R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 AMPLIFIERS FOR 7800 SERIES AND R7140 RELAY MODULES

65-0109—14

4

Table 2. Flame Detection Systems.

a

Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES and R7140 Relay Module.

b

R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors. 

c

Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner oper-

ation and shuts down burner if detection system fails. 

d

Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails. 

e

200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter. Applies 

to R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.

f

Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use 

C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detec-

tion system for appliances with burners that remain on continuously for twenty-four hours or longer.

g

R7847A,B Amplifiers with 0.8/1 second FFRT should 

NOT

 be used with C7012A,C Solid State Ultraviolet Detectors.

h

R7824C Series 2 and greater and R7847C Series 4 or greater, check flame detector system when flame reaches 1.5 Vdc or at 

4.5 seconds, whichever occurs first.

NOTE: R7824C Series 2 or greater and R7847C Series 4 or greater, pulse the shutter when signal of 1.5 Vdc is sensed. Display 

readings of 0.7 to 2.4 Vdc are common.

i

Order flame rod separately; see flame detector Instructions for holder.

Plug-in Flame Signal Amplifiers

Applicable Flame Detectors

Type

Color

Self-Checking

Model

Flame 

Failure 

Response 

Time (sec)

a

Fuel

Type

Models

Rectification Green

Dymanic Self-

Check

R7824C

b,c,h

3

Gas,  oil, 

coal

Ultraviolet (Purple 

Peeper®)

C7024E,F

No

R7847A

g

0.8/1 or 2/3 Gas

Rectifying Flame Rod 
Holders

i

C7004, C7007, C7011 

Complete Assemblies: 

C7008, C7009, Q179

No

R7847A

g

2/3

Gas, oil, 

coal

Ultraviolet (Purple 

Peeper®)

C7012A,C.

Dynamic Ampli-

Check®

R7847B

d,g

0.8/1 or 

2/3

Gas

Rectifying Flame Rod 
Holders

i

C7004, C7007, C7011 

Complete Assemblies: 

C7008, C7009, Q179

Dynamic Ampli-

Check®

R7847B

d,g

2/3 Gas, 

oil, 

coal

Ultraviolet (Purple 

Peeper®)

C7012A,C

Dynamic Self 

Check

R7847C

c,h

3

Gas,  oil, 

coal

Ultraviolet (Purple 

Peeper®)

C7012E,F

Infrared

Red

No

R7848A

2/3

Gas, oil, 

coal

Infrared (Lead 

Sulfide)

C7015

Dynamic Ampli-

Check®

R7848B

d

2/3

Gas, oil, 

coal

Infrared (Lead 

Sulfide)

C7015

Red/

White

No

R7852A

2/3

Gas, oil, 

coal

Infrared (Lead 

Sulfide)

C7915

Dynamic Ampli-

Check®

R7852B

b

2/3

Gas, oil, 

coal

Infrared (Lead 

Sulfide)

C7915

Ultraviolet

Purple No

R7849A

0.8/1 or

2/3

Gas, oil Ultraviolet 

(Minipeeper)

C7027, C7035, C7044

f

Dynamic Ampli-

Check®

R7849B

d

0.8/1 or 

2/3

Gas, oil Ultraviolet 

(Minipeeper)

C7027, C7035, C7044

f

Dynamic Self-

Check

R7861A

c,e

0.8/1 or 

2/3

Gas, oil, 

coal

Ultraviolet

C7061

Blue

Dynamic Self-

Check

R7886A

c,e

2/3

Gas, oil, 

coal

Ultraviolet (Adjustable 

Sensitivity)

C7076

Optical

White

Dymanic Ampli-

Check®

R7851B

0.8/1 or 2/3 Gas, oil, 

coal

Optical (UV, Visible 

Light)

C7927, C7962

Dynamic Self-

Check

R7851C

c

2/3

Gas, oil, 

coal

Optical (UV only)

C7961

Содержание R7824

Страница 1: ...40 Relay Modules The R7849A B Ultraviolet Flame Amplifiers are solid state plug in amplifiers that respond to an ultraviolet signal from a C7027 C7035 or C7044 Ultraviolet Flame Detector to indicate the presence of flame when used with 7800 SERIES and R7140 Relay Modules The R7851B Optical Flame Amplifiers are solid state plug in amplifiers that respond to optical signals from C7927 and C7962 Flam...

Страница 2: ...n the amplifier and relay module selected See Table 1 Plug in to 7800 SERIES and R7140 Relay Module through printed circuit board edge connector keyed for proper orientation Flame signal test jacks measure amplifier flame signal voltage 0 0 to 5 0 Vdc Flame signal strength reading range Color coded label identifies flame detection type Green rectification Red infrared Purple ultraviolet Blue pulse...

Страница 3: ...able The Amplifiers R7847B C R7861A R7886 R7851C or R7852B used with the appropriate flame detector and used in Relay Module EC7810A 20A 30A 40L 50A RM7800 E G L M 30A 38 A B C 40 E G L M 50A 90 A B C D 97 A C 98A is SIL 3 Capable in a properly designed Safety Instrumented System See form number 65 0312 for Certificate Agreement Approvals Underwriters Laboratories Inc Listed File no MP268 Guide no...

Страница 4: ... and R7847C Series 4 or greater pulse the shutter when signal of 1 5 Vdc is sensed Display readings of 0 7 to 2 4 Vdc are common i Order flame rod separately see flame detector Instructions for holder Plug in Flame Signal Amplifiers Applicable Flame Detectors Type Color Self Checking Model Flame Failure Response Time sec a Fuel Type Models Rectification Green Dymanic Self Check R7824Cb c h 3 Gas o...

Страница 5: ...Shock Hazard Can cause severe injury death or property damage Disconnect the power supply before beginning installation More than one power supply disconnection can be involved 1 Align the amplifier circuit board edge connector with the keyed receptacle on the 7800 SERIES and R7140 Relay Module Be sure the amplifier nameplate faces away from the Relay Module 2 Push in the amplifier until the circu...

Страница 6: ...AGE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE FLAME DETECTOR LEADS ARE COLOR CODED THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW MUST BE CONNECTED TO THE G TERMINAL THE UV SENSING TUBE IS POLARITY SENSITIVE CAUTION EQUIPMENT DAMAGE HAZARD INCOR...

Страница 7: ... amplifier and flame detector is used Flame Signal Measurement Fig 4 Flame signal can be measured at the Flame Signal Test Jacks see Fig 4 and at the Keyboard Display Module Measure the flame signal at the appropriate times defined in the Checkout section see applicable 7800 SERIES and R7140 Relay Module Instructions See Table 3 for acceptable and maximum flame signal voltage strengths CAUTION Equ...

Страница 8: ...t and the power supply is of the correct voltage and frequency and is sinusoidal 2 Check the detector wiring for defects including a Incorrect connections b Wrong type of wire c Deteriorated wire d Open circuits e Short circuits f Leakage paths caused by moisture soot or accu mulated dirt 3 For a flame rod make sure a There is enough ground area b The flame rod is properly located in the flame c T...

Отзывы: