background image

ELSTER RABO

®

 Rotary Gas Meter

06    Honeywell

Figure 5. Horizontal installation

Figure 6. Vertical installation

Figure 7. Sight glass

Figure 4. Side view

b) Mounting

1)

Always  follow  your  company’s  procedures,  and 
applicable local codes and ordinances.

2)

Ensure gas valves are closed.

3)

Ensure  the  upstream  piping  is  clean  and  free  of  any 
debris.

4)

Remove protective caps from meter inlet and outlet prior 
to installation.

5)

Ensure the impellers turn freely.

6)

Ensure  the  direction  of  flow  using  the  arrow  on  the 
nameplate.

7)

Ensure  the  meter  orientation  is  correct.  Impeller  shafts 
must be horizontal [Figure 4].

8)

Connect  the  inlet  and  outlet  pipe  flanges  using 
appropriate  bolts  and  gaskets.  Inlet  and  outlet  pipe 
flanges should be parallel and should not introduce any 
bind on the meter body when tightened.

9)

Level meter to within 1/16" per foot in all directions and 
tighten flange bolts evenly (maximum 80ft-lbs). 

c) Adding Oil

!

WARNING

Add oil only to the index end of the meter.

1)

Ensure gas valves are closed and meter and piping are 
depressurized.

!

WARNING

Failure  to  depressurize  the  meter  prior  to  removing 

meter  and/or  components  could  result  in  personal 

injury and/or property damage.

2)

Remove oil fill plug in the counter end case cover using a 
5mm hex key [Figures 5 and 6].

3)

Using the supplied syringe and oil, slowly add oil until 
it is +/-1/16" of the center of the sight glass [Figure 7]. 

DO NOT OVERFILL.

 Only use Shell Morlina lubricating oil.

!

WARNING

DO NOT remove any sight glasses. No maintenance 

can be performed through these openings.

4)

Reinstall the oil fill plug.

OIL

FILL

OIL

LEVEL

SIGHT

GLASS

OIL

DRAIN

OIL

FILL

OIL

FILL

OIL

FILL

OIL

LEVEL

SIGHT

GLASS

OIL

DRAIN

RABO

®

 Rotary Gas Meter

04 Elster Instromet

RABO

®

 Rotary Gas Meter

05 Elster Instromet

7. Decommissioning and Removal

a) Always follow your company’s procedures, and local codes 

and ordinances.

b) Slowly open bypass valve.
c)

Slowly close the meter’s outlet valve, then the inlet valve.

d) Slowly, completely depressurize the meter piping.

!

WARNING

Failure to depressurize the meter prior to removing meter 

and/or components could result in personal injury and/or 

property damage.

e)

Drain oil from the index end case cover and dispose of the oil 
in accordance with applicable regulations.

f)

If removing the meter from the piping system, loosen flange 
bolts.  Ensure  meter  is  properly  supported  before  removing 
bolts completely.

8. Inspection and Maintenance

It  is  recommended  to  inspect  Elster  RABO  meters  periodically  to 
help  ensure  accurate  performance  over  a  long  period  of  time. 
Maintenance intervals can be derived from inspection criteria. 
Routine inspections should include:
a) Checking to ensure the meter is level in all planes
b) Listening for abnormal sounds in the meter
c)

Checking oil level and clarity — oil should be red and clear

d) Checking index movement if gas is flowing
e)

Checking for leaks

f)

Testing the meter’s differential pressure

Routine maintenance should include:
a) Changing the oil if the color becomes dark
b) Adding  oil  if  the  color  is  red  and  clear,  but  below  the 

recommended level

9. Testing

Elster RABO meters should be tested in accordance with applicable 
governing  standards.  The  accuracy  of  a  meter  can  only  be 
determined by comparing results to a traceable reference, typically 
a  sonic  nozzle,  bell,  piston  or  transfer  prover.  Accuracy  may  be 
done on site using transfer provers, and typically requires removal 
for testing with other technologies. 
Differential pressure testing is a method of determining whether 
the performance of a rotary meter may have changed over time, 
and  can  be  done  on  site  while  the  meter  is  operating  under 
pressure. Baseline data must be captured during initial start-up  to 
which future data can be compared.

a) Proving

When  testing  a  meter  on  a  prover,  the  meter  temperature, 
pressure  and  volume  are  necessary  inputs  for  the  proving 
device. The meter temperature is obtained by a temperature 
probe  installed  near  the  inlet  of  the  meter.  A  thermowell 
can  be  installed  in  the  meter  run  piping  or  on  the  meter 
itself  to  facilitate  installation  of  the  temperature  probe. 
The meter pressure should come from the meter differential 
pressure taps. 

Figure 8. Back of meter

6. Start-up/Commissioning

After the meter has been properly installed, it is important to use 
extreme care during start-up to mitigate adverse conditions that 
can damage the meter. 
a) Ensure  that  the  maximum  operating  pressure  of  the  meter 

will not be exceeded.

b) Always follow your company’s procedures, and local codes 

and ordinances.

c)

With the meter run’s inlet and outlet valves closed, open the 
bypass valve and pressurize the piping system.

d) With  the  meter  outlet  valve  closed,  slowly  open  the  meter 

inlet  valve  not  to  exceed  5  psig  per  second  until  pressure 
is  equalized  throughout  the  meter  piping  system.  Rapid 
pressurization  can  cause  an  over-speed  condition  and 
can  damage  the  meter.  Damage  will  not  be  covered 
under warranty. When the meter piping system pressure is 
stabilized, open the inlet valve completely.

e)

Slowly open the meter’s outlet valve until the meter starts to 
operate at low speed. Meter speed can be seen through the 
view port located on the back of the meter [Figure 8]. 

f)

Operate  the  meter  at  low  flow  for  1  to  2  minutes  to  verify 
proper operation. If the index does not start registration, or 
if  you  hear  knocking  or  scraping  sounds  coming  from  the 
meter, stop the flow and follow appropriate decommissioning 
procedures before removing the meter from the line.

g) If operation is satisfactory, gradually open the meter’s outlet 

valve to the full open position.

h)

Slowly close the bypass valve.

i)

Check  the  meter  connections  for  leaks  using  common 
industry practices.

j)

Clock the meter (see Index section 11c) to confirm the flow rate 
is not exceeding the maximum capacity of the meter.

k)

Perform  and  record  the  meter’s  differential  pressure  (see 
Testing section 9b).

VIEW PORT

���������������

Figure 8. Back of meter

6. Start-up/Commissioning

7. Decommissioning and Removal

After the meter has been properly installed, it is important to use 
extreme  care  during  start-up  to  mitigate  adverse  conditions  that 
can damage the meter.
a)   Ensure  that  the  maximum  operating  pressure  of  the  meter 
 

will not be exceeded.

b)   Always follow your company’s procedures, and local codes 
 

and ordinances.

c)   With the meter run’s inlet and outlet valves closed, open the  
 

bypass valve and pressurize the piping system.

d)   With  the  meter  outlet  valve  closed,  slowly  open  the  meter  
 

inlet  valve  not  to  exceed  5  psig  per  second  until  pressure  

 

is  equalized  throughout  the  meter  piping  system.  Rapid  

 

pressurization  can  cause  an  over-speed  condition  and  

 

can  damage  the  meter.  Damage  will  not  be  covered  

 

under warranty. When the meter piping system pressure is  

 

stabilized, open the inlet valve completely.

e)   Slowly open the meter’s outlet valve until the meter starts to  
 

operate at low speed. Meter speed can be seen through the  

 

view port located on the back of the meter [Figure 8]. 

f)   Operate  the  meter  at  low  flow  for  1  to  2  minutes  to  verify  
 

proper operation. If the index does not start registration, or  

 

if  you  hear  knocking  or  scraping  sounds  coming  from  the  

 

meter, stop the flow and follow appropriate decommissioning  

 

procedures before removing the meter from the line.

g)   If operation is satisfactory, gradually open the meter’s outlet  
 

valve to the full open position.

h)   Slowly close the bypass valve.
i)   Check  the  meter  connections  for  leaks  using  common 
 

industry practices.

j)   Clock the meter (see Index section 11c) to confirm the flow rate 
 

 is not exceeding the maximum capacity of the meter.

k)   Perform  and  record  the  meter’s  differential  pressure  (see  
 

Testing section 9b).

8. Inspection and Maintenance

9. Testing

e)   Drain oil from the index end case cover and dispose of the oil 
 

in accordance with applicable regulations.

f)   If removing the meter from the piping system, loosen flange 
 

bolts.  Ensure  meter  is  properly  supported  before  removing 

 

bolts completely.

a)   Always follow your company’s procedures, and local codes 
 

and ordinances.

b)   Slowly open bypass valve.
c)   Slowly close the meter’s outlet valve, then the inlet valve.
d)   Slowly, completely depressurize the meter piping. 

Failure to depressurize the meter prior to removing meter 

and/or components could result in personal injury and/or 

property damage.

It  is  recommended  to  inspect  Elster  RABO  meters  periodically  to 
help  ensure  accurate  performance  over  a  long  period  of  time.  
Maintenance intervals can be derived from inspection criteria. 

Routine inspections should include:

a)   Checking to ensure the meter is level in all planes
b)   Listening for abnormal sounds in the meter
c)   Checking oil level and clarity — oil should be red and clear
d)   Checking index movement if gas is flowing
e)   Checking for leaks
f)   Testing the meter’s differential pressure

Routine maintenance should include:
a)   Changing the oil if the color becomes dark
b)   Adding  oil  if  the  color  is  red  and  clear,  but  below  the  
 

recommended level

Elster RABO meters should be tested in accordance with applicable  
governing  standards.  The  accuracy  of  a  meter  can  only  be  
determined by comparing results to a traceable reference, typically  
a  sonic  nozzle,  bell,  piston  or  transfer  prover.  Accuracy  may  be 
done on site using transfer provers, and typically requires removal  
for testing with other technologies. 
Differential pressure testing is a method of determining whether  
the performance of a rotary meter may have changed over time,  
and  can  be  done  on  site  while  the  meter  is  operating  under  
pressure. Baseline data must be captured during initial start-up to  
which future data can be compared.

a)   Proving 

 

When  testing  a  meter  on  a  prover,  the  meter  temperature,  

 

pressure  and  volume  are  necessary  inputs  for  the  proving  

 

device. The meter temperature is obtained by a temperature  

 

probe  installed  near  the  inlet  of  the  meter.  A  thermowell

 

can  be  installed  in  the  meter  run  piping  or  on  the  meter

 

itself  to  facilitate  installation  of  the  temperature  probe.

 

The meter pressure should come from the meter differential

 

pressure taps.

Содержание RABO

Страница 1: ...Instromet RABO Rotary Gas Meter Instruction Manual ...

Страница 2: ......

Страница 3: ...15 Troubleshooting 11 RABO Rotary Gas Meter RABO Rotary Gas Meter 02 Elster Instromet RABO Rotary Gas Meter 1 General Information 3 2 Intended Use and Application 3 3 Operating Principle 3 4 Receiving Handling and Storage 4 5 Installation 4 6 Start up Commissioning 6 7 Decommissioning and Removal 6 8 Inspection and Maintenance 6 9 Testing 6 10 Technical Data 8 11 Index 9 12 Pulser 11 13 Thermowell...

Страница 4: ... transit you should notify the shipper immediately file a claim with the carrier and notify your Elster supplier Damage to internal components may occur without visible external damage All new meters should be inspected and checked for free rotation of the impellers by lightly blowing into the inlet of the meter This slight air pressure should cause the impellers to rotate freely and come to a stop...

Страница 5: ...ex end of the meter 1 Ensure gas valves are closed and meter and piping are depressurized WARNING Failure to depressurize the meter prior to removing meter and or components could result in personal injury and or property damage 2 Remove oil fill plug in the counter end case cover using a 5mm hex key Figures 5 and 6 3 Using the supplied syringe and oil slowly add oil until it is 1 16 of the center ...

Страница 6: ...or 1 to 2 minutes to verify proper operation If the index does not start registration or if you hear knocking or scraping sounds coming from the meter stop the flow and follow appropriate decommissioning procedures before removing the meter from the line g If operation is satisfactory gradually open the meter s outlet valve to the full open position h Slowly close the bypass valve i Check the meter...

Страница 7: ... never left in a plug for a period of hours or days Severe deformation of the valves may occur if the probe is left in the plug for a long period of time b Differential Pressure Testing Typically when proving a meter both the meter pressure and meter differential pressure are used and recorded The RABO meter differential pressure ports are not full bore and most temperature probes will not fit thr...

Страница 8: ...0 40 50 60 75 100 150 175 250 290 0 0 0 1 0 3 0 7 1 4 2 1 2 8 3 4 4 1 5 2 6 9 10 3 12 1 17 2 20 0 100 110 130 160 230 300 370 430 500 600 770 1 110 1 270 1 780 2 050 3 500 3 900 4 600 5 800 8 200 10 500 12 900 15 300 17 700 21 200 27 200 39 100 45 000 62 800 72 300 5 500 6 100 7 200 9 100 12 800 16 600 20 300 24 000 27 800 33 400 42 700 61 400 70 700 98 700 113 700 160 170 200 260 360 470 570 680 ...

Страница 9: ... factor shown on the index face plate In the example on the next page the reading would be 1357900 cubic feet Figure 10 RABO Rotary Gas Meter 08 Elster Instromet c Dimensions and Weights b How to Read 11 Index ANSI Class 125 150 flat face flange connection A B C D E F G Nom Pipe Size Bolt Size H Bolts Flange Bolt Circle J Shipping Weight Carton Size in mm in mm in mm in mm in mm in mm in mm in mm ...

Страница 10: ...e change gear from the damaged index to the replacement Figures 14 and 15 Remove the change gear on the damaged index Pry the locking collar off with a knife blade or other sharp object Unscrew the change gear WARNING Each meter size uses a common index that has unique colored gears Interchanging colored gears will result in inaccurate readings Ensure the replacement index has the same color gears...

Страница 11: ... index cover 11 Install security seals LOCKING COLLAR CHANGE GEAR INDEX Meter Gear Color 3 5M G65 White 5 5M G100 Dark Green 9M G160 Green 14M G250 Red Table 1 LOCKING COLLAR CHANGE GEAR SUPPORT HOLE SUPPORT HOLE Figure 14 Change gear removal 12 Pulser All RABO meter indexes can be easily outfitted with a pulse output device to interface with auxiliary equipment Installation of a pulser is quick an...

Страница 12: ... Screw the thermowell into the meter and tighten to 18 ft lbs 8 Re pressurize the meter as instructed in Start up Commissioning see section 6 Figure 21 Auxilary equipment mounted ACCESSORY Figure 18 Auxiliary ports 13 Thermowell All RABO meters come equipped with two 2 NPT auxiliary ports on the meter body Figure 18 which can be used for sensing pressure and temperature of the flowing gas A thermo...

Страница 13: ...he posts in the index base plate 2 Ensure the shaft on the magnet holder aligns with the support hole on the index frame Figure 24 Figure 24 ID retaining screws INDEX RETAINING SCREW SUPPORT HOLE ON BACK SIDE INDEX RETAINING SCREW INDEX RETAINING SCREW 3 Tighten the three screws until snug Do not overtighten a Each screw should have a 2mm thick retaining washer to space the ID gearing and index as...

Страница 14: ...ent should be pipe or wall mounted adjacent to the meter Elster provides customized brackets for commonly used equipment Figure 32 Please contact your local Elster representative for details Figure 26 Support bracket attachment 3 5M 5 5M Horizontal Flow 3 5M 5 5M Vertical Flow 2 Using a 5mm Allen wrench loosely install two M6 socket head cap screws through the support bracket into the meter case c...

Страница 15: ...ng Impellers out of time Retime impellers Impellers contacting body Rotate manually to verify impellers spin freely Low registration Upstream or bypass leak Check all valves for leakage Non registration Broken or binding index odometer Replace odometer Obstruction in meter Remove meter remove obstructions flush meter 15 Troubleshooting probe and leading threads to ensure no pipe dope enters the met...

Страница 16: ...ms and solutions for the safe control and delivery of natural gas across the globe Trusted Brands Elster American Meter Company LLC Elster Perfection Corporation Elster Instromet Elster Canadian Meter Company LLC Elster Gas Depot Elster Meter Services Elster American Meter Company LLC 2221 Industrial Road Nebraska City NE 68410 USA T 1 402 873 8200 F 1 402 873 7616 www elster com gas 2014 by Elste...

Отзывы: