE PILOT COM 3 197516A WIRING HARNESS SPARK DAMPER PLUG 5 VENT 24V GND 24V TH W S8600F H M S8610F H GND MV MV PV PV BURNER PILOT GAS SUPPLY LIMIT CONTROLLER GROUND IGNITER 1 L2 L1 HOT 4 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND L...

Страница 6: ...SE SPARK 5 VENT DAMPER PLUG 24V GND 24V TH W S8600A B S8610A B GND MV MV PV PV BURNER M1177C L2 L1 HOT 1 PILOT GAS SUPPLY COMBUSTION 1 AIR BLOWER MOTOR GROUND 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT THERMOSTAT TO TH W LEAVE 24V OPEN DO NOT REMOVE VENT DAMPER PLUG PILOT BURNER Q345 Q346 Q348 Q362 Q381 PILOT BURNER IGNITER SENSOR LIMIT CONTROLLER L2 L1 HOT 2 ALTERNATE LIMIT CONT...

Страница 7: ...L COMBUSTION AIR BLOWER RELAY 4 Q381PILOT BURNER IGNITER SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CONTROLLER 1 L1 L2 L1 L2 HOT 1 COMBUSTION AIR BLOWER MOTOR HOT M1178C 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MOD...

Страница 8: ...UND PILOT GAS SUPPLY 4 1K3 1 2 3 4 5 6 L2 L1 HOT 1 TRANSFORMER LIMIT 2 CONTROLLER THERMOSTAT OR CONTROLLER LIMIT CONTROLLER 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TOTRANSFORMER 5 FOR MODULE WITH TH W TERMINAL AND VENT DAMPER PLUG CONNECT T...

Страница 9: ...R SENSOR PILOT BURNER GROUND PILOT GAS SUPPLY LIMIT CON TROLLER FAN CENTER 4 R C W G Y MOTOR COMBUSTION AIR BLOWER RELAY COIL FAN MOTOR FAN CONTROL C H 2 AIR PROVING SWITCH 1 POWER SUPPLY PROVIDE DISCONNECTMEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER 5 FOR MODULE ...

Страница 10: ...OR PILOT BURNER GROUND PILOT GAS SUPPLY CABLE 2 L1 HOT 1 BLUE YELLOW G L1 5 BLACK TP 1K ORANGE B R L8148J 1K1 1K3 Z W T TV 1K2 AUTO MANUAL SWITCH C1 FAN MOTOR L2 L2 B3 B2 B1 C2 M1181C THERMOSTAT 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 CUT PLUG OFF MODULE END OF D80D WIRE HARNESS CONNECT LEADWIRE COLORS AS SHOWN 3 MAXIMUM CABLE LENGTH 3 ft 0 9 m 4 FOR MODULE WI...

Страница 11: ...y Turn gas supply off Set thermostat or controller above room temperature to call for heat Watch for spark at pilot burner either immediately or following prepurge See device label Time spark from start to shutoff See device label On S8600M wait 6 min nom Ignition sequence should start again followed by shutoff after 90 sec max Open manual gas cock and make sure no gas is flowing to pilot or main ...

Страница 12: ...ustion air blower starts on a call for heat On proof of airflow the air proving switch closes and energizes the S8660 S8670 When the module is used in an atmospheric system the call for heat energizes the module In either case the module first initiates a 45 sec delay to allow system prepurge After prepurge the module starts the pilot ignition sequence START STAGE 1 TRIAL FOR IGNIITION 3 Pilot bur...

Страница 13: ...yretry for ignition Operation on ignition failure is the same as lockout modules except that a timer starts timing imme diately following shutoff Six minutes nom five minutes min after shutoff the module restarts the ignition se quence The ignition trial shutoff wait sequence continues until either the pilot lights or the thermostat is set below room temperature to end the call for heat The module...

Страница 14: ...exposure to extreme heat which can permit leakage to ground Replace pilot burner igniter sensor and provide shield ifnecessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire made from ignition cable or other heavily insulated wire Close the manual gas valve Disconnect the ignition cable at the SPARK...

Страница 15: ...stem SPARK STOPS WHEN PILOT IS LIT Check continuity of ignition cable and ground wire Clean flame rod Check electrical connections between flame rod and module Check for cracked ceramic flame rod insulator Check that pilot flame covers flame rod and is steady and blue Adjust pilot flame If problem persists replace module Spark okay Pull ignition lead and check spark at module TURN GAS SUPPLY OFF T...

Страница 16: ...16 44 ซ บรมราชชนนี 70 ถ บรมราชชนนี ศาลาธรรมสพน ทวีวัฒนา กทม 10170 Website https www add furnace com โทร 02 888 3472 Line ID add11 e mail add028883472 gmail com Fig 15 S8660 S8670 troubleshooting guide ...

Страница 17: ...CIRCUITS SPARK IGNITER SENSOR GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND MV WIRED AS FOLLOWS TO 24V TO 24V GND MAIN INTERNAL WIRING 1K1 2K2 1K2 VALVE MV PILOT VALVE PV MV PV EX...

Страница 18: ...E DETECTOR CIRCUIT RELAY DRIVERS HYBRID CIRCUIT TIMING CIRCUITS SPARK IGNITER GND BUR NER BURNER GROUND MAIN 1K1 1K2 3K2 VALVE MV PILOT MV PV 2K 3K1 VALVE PV 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 2 ALTERNATE LIMIT CONTROLLER LOCATION 3K RELAY ON 100 PERCENT SHUTOFF MODELS ONLY ON NON SHUTOFF MODELS PV AND 3 MV WIRED AS FOLLOWS TO 24V MAIN TO 24V GND INTERNAL W...

Страница 19: ...all building doors and windows and all doors between the space in which the appliance is located and other spaces of the building Turn on clothes dryers Turn on any exhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers If after complet ing steps 7 through 12 it is believed sufficient combus tion air ...

Страница 20: ...laced with a Class 2 transformer of adequate rating 6 Check the heat anticipator in the comfort thermo stat to determine if it is properly adjusted to the current draw of the control system Follow the thermostat manufacturer s instructions 7 Make certain wiring connections are tight and wires are positioned and secured so they will not be able to contact high temperature locations 8 Conduct a Gas ...

Отзывы: