R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

Automation and Control Solutions

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN  55422
customer.honeywell.com

® U.S. Registered Trademark
© 2011 Honeywell International Inc.
65-0109—14    M.S.  Rev. 06-11 
Printed in U.S.A.

Table 3. Flame signal.

a

This minimum or stronger signal can be easily obtained if the detector is correctly installed and positioned to properly sense the 

flame. Obtain this voltage before completing checkout.

b

The flame amplifiers are Ampli-Check® type.

c

Adjust slightly, or face the pipe down, or extend the sight pipe on C7012A,C applications to obtain a maximum flame signal 

reading less than 5.0 volts.

d

The flame signal amplifier circuitry is tested one-half second every five seconds during burner operation and shuts down the 

burner if the amplifier fails (all installations).

e

R7824C Series 2 or greater and R7847C Series 4 or greater, pulse the shutter when the flame signal reaches 1.5 Vdc.

NOTE: R7824C, Series 2 or greater, pulse shutter when sig-

nal of 1.5 Vdc is sensed. Display readings of 0.7 to 

2.4 Vdc are common.

The flame signal for the pilot alone, the main burner flame 

alone, and both together must be steady and a minimum of 

1.25V. If the flame signal is unsteady, or less than the 

minimum acceptable voltage, check the flame detector 

installation and circuitry in the following procedure.

1.

Check the supply voltages at terminals (L1) and L2 (N). 

Make sure the master switch is closed, connections are 

correct, and the power supply is of the correct voltage 

and frequency and is sinusoidal. 

2.

Check the detector wiring for defects including:

a. Incorrect connections.

b. Wrong type of wire.

c. Deteriorated wire.

d. Open circuits.

e. Short circuits.

f. Leakage paths caused by moisture, soot or accu-

mulated dirt.

3.

For a flame rod, make sure:

a. There is enough ground area.

b. The flame rod is properly located in the flame.

c. Temperature at the flame rod insulator is no greater 

than 500°F (260°C).

4.

For all optical detectors, clean the detector viewing 

window, lens, and inside of the sight pipe as applicable. 

5.

With the burner running, check the temperature at the 

detector. If it exceeds the detector maximum rated 

temperature:

a. Add a heat block to stop conducted heat traveling 

up the sight pipe.

b. Add a shield or screen to reflect radiated heat.

c. Add cooling (refer to sight pipe ventilation in the 

detector Instructions).

6.

Make sure that the flame adjustment is not too lean.

7.

Make sure the optical detector is properly sighting the 

flame.

8.

If necessary, resight or reposition the detector. 

9.

If you cannot obtain proper operation, replace the 

plug-in amplifier.

10.

If you cannot yet obtain proper operation, replace the 

flame detector.

IMPORTANT

If you make any changes to the flame detection 

system, repeat all required Checkout tests in 

Checkout section of the Instructions for the 

applicable 7800 SERIES and R7140 Relay Module.

Flame Detector

Flame Signal Amplifier

Minimum Acceptable 

Steady dc Voltage

a

Maximum Expected dc Voltage

Flame Rod 
C7012A,C

c

R7847A,B

b

1.25 Vdc 

5.0 Vdc at Keyboard Display Module 

or on volt-ohmmeter.

C7015A

R7848A,B

b

C7024E,F

R7824C

d,e

C7027A

C7035A

C7044A

R7849A,B

b

C7927

C7962

R7851B

b

C7915

R7852A,B

b

C7061A

R7861A

d

C7076A,D

R7886A

d

C7961E

R7851C

d

Содержание R7824

Страница 1: ...40 Relay Modules The R7849A B Ultraviolet Flame Amplifiers are solid state plug in amplifiers that respond to an ultraviolet signal from a C7027 C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules The R7851B Optical Flame Amplifiers are solid state plug in amplifiers that respond to optical signals from C7927 and C7962 Flam...

Страница 2: ...n the amplifier and relay module selected See Table 1 Plug in to 7800 SERIES and R7140 Relay Module through printed circuit board edge connector keyed for proper orientation Flame signal test jacks measure amplifier flame signal voltage 0 0 to 5 0 Vdc Flame signal strength reading range Color coded label identifies flame detection type Green rectification Red infrared Purple ultraviolet Blue pulse...

Страница 3: ...able The Amplifiers R7847B C R7861A R7886 R7851C or R7852B used with the appropriate flame detector and used in Relay Module EC7810A 20A 30A 40L 50A RM7800 E G L M 30A 38 A B C 40 E G L M 50A 90 A B C D 97 A C 98A is SIL 3 Capable in a properly designed Safety Instrumented System See form number 65 0312 for Certificate Agreement Approvals Underwriters Laboratories Inc Listed File no MP268 Guide no...

Страница 4: ... and R7847C Series 4 or greater pulse the shutter when signal of 1 5 Vdc is sensed Display readings of 0 7 to 2 4 Vdc are common i Order flame rod separately see flame detector Instructions for holder Plug in Flame Signal Amplifiers Applicable Flame Detectors Type Color Self Checking Model Flame Failure Response Time sec a Fuel Type Models Rectification Green Dymanic Self Check R7824Cb c h 3 Gas o...

Страница 5: ...Shock Hazard Can cause severe injury death or property damage Disconnect the power supply before beginning installation More than one power supply disconnection can be involved 1 Align the amplifier circuit board edge connector with the keyed receptacle on the 7800 SERIES and R7140 Relay Module Be sure the amplifier nameplate faces away from the Relay Module 2 Push in the amplifier until the circu...

Страница 6: ...AGE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE CAUTION EQUIPMENT DAMAGE HAZARD INCOR...

Страница 7: ... amplifier and flame detector is used Flame Signal Measurement Fig 4 Flame signal can be measured at the Flame Signal Test Jacks see Fig 4 and at the Keyboard Display Module Measure the flame signal at the appropriate times defined in the Checkout section see applicable 7800 SERIES and R7140 Relay Module Instructions See Table 3 for acceptable and maximum flame signal voltage strengths CAUTION Equ...

Страница 8: ...t and the power supply is of the correct voltage and frequency and is sinusoidal 2 Check the detector wiring for defects including a Incorrect connections b Wrong type of wire c Deteriorated wire d Open circuits e Short circuits f Leakage paths caused by moisture soot or accu mulated dirt 3 For a flame rod make sure a There is enough ground area b The flame rod is properly located in the flame c T...

Отзывы: